Cheat sheet
Fire Inspector I/II Cheat Sheet
Administration
- 25% of exam
- NFPA Inspector Credentials Violation Notice Elements Legal Authority Terms Common Permit Triggers Violation Response Picker
Fire Protection Systems & Equipment
- 30% of exam
- Sprinkler System Types Sprinkler Temperature Colors NFPA 25 ITM Intervals NFPA 72 Alarm Facts Extinguisher Placement Rules Standpipes and FDCs
Hazardous Substances & Materials
- 15% of exam
- Flammable Liquid Classes NFPA 704 Diamond Hazmat Storage Limits Hot Work and Dust
Occupancy Requirements
- 30% of exam
- Construction Types Occupant Load Factors Egress Dimensions Travel and Dead Ends Walls and Barriers Exit Signs and Lighting
Quick Facts
- Exam NFPA CFI-I (retiring)
- Items 100 multiple-choice
- Time 4 hours maximum
- Format Open book, Prometric center
- Pass Not published by NFPA
- Fee $499 application; $249 retest
- Recert 60 points / 3 years
- Blueprint NFPA 1031 (2014) Ch. 4
- Practicum 17 activities plus exam
- Prerequisite High school diploma or equivalent
- Replacement CFI: 72 items, 3 hours
- Last exam day June 30, 2027
Fire Inspector I vs II AD
Inspector I
- Routine field inspections
- Recognizes permit need
- Recognizes plan review need
- NFPA 1031 Chapter 4
Inspector II
- Complex facility inspections
- Processes permits
- Performs plans review
- NFPA 1031 Chapter 5
- Recognize versus process
Violation Response Picker AD
- Minor housekeeping issue → Notice with deadline ( Re-inspect later )
- Exit locked or blocked → Immediate abatement ( Imminent hazard )
- Assembly overcrowded → Reduce occupant count ( Posted load governs )
- System out of service → Require fire watch ( Impairment program )
- Owner refuses entry → Administrative warrant ( Camara rule )
- Owner disputes interpretation → Refer to appeals ( Board decides )
- Alternative method offered → Equivalency request ( Applicant proves it )
- Work exceeds maintenance → Refer to plan review ( Inspector II task )
NFPA Inspector Credentials AD
- CFI-I Inspector I, retiring 2027
- CFI-II Inspector II, retiring 2027
- CFI New single inspector level
- CFRI First responder inspector level
- Pro Board Accredits agencies, not people
- IFSAC Accredits agencies and programs
- NFPA 1031 2014 standard, Chapters 4-5
- NFPA 1030 2024 consolidated standard
Pro Board vs IFSAC AD
Pro Board
- Accredits certifying agencies
- Founded 1972
- National certification registry
IFSAC
- Certificate and degree assemblies
- Accredits agencies and programs
- International reciprocity
- Neither tests individuals
Violation Notice Elements AD
- Code cited Edition and section number
- Condition What was actually observed
- Location Exact room or area
- Correction Required action to comply
- Deadline Specific compliance date
- Re-inspection Verify and document closure
- Signature Inspector and receiving party
- Weak finding "Housekeeping poor" is unenforceable
NFPA 1031 vs NFPA 1030 AD
NFPA 1031
- 2014 edition
- Inspector I, II, III
- Plan examiner I, II
NFPA 1030
- 2024 edition
- First responder inspector added
- Inspector III removed
- Existing certifications stay valid
Legal Authority Terms AD
- AHJ Approves, interprets, enforces code
- Adoption by reference Ordinance adopts code text
- Police power State delegates to municipality
- Camara v. Municipal Court Warrant needed without consent
- See v. City of Seattle Same rule, commercial premises
- Administrative warrant Neutral inspection plan justifies
- Due process Notice, hearing, appeal rights
- Board of appeals Hears interpretation and equivalency
- Equivalency Applicant proves equal safety
- Variance Relief for one property
Common Permit Triggers AD
- Hot work Welding, cutting, grinding
- Assembly use More than 50 persons
- Flammable liquids Over 5 gallons indoors
- Spray finishing Booths and spray rooms
- Hazmat above MAQ Exceeds control area limit
- Construction permit Install or modify systems
- Operational permit Conduct a hazardous process
- Permit status Revocable, non-transferable privilege
Extinguisher Use: PASS SY
- Pull, Aim, Squeeze, Sweep
- Pull the pin Aim at base Squeeze the lever Sweep side to side
Fire Detection vs Notification SY
Detection
- Initiating devices
- Smoke, heat, pull station
- Sends the signal in
Notification
- Horns, strobes, speakers
- Warns the occupants
- Sends the signal out
- Input versus output
Extinguisher Class Picker SY
- Wood, paper, cloth → Class A ( 75 feet travel )
- Gasoline, oil, solvent → Class B ( 30 or 50 feet )
- Energized electrical → Class C ( Non-conductive agent )
- Power disconnected → Reclassify A or B ( Fuel decides )
- Magnesium, titanium, sodium → Class D ( Dry powder only )
- Cooking oil, fat → Class K ( 30 feet travel )
- Commercial fryer present → Class K plus hood ( Wet chemical )
Sprinkler System Types SY
- Wet pipe Water always in pipe
- Dry pipe Air holds water back
- Preaction, single interlock Detection admits water first
- Preaction, double interlock Detection plus sprinkler needed
- Deluge Open heads, all discharge
- Antifreeze loop Wet system, freezing areas
- Dry water delivery 60 seconds where required
- Quick-opening device Accelerator or exhauster
- OS&Y, PIV Control valves, locked open
- Deflector clearance 18 inches below, storage
Gauge Check Rhythm SY
- Dry weekly, wet monthly, drain annually
- Dry, preaction, deluge: weekly Wet system gauge: monthly Main drain: annual Internal pipe: 5 years
Standpipe Class I vs II SY
Class I
- 2½ in. outlets
- Fire department use
- 100 psi most remote
Class II
- 1½ in. hose stations
- Occupant or trained use
- 65 psi most remote
- Class III has both
ITM Interval Picker SY
- Dry system gauge → Weekly ( Air pressure )
- Wet system gauge → Monthly ( Water pressure )
- Supervised control valve → Quarterly ( Inspect only )
- Vane waterflow switch → Semiannual ( Test it )
- Main drain → Annual ( Each riser )
- Dry valve full trip → Every 3 years ( Partial annually )
- Internal pipe check → Every 5 years ( Obstