Cheat sheet
Backflow Tester Cheat Sheet
Hydraulic Principles
- 30% of exam
- Backflow Types Pressure Hazard Cross-Connection Selection Picker
Assemblies Equipment
- 30% of exam
- RP Assembly DC Assembly PVB SVB Check Valves Troubleshooting
Field Test Procedures
- 20% of exam
- Test Setup RP Test DC Test PVB Test Test Picker
Cross-Connection Control
- 10% of exam
- Containment Isolation Surveys Air Gap Hazard Rating
Field Test Equipment
- 5% of exam
- Differential Gauge Hoses Test Cocks Bleeding Calibration
Codes Regulations
- 5% of exam
- SDWA Purveyor Records Reporting Recertification
Quick Facts
- Exam Backflow Tester
- Bodies ABPA / ASSE
- Written 100 questions
- Time 3 hours
- Pass 70%
- Practical Hands-on testing
- Assemblies RP DC PVB SVB
- Validity 3 years
- Gauge Annual calibration
Two Backflows HY
- Pressure pushes; siphon pulls.
- Backpressure Backsiphonage
Backpressure vs Backsiphonage HY
Backpressure
- Downstream pressure higher
- Pumps/boilers cause
Backsiphonage
- Supply pressure drops
- Vacuum draws back
- Pressure direction decides
Selection Picker HY
- Health hazard → RP or air gap
- Low hazard → DC
- Backpressure exists → RP/DC ( Not PVB )
- Backsiphonage only → PVB/SVB
- Maximum protection → Air gap
- Fixture protection → Isolation
Hydraulics Basics HY
- Backflow Reverse flow
- Backpressure Downstream pressure higher
- Backsiphonage Supply pressure drops
- Static pressure No-flow pressure
- Dynamic pressure Flowing pressure
- Pressure loss Drop across device
RP Parts EQ
- Check, zone, relief, check.
- Check 1 Zone Relief Check 2
RP vs DC EQ
RP
- Relief valve present
- High hazard use
DC
- No relief valve
- Low hazard use
- Health hazard needs RP
Failure Picker EQ
- Reading unstable → Bleed hoses
- Check leaks → Clean seat
- Relief won't open → Inspect diaphragm
- Shutoff leaks → Repair shutoff
- Gauge suspect → Check calibration
- Wrong assembly → Hazard review
RP Assembly EQ
- RP Reduced pressure principle
- Check 1 Creates zone pressure
- Check 2 Prevents outlet return
- Relief valve Vents failed zone
- Zone Reduced pressure area
- Use High hazard protection
PVB vs SVB EQ
PVB
- Vacuum breaker
- May spill water
SVB
- Spill-resistant design
- Vacuum breaker
- Both backsiphonage only
DC Assembly EQ
- DC Double check assembly
- Check 1 First closure point
- Check 2 Second closure point
- Shutoff 1 Inlet isolation
- Shutoff 2 Outlet isolation
- Use Low hazard protection
Device vs Assembly EQ
Device
- Often non-testable
- No test cocks
Assembly
- Field testable
- Has shutoffs/cocks
- Testability matters
PVB SVB EQ
- PVB Pressure vacuum breaker
- SVB Spill-resistant breaker
- Air inlet Opens on vacuum
- Check valve Holds downstream water
- Backpressure Not protected
- Elevation Install above outlets
Troubleshooting EQ
- Debris Fouls check seat
- Scale Restricts movement
- Spring Weak closure force
- Diaphragm Relief valve failure
- Leaky shutoff Invalid test
- Air in hose Unstable reading
Test Start PR
- Identify, isolate, connect, bleed.
- Identify Isolate Connect Bleed
Test Picker PR
- Before connection → Gauge zero
- Hoses attached → Bleed air
- RP assembly → Relief plus checks
- DC assembly → Two checks
- PVB/SVB → Air inlet/check
- Any failure → Repair retest
Test Setup PR
- Permission Notify responsible party
- Flow direction Confirm before testing
- Test cocks Open slowly
- Bleed hoses Remove trapped air
- Gauge zero Check before readings
- Record Document findings
RP Test Logic PR
- Relief opening Must open
- Zone pressure Lower than supply
- Check 1 Holds differential
- Check 2 Holds backpressure
- Shutoff 2 Must be tight
- Fail Repair then retest
DC PVB Tests PR
- DC check 1 Must hold tight
- DC check 2 Must hold tight
- DC shutoff No leakage
- PVB check Holds pressure
- Air inlet Opens to atmosphere
- SVB spill Minimized discharge
Containment vs Isolation CR
Containment
- Service entrance
- Protects public system
Isolation
- Individual fixture
- Protects internal users
- Location decides
Hazard Control CR
- Cross-connection Potable/nonpotable link
- Pollution Aesthetic quality hazard
- Contamination Health hazard
- Containment Service protection
- Isolation Fixture protection
- Air gap Physical separation
Pollution vs Contamination CR
Pollution
- Aesthetic concern
- Non-health hazard
Contamination
- Health concern
- Toxic/pathogenic hazard
- Health risk escalates
Test Kit TE
- Differential gauge Measures pressure difference
- High hose Connect upstream side
- Low hose Connect downstream side
- Bypass hose Equalizes as needed
- Calibration Check yearly
- Needle valves Control gauge flow
Report Basics RE
- Assembly, readings, result, signature.
- Assembly Readings Result Signature
Records Regs RE
- SDWA Drinking water law
- Purveyor Water supplier
- Authority Local program rules
- Report Submit test results
- Serial number Assembly identifier
- Recertify Renew credential
Common Traps
PVB Trap
- Backsiphonage only ≠ Backpressure protection
Hazard Trap
- Pollution ≠ Contamination
Gauge Trap
- Air in hose ≠ True pressure
Shutoff Trap
- Leaky shutoff ≠ Valid test
RP Trap
- Relief valve opens ≠ Relief valve closed
Location Trap
- Containment ≠ Isolation
Last Minute
- 1. Name two backflow types
- 2. Classify hazard first
- 3. Match assembly to hazard
- 4. Confirm flow direction
- 5. Bleed gauge hoses
- 6. Test shutoffs matter
- 7. RP relief must open
- 8. PVB excludes backpressure
- 9. Record serial number
- 10. Repair then retest
Backflow Prevention Assembly Tester
- Practice Questions 100 questions Study Guide 24 topics Cheat Sheet 66 facts Flashcards 50 cards Blogs 2 blogs Free CE Podcast