Cheat sheet

NFPA CFPS Cheat Sheet

Practice this exam

Fire Suppression

  • 22% of exam
  • Sprinkler Systems NFPA 13 Design Water Supply & Pumps Standpipes Clean Agents

Safety in the Built Environment

  • 16% of exam
  • Building Construction Egress & Occupant Load Interior Finish Fire-Resistance

Detection and Alarm

  • 14% of exam
  • Heat Detectors Smoke Detectors NFPA 72 Notification Signals

Fire Prevention

  • 12% of exam
  • Hazardous Materials NFPA 30 Portable Extinguishers Fire Classes

Info & Analysis for Fire Protection

  • 9% of exam
  • Fire Tetrahedron Heat Transfer Fire Dynamics Risk Analysis

Facility Fire Hazard Management

  • 9% of exam
  • NFPA 1600 Pre-Incident Planning Emergency Management Risk Assessment

Organizing for Fire & Rescue Services

  • 9% of exam
  • Incident Command ICS Sections Span of Control NIMS

Confining Fires

  • 9% of exam
  • Fire Barriers Fire Walls Smoke Control Compartmentation

Quick Facts

  • Exam CFPS
  • Credential Certified Fire Protection Specialist
  • Administrator NFPA
  • Questions 100 MCQ
  • Time 3 hours
  • Pass score Not published by NFPA
  • Format Open-book, 21st ed. Handbook only
  • Level Professional (2-6 yrs experience)
  • Blueprint 21st ed., effective Jun 2024

Wet Pipe vs Dry Pipe FI

Wet pipe

  • Always water-filled piping
  • Fastest sprinkler response

Dry pipe

  • Pressurized air or nitrogen
  • Used in freezing areas
  • Heated space vs freezing

Sprinkler System Selection FI

  • Standard indoor, no freeze risk → Wet pipe system
  • Unheated space, freeze risk → Dry pipe system
  • Computer room, accidental discharge risk → Pre-action system
  • High hazard, flammable liquids → Deluge system
  • Small system, limited freeze area → Antifreeze system ( Listed solution only )

Sprinkler System Types FI

  • Wet pipe Water-filled, fastest response
  • Dry pipe Pressurized air, freeze-protected
  • Pre-action Closed heads plus detection interlock
  • Deluge Open heads, simultaneous discharge
  • Antifreeze system Listed solution, small systems

Pre-Action vs Deluge FI

Pre-action

  • Closed sprinkler heads
  • Requires detection interlock

Deluge

  • Open sprinkler heads
  • All heads discharge together
  • Selective vs simultaneous discharge

NFPA 13 Design Parameters FI

  • Light hazard area 225 sq ft max coverage
  • Ordinary hazard area 130 sq ft max coverage
  • Extra hazard area 100 sq ft max coverage
  • Light hazard density 0.10 gpm per sq ft
  • OH1 density 0.15 gpm per sq ft
  • OH2 density 0.20 gpm per sq ft

Water Supply & Pumps FI

  • Fire pump Boosts system water pressure
  • Jockey pump Maintains pressure, prevents cycling
  • Vertical turbine pump Lifts water from below grade
  • Fire hydrant Firefighter water connection point
  • Fire flow Water volume to extinguish

Standpipes & Clean Agents FI

  • Standpipe Class I 100 psi residual, 2.5 in
  • Standpipe Class II 65 psi residual, 1.5 in
  • Main drain test Quarterly per NFPA 25
  • Clean agent (IG-541) Inert gas, no residue

Building Construction Type Selection BU

  • Need highest fire resistance → Type I fire-resistive
  • Noncombustible, lower rating acceptable → Type II construction
  • Combustible interior, masonry exterior → Type III ordinary
  • Exposed heavy structural timber → Type IV heavy timber
  • Wood-frame, fully combustible → Type V construction

Building Construction Types BU

  • Type I Fire-resistive, noncombustible frame
  • Type II Noncombustible, lower fire rating
  • Type III Ordinary: masonry walls, wood joists
  • Type IV Heavy timber, exposed structural members
  • Type V Wood frame, fully combustible

