Administration

  • 25% of exam
  • NFPA Inspector Credentials Violation Notice Elements Legal Authority Terms Common Permit Triggers Violation Response Picker

Fire Protection Systems & Equipment

  • 30% of exam
  • Sprinkler System Types Sprinkler Temperature Colors NFPA 25 ITM Intervals NFPA 72 Alarm Facts Extinguisher Placement Rules Standpipes and FDCs

Hazardous Substances & Materials

  • 15% of exam
  • Flammable Liquid Classes NFPA 704 Diamond Hazmat Storage Limits Hot Work and Dust

Occupancy Requirements

  • 30% of exam
  • Construction Types Occupant Load Factors Egress Dimensions Travel and Dead Ends Walls and Barriers Exit Signs and Lighting

Quick Facts

  • Exam NFPA CFI-I (retiring)
  • Items 100 multiple-choice
  • Time 4 hours maximum
  • Format Open book, Prometric center
  • Pass Not published by NFPA
  • Fee $499 application; $249 retest
  • Recert 60 points / 3 years
  • Blueprint NFPA 1031 (2014) Ch. 4
  • Practicum 17 activities plus exam
  • Prerequisite High school diploma or equivalent
  • Replacement CFI: 72 items, 3 hours
  • Last exam day June 30, 2027

Fire Inspector I vs II AD

Inspector I

  • Routine field inspections
  • Recognizes permit need
  • Recognizes plan review need
  • NFPA 1031 Chapter 4

Inspector II

  • Complex facility inspections
  • Processes permits
  • Performs plans review
  • NFPA 1031 Chapter 5
  • Recognize versus process

Violation Response Picker AD

  • Minor housekeeping issue → Notice with deadline ( Re-inspect later )
  • Exit locked or blocked → Immediate abatement ( Imminent hazard )
  • Assembly overcrowded → Reduce occupant count ( Posted load governs )
  • System out of service → Require fire watch ( Impairment program )
  • Owner refuses entry → Administrative warrant ( Camara rule )
  • Owner disputes interpretation → Refer to appeals ( Board decides )
  • Alternative method offered → Equivalency request ( Applicant proves it )
  • Work exceeds maintenance → Refer to plan review ( Inspector II task )

NFPA Inspector Credentials AD

  • CFI-I Inspector I, retiring 2027
  • CFI-II Inspector II, retiring 2027
  • CFI New single inspector level
  • CFRI First responder inspector level
  • Pro Board Accredits agencies, not people
  • IFSAC Accredits agencies and programs
  • NFPA 1031 2014 standard, Chapters 4-5
  • NFPA 1030 2024 consolidated standard

Pro Board vs IFSAC AD

Pro Board

  • Accredits certifying agencies
  • Founded 1972
  • National certification registry

IFSAC

  • Certificate and degree assemblies
  • Accredits agencies and programs
  • International reciprocity
  • Neither tests individuals

Violation Notice Elements AD

  • Code cited Edition and section number
  • Condition What was actually observed
  • Location Exact room or area
  • Correction Required action to comply
  • Deadline Specific compliance date
  • Re-inspection Verify and document closure
  • Signature Inspector and receiving party
  • Weak finding "Housekeeping poor" is unenforceable

NFPA 1031 vs NFPA 1030 AD

NFPA 1031

  • 2014 edition
  • Inspector I, II, III
  • Plan examiner I, II

NFPA 1030

  • 2024 edition
  • First responder inspector added
  • Inspector III removed
  • Existing certifications stay valid

Legal Authority Terms AD

  • AHJ Approves, interprets, enforces code
  • Adoption by reference Ordinance adopts code text
  • Police power State delegates to municipality
  • Camara v. Municipal Court Warrant needed without consent
  • See v. City of Seattle Same rule, commercial premises
  • Administrative warrant Neutral inspection plan justifies
  • Due process Notice, hearing, appeal rights
  • Board of appeals Hears interpretation and equivalency
  • Equivalency Applicant proves equal safety
  • Variance Relief for one property