Egress, Occupancy & Finish BU

  • Egress door width 32 in minimum clear opening
  • Level egress factor 0.2 in/person, non-sprinklered
  • Business occupant load 150 sq ft per person
  • Class A finish Flame spread index 0-25
  • Class B finish Flame spread index 26-75
  • Fire barrier rating 1 hour minimum

Ionization vs Photoelectric DE

Ionization

  • Detects fast flaming fires
  • Small combustion particles

Photoelectric

  • Detects smoldering fires
  • Large visible smoke particles
  • Flaming fire vs smoldering fire

Heat vs Smoke Detector Choice DE

  • Dusty or high-humidity area → Heat detector ( Avoids false alarms )
  • Rapid fire growth expected → Rate-of-rise detector
  • Fast flaming fire risk → Ionization smoke detector
  • Smoldering fire risk → Photoelectric smoke detector
  • HVAC duct air stream → Duct smoke detector

Detection Devices (NFPA 72) DE

  • Fixed-temp heat detector Activates at set temperature
  • Rate-of-rise detector Triggers on rapid temp rise
  • Ionization detector Best for fast flaming fires
  • Photoelectric detector Best for smoldering fires
  • Duct smoke detector Samples air in HVAC ducts
  • Smoke detector spacing 30 ft nominal, flat ceiling
  • 0.7 spacing method 21 ft max to any point

Notification & Signals DE

  • Audible signal minimum 15 dBA above ambient
  • Sleeping area minimum 75 dBA at pillow
  • Temporal-3 (T3) Standard fire evacuation signal
  • Temporal-4 (T4) Carbon monoxide alarm signal
  • FACP Central alarm monitoring panel

PASS Extinguisher Technique FI

  • Pull, aim, squeeze, and sweep
  • Pull: safety pin free Aim: at fire base Squeeze: handle lever down Sweep: side to side

Fire Extinguisher Class Selection FI

  • Wood, paper, cloth fire → Class A extinguisher
  • Flammable liquid fire → Class B extinguisher
  • Energized electrical fire → Class C extinguisher
  • Combustible metal fire → Class D extinguisher
  • Commercial kitchen grease fire → Class K extinguisher

Hazardous Materials & NFPA 30/704 FI

  • Class I liquid Flash point below 100°F
  • Class II liquid Flash point 100-140°F
  • Class IIIA liquid Flash point 140-200°F
  • Class IIIB liquid Flash point 200°F or higher
  • Storage cabinet max 120 gal Class I/II/IIIA
  • SDS format 16-section GHS standard
  • NFPA 704 diamond Health, flammability, instability, special

Fire Classes & Extinguishers FI

  • Class A fire Ordinary combustibles: wood, paper
  • Class B fire Flammable and combustible liquids
  • Class C fire Energized electrical equipment
  • Class D fire Combustible metals like magnesium
  • Class K fire Commercial cooking oils, fats
  • ABC dry chemical Interrupts chain reaction step
  • Class A travel distance 75 ft maximum

Fire Tetrahedron IN

  • Fuel, oxygen, heat, and chain reaction
  • Fuel: combustible material Oxygen: supports combustion Heat: ignition energy source Chain reaction: sustains fire

Flashover vs Backdraft IN

Flashover

  • Ventilated, radiant-heat driven
  • Gradual ignition of surfaces

Backdraft

  • Oxygen-starved, ventilation-limited fire
  • Explosive on sudden air
  • Radiant growth vs oxygen-starved explosion

Fire Science Fundamentals IN

  • Fire tetrahedron Fuel, oxygen, heat, chain reaction
  • Conduction Heat transfer through direct contact
  • Convection Heat transfer via fluid movement
  • Radiation Heat transfer via electromagnetic waves
  • Flash point Lowest temp forming ignitable vapor
  • Autoignition temperature Ignites without external spark
  • Smoldering Flameless, low-temperature combustion