Common Permit Triggers AD

  • Hot work Welding, cutting, grinding
  • Assembly use More than 50 persons
  • Flammable liquids Over 5 gallons indoors
  • Spray finishing Booths and spray rooms
  • Hazmat above MAQ Exceeds control area limit
  • Construction permit Install or modify systems
  • Operational permit Conduct a hazardous process
  • Permit status Revocable, non-transferable privilege

Extinguisher Use: PASS SY

  • Pull, Aim, Squeeze, Sweep
  • Pull the pin Aim at base Squeeze the lever Sweep side to side

Fire Detection vs Notification SY

Detection

  • Initiating devices
  • Smoke, heat, pull station
  • Sends the signal in

Notification

  • Horns, strobes, speakers
  • Warns the occupants
  • Sends the signal out
  • Input versus output

Extinguisher Class Picker SY

  • Wood, paper, cloth → Class A ( 75 feet travel )
  • Gasoline, oil, solvent → Class B ( 30 or 50 feet )
  • Energized electrical → Class C ( Non-conductive agent )
  • Power disconnected → Reclassify A or B ( Fuel decides )
  • Magnesium, titanium, sodium → Class D ( Dry powder only )
  • Cooking oil, fat → Class K ( 30 feet travel )
  • Commercial fryer present → Class K plus hood ( Wet chemical )

Sprinkler System Types SY

  • Wet pipe Water always in pipe
  • Dry pipe Air holds water back
  • Preaction, single interlock Detection admits water first
  • Preaction, double interlock Detection plus sprinkler needed
  • Deluge Open heads, all discharge
  • Antifreeze loop Wet system, freezing areas
  • Dry water delivery 60 seconds where required
  • Quick-opening device Accelerator or exhauster
  • OS&Y, PIV Control valves, locked open
  • Deflector clearance 18 inches below, storage

Gauge Check Rhythm SY

  • Dry weekly, wet monthly, drain annually
  • Dry, preaction, deluge: weekly Wet system gauge: monthly Main drain: annual Internal pipe: 5 years

Standpipe Class I vs II SY

Class I

  • 2½ in. outlets
  • Fire department use
  • 100 psi most remote

Class II

  • 1½ in. hose stations
  • Occupant or trained use
  • 65 psi most remote
  • Class III has both

ITM Interval Picker SY

  • Dry system gauge → Weekly ( Air pressure )
  • Wet system gauge → Monthly ( Water pressure )
  • Supervised control valve → Quarterly ( Inspect only )
  • Vane waterflow switch → Semiannual ( Test it )
  • Main drain → Annual ( Each riser )
  • Dry valve full trip → Every 3 years ( Partial annually )
  • Internal pipe check → Every 5 years ( Obstruction, corrosion )
  • Electric pump churn → Monthly ( 10 minutes )
  • Diesel pump churn → Weekly ( 30 minutes )

Sprinkler Temperature Colors SY

  • Ordinary 135-170°F, uncolored or black
  • Intermediate 175-225°F, white frame
  • High 250-300°F, blue frame
  • Extra high 325-375°F, red frame
  • Orange bulb 135°F rating
  • Red bulb 155°F rating
  • Yellow bulb 175°F rating
  • Green bulb 200°F rating
  • Blue bulb 286°F rating

Inspection vs Testing SY

Inspection

  • Visual, nothing operated
  • Confirms nothing changed
  • Often owner performed

Testing

  • Component is operated
  • Confirms it functions
  • Qualified person required
  • Maintenance repairs or replaces

NFPA 25 ITM Intervals SY

  • Dry, preaction gauges Weekly inspection
  • Wet system gauges Monthly inspection
  • Sealed control valves Weekly inspection
  • Locked control valves Monthly inspection
  • Supervised control valves Quarterly inspection
  • Fire department connection Quarterly inspection
  • Main drain test Annually at each riser
  • Waterflow switch test Semiannual, vane or pressure
  • Dry valve trip test Annual partial, 3-year full
  • Internal pipe assessment Every 5 years
  • Antifreeze concentration Tested annually
  • Electric pump churn Monthly no-flow test
  • Diesel pump churn Weekly no-flow test
  • Fire pump flow test Annual, three curve points
  • Pump at 150% 65% of rated pressure
  • ITM responsibility Building owner, always