Stages of Fire Growth IN

  • Incipient, growth, flashover, fully developed, decay
  • Incipient: ignition just starts Growth: heat release climbing Flashover: near 600°C radiant Decay: fuel or oxygen depletes

Fire Development Stages IN

  • Incipient stage Ignition begins, minimal heat
  • Growth stage Heat release rate increasing
  • Flashover Simultaneous ignition near 600°C
  • Fully developed Maximum heat release, ventilation-limited
  • Decay stage Fuel or oxygen depleting
  • Backdraft Explosive ignition on sudden ventilation

Risk, Modeling & Cause IN

  • Fire risk assessment Identify hazards, evaluate risk
  • Fire modeling tools FDS, CFAST, BRANZFIRE
  • Fire cause categories Natural, accidental, incendiary, undetermined
  • Decomposition Break complex problem into parts

RACE Emergency Response FA

  • Rescue, Activate, Confine, Extinguish or Evacuate
  • Rescue: remove occupants Activate: sound the alarm Confine: close doors Extinguish or evacuate area

Emergency & Risk Management FA

  • NFPA 1600 Mitigation, preparedness, response, recovery
  • NFPA 1620 Pre-incident plan for responders
  • CWPP Community Wildfire Protection Plan
  • Defend-in-place Occupants stay in safe zone
  • Emergency plan General strategy, not tasks
  • Post-incident analysis Reviews what went wrong

Strike Team vs Task Force FI

Strike team

  • Same resource type only
  • Example: five fire engines

Task force

  • Mixed resource types
  • Assembled for one mission
  • Uniform resources vs mixed resources

Incident Command System (ICS) FI

  • Incident Commander Overall responsibility for response
  • Operations Section Executes tactical objectives
  • Planning Section Develops incident action plan
  • Logistics Section Provides resources and support
  • Finance/Admin Section Tracks incident costs
  • Span of control 3 to 7 resources

Fire Wall vs Fire Barrier CO

Fire wall

  • Stands alone structurally
  • Higher rating: 2-4 hr

Fire barrier

  • Relies on building structure
  • Minimum rating: 1 hr
  • Standalone vs structure-dependent

Compartmentation & Smoke Control CO

  • Fire barrier 1 hour minimum rating
  • Fire wall Stands alone if structure collapses
  • Fire-rated duct Stops fire/smoke via HVAC
  • Smoke damper Controls smoke in ductwork
  • Smoke barrier Contains smoke movement
  • Engineered smoke control Pressurization plus exhaust system

Common Traps

Flashover ≠ Backdraft

  • Flashover: ventilated growth stage ≠ Backdraft: oxygen-starved sudden explosion

Fire Wall ≠ Fire Barrier

  • Wall: standalone structural stability ≠ Barrier: relies on structure

MSDS ≠ SDS

  • MSDS: old pre-GHS format ≠ SDS: current GHS 16-section

Combustible ≠ Flammable

  • Combustible: flash point 100°F+ ≠ Flammable: flash point below 100°F

Jockey Pump ≠ Fire Pump

  • Jockey: maintains pressure only ≠ Fire pump: primary suppression flow

Class A ≠ Class K

  • Class A: ordinary combustibles ≠ Class K: cooking oil fires

Last Minute

  • 1. Weights: Suppression 22%, Built-Env 16%
  • 2. Detection & Alarm 14% of exam
  • 3. Fire tetrahedron: fuel, oxygen, heat, reaction
  • 4. Flashover ignites near 600°C
  • 5. Class A-K matches fuel type
  • 6. Wet pipe = always water-filled
  • 7. Dry pipe = freeze-prone areas
  • 8. Deluge = open heads, simultaneous
  • 9. NFPA 13 light: 0.10 gpm/sf
  • 10. Only 21st-ed Handbook allowed open-book
  • 11. Passing score not published (NFPA)
  • 12. Span of control: 3 to 7

CFPS Certified Fire Protection Specialist

  • Practice Questions 140 questions Study Guide 35 topics Cheat Sheet 92 facts Flashcards 50 cards Shorts 1 short Videos 1 video Blogs 1 blog Free CE Podcast