NFPA 72 Alarm Facts SY

  • Secondary power 24 hours standby, 5 alarm
  • Voice system power 24 hours standby, 15 alarm
  • Pull station height 42-48 inches above floor
  • Pull station location Within 5 feet of exit
  • Pull station spacing Travel under 200 feet
  • Public mode audible 15 dBA above average ambient
  • Sleeping area audible 75 dBA at pillow
  • Low-frequency signal 520 Hz, sleeping rooms
  • Strobe flash rate 1 to 2 Hz
  • Rate-of-rise detector 12-15°F per minute
  • Photoelectric detector Better for smoldering fires
  • Ionization detector Better for flaming fires
  • Duct smoke detector Required above 2,000 CFM
  • Annual test All devices, 100 percent

Extinguisher Placement Rules SY

  • Class A travel 75 feet maximum
  • Class B travel 30 or 50 feet
  • Class C travel Follows A or B
  • Class D travel 75 feet maximum
  • Class K travel 30 feet from appliance
  • 40 lb or less Top within 5 feet
  • Over 40 lb Top within 3.5 feet
  • Floor clearance At least 4 inches
  • Monthly inspection Quick visual check
  • Annual maintenance Technician thorough exam
  • 6-year internal exam Stored-pressure dry chemical
  • Hydrostatic test 5 or 12 years
  • 1-A rating About 1.25 gallons water
  • 20-B rating Square feet, liquid fire

Standpipes and FDCs SY

  • Class I 2½ in., fire department
  • Class II 1½ in., occupant use
  • Class III Both hose connection sizes
  • Class I pressure 100 psi, most remote
  • Class II pressure 65 psi, most remote
  • Class I flow 500 gpm, first standpipe
  • Each added standpipe 250 gpm more
  • Manual dry standpipe Fire department supplies water
  • FDC clear space 3 feet all around
  • FDC inlet height 18 to 48 inches
  • FDC signage States systems it serves
  • Dry standpipe hydrostatic Every 5 years

NFPA 704 Positions HA

  • Blue left, red top, yellow right, white bottom
  • Blue: health Red: flammability Yellow: instability White: special hazard

Flammable vs Combustible Liquid HA

Flammable

  • Class I only
  • Flash below 100°F
  • Gasoline, acetone, ether

Combustible

  • Class II and III
  • Flash 100°F or above
  • Diesel, heating oil
  • 100°F flash point splits

Hazmat Compliance Picker HA

  • Flash below 100°F → Flammable, Class I ( NFPA 30 )
  • Flash 100-140°F → Combustible, Class II ( Diesel fuel )
  • Storage exceeds MAQ → Require permit ( Or add control area )
  • Liquids in cabinet → 60 gallons maximum ( Class I and II )
  • Reading 704 diamond → Blue, red, yellow, white ( Left, top, right, bottom )
  • Cylinder lying loose → Cite securement violation ( Upright and capped )

Flammable Liquid Classes HA

  • Class IA Flash under 73°F, boil under 100°F
  • Class IB Flash under 73°F, boil 100°F up
  • Class IC Flash 73-100°F
  • Class II Flash 100-140°F
  • Class IIIA Flash 140-200°F
  • Class IIIB Flash 200°F and above
  • Flammable liquid Class I only
  • Combustible liquid Class II and III
  • Gasoline Class IB example
  • Diesel fuel Class II example
  • Motor oil Class IIIB example
  • Vapor density Above 1.0 sinks, travels

Flash Point Split HA

  • Under 100°F flammable, at or above combustible
  • Class IA, IB, IC Class II: 100-140°F Class IIIA: 140-200°F Class IIIB: 200°F up

NFPA 704 Diamond HA

  • Blue, left Health hazard
  • Red, top Flammability hazard
  • Yellow, right Instability hazard
  • White, bottom Special hazard symbol
  • Rating 0 Minimal hazard
  • Rating 4 Severe hazard
  • OX Oxidizer
  • W with slash Reacts with water
  • SA Simple asphyxiant gas
  • GHS scale Category 1 is worst
  • Safety data sheet 16 standard sections

Hazmat Storage Limits HA

  • Storage cabinet 60 gallons, Class I-II
  • Cabinet, Class III 120 gallons maximum
  • Control area Rated space holding MAQ
  • Cabinet increase MAQ doubled
  • Sprinkler increase MAQ doubled again
  • Both increases Four times baseline MAQ
  • Secondary containment 110% of largest container
  • LP-gas relief valve Opens near 250 psi
  • Compressed cylinders Upright, secured, capped
  • Cryogenic expansion Roughly 700 to 800 times

Hot Work and Dust HA

  • Hot work clearance 35 feet of combustibles
  • IFC fire watch 30 minutes after work
  • NFPA 51B fire watch 60 minutes after work
  • Post-watch monitoring Up to 3 more hours
  • Dust accumulation 1/32 inch over 5%
  • Dust pentagon Adds dispersion and confinement
  • Dust hazard analysis Required by NFPA 652
  • Spray booth airflow 100 feet per minute
  • Spray booth wiring Class I, Division 1

Means of Egress Parts OC

  • Access, exit, discharge, then public way
  • Exit access: to the door Exit: rated enclosure Exit discharge: to outside Public way: 10 feet

Exit Access vs Exit OC

Exit access

  • Room to the exit door
  • Usually not rated
  • Travel distance applies

Exit

  • Rated enclosure
  • 1 hour under 4 stories
  • 2 hours at 4 stories
  • Discharge ends at public way

Egress Requirement Picker OC

  • Need occupant load → Area divided by factor ( Net or gross )
  • Need stair width → Load times 0.3 inch ( NFPA 101 )
  • Need door width → Load times 0.2 inch ( Level component )
  • Load over 500 → Three exits ( Minimum count )
  • Load over 1,000 → Four exits ( Minimum count )
  • Checking exit spacing → Half the diagonal ( One third sprinklered )
  • Corridor serves 50 → 44 inches clear ( 36 under fifty )
  • Door serves 50 → Swing with travel ( Panic hardware likely )

Construction Types OC

  • Type I Noncombustible, fire-resistive frame
  • Type II Noncombustible, lower ratings
  • Type III Masonry walls, wood interior
  • Type IV Heavy timber, no concealed
  • Type V Wood frame throughout
  • Subtype A Protected, higher ratings
  • Subtype B Unprotected, lower ratings
  • Type IV columns 8x8 inch nominal minimum
  • Rating test ASTM E119 or UL 263
  • Unexposed side limit 250°F average rise
  • Firestop F-rating Resists flame passage
  • Firestop T-rating Limits temperature rise

Egress Width Factors OC

  • Stairs 0.3, level 0.2, per occupant
  • Stairs: 0.3 inch Level: 0.2 inch Multiply by occupant load Then check minimum widths

Fire Wall vs Fire Barrier OC

Fire wall

  • Foundation through roof
  • Structurally independent
  • Creates separate buildings

Fire barrier

  • Floor slab to slab
  • Not structurally independent
  • Shafts, exits, separations
  • One side may collapse

Occupant Load Factors OC

  • Assembly, concentrated 7 net square feet
  • Assembly, less concentrated 15 net square feet
  • Classroom 20 net square feet
  • Shops, laboratories 50 net square feet
  • Day care 35 net square feet
  • Business 150 gross square feet
  • Mercantile, street floor 30 gross square feet
  • Mercantile, above street 60 gross square feet
  • Health care sleeping 120 gross square feet
  • Residential 200 gross square feet
  • Industrial 100 gross square feet
  • Storage in mercantile 300 gross square feet
  • Storage, other occupancies 500 gross square feet
  • Net versus gross Net excludes walls, fixtures

NFPA 101 vs IBC Width OC

NFPA 101

  • 0.3 inch stairs
  • 0.2 inch level components
  • Table 7.3.3.1

IBC

  • 0.3 inch stairways
  • 0.2 inch other components
  • Reduced with sprinkler, voice
  • Check the adopted code

Egress Dimensions OC

  • Stair capacity factor 0.3 inch per occupant
  • Level capacity factor 0.2 inch per occupant
  • Corridor, 50 or more 44 inches clear
  • Corridor, under 50 36 inches clear
  • Door clear width 32 inches minimum
  • Door leaf maximum 48 inches wide
  • Two exits Required for most spaces
  • Three exits Over 500 occupants
  • Four exits Over 1,000 occupants
  • Exit remoteness Half the overall diagonal
  • Sprinklered remoteness One third the diagonal
  • Door swing With travel at 50
  • Unlatch force 15 pounds maximum
  • Panic hardware IBC 50; NFPA 101 100

Travel and Dead Ends OC

  • Business travel 200 feet, 300 sprinklered
  • Assembly travel 200 feet, 250 sprinklered
  • High hazard travel 75 feet, 100 sprinklered
  • Common path 75 feet typical limit
  • Common path, sprinklered 100 feet, business
  • Dead-end corridor 20 feet typical limit
  • Dead end, sprinklered 50 feet allowed
  • Public way 10 feet clear minimum

Walls and Barriers OC

  • Fire wall Foundation through roof, independent
  • Fire wall parapet 30 inches above roof
  • Fire barrier Floor slab to slab
  • Fire partition Corridors and tenant separations
  • Smoke barrier Continuous, limits smoke movement
  • Smoke partition Resists smoke, usually unrated
  • Exit enclosure, under 4 1-hour rating
  • Exit enclosure, 4 up 2-hour rating
  • Fire damper 165°F fusible link typical
  • Smoke damper Closed by smoke detector

Exit Signs and Lighting OC

  • Exit sign letters 6 inches high minimum
  • Letter stroke 3/4 inch minimum
  • Viewing distance 100 feet maximum
  • Emergency light duration 90 minutes minimum
  • Initial illumination 1 foot-candle average
  • End illumination 0.6 foot-candle average
  • Transfer time 10 seconds maximum
  • Class A finish Flame spread 0-25
  • Class B finish Flame spread 26-75
  • Class C finish Flame spread 76-200
  • Smoke developed limit 450 for all classes
  • Decorative materials NFPA 701 flame propagation

Occupancy Classifications OC

  • Assembly 50 or more gathering
  • Educational 6 or more, through 12th
  • Day care Clients receiving supervised care
  • Health care Occupants incapable of self-preservation
  • Detention, correctional Occupants under restraint
  • Residential Sleeping, not health care
  • Mercantile Display and sale
  • Business Offices and services
  • Industrial Manufacturing and processing
  • Storage Goods, not manufacturing

Common Traps

Adopted edition, not newest

  • Cite the adopted edition ≠ A newer edition is unenforceable

Business factor changed

  • NFPA 101 2018: 150 gross ≠ Older editions used 100

Instability, not reactivity

  • Yellow means instability ≠ 704 dropped reactivity wording

Recognize versus perform

  • Inspector I recognizes the need ≠ Inspector II performs review

Fire watch duration differs

  • IFC says 30 minutes ≠ NFPA 51B says 60 minutes

Inspection is not testing

  • Inspection is visual only ≠ Testing operates the device

Pro Board sets no score

  • Pro Board accredits agencies ≠ Agencies set their cut scores

Class III is combined

  • Class III has both sizes ≠ Not a third pressure

GHS scale is inverted

  • NFPA 704: 4 is worst ≠ GHS: Category 1 worst

Clearance is below deflector

  • 18 inches below deflector ≠ Not measured from ceiling

CFI-I is being retired

  • No new applications after 2026 ≠ Testing ends June 30, 2027

Last Minute

  • 1. Systems 30%, Occupancy 30%, Administration 25%
  • 2. Hazardous materials is smallest, 15%
  • 3. Exam is open book, 4 hours
  • 4. Stairs 0.3 inch, level 0.2
  • 5. Business occupant factor is 150 gross
  • 6. Three exits above 500 occupants
  • 7. Four exits above 1,000 occupants
  • 8. Class A extinguisher within 75 feet
  • 9. Class K within 30 feet
  • 10. Flammable liquid flashes below 100°F
  • 11. 704: blue, red, yellow, white
  • 12. Main drain test is annual
  • 13. Dead end 20 feet, 50 sprinklered
  • 14. Notice needs edition, section, deadline
  • 15. Inspector II does plans review

Certified Fire Inspector I/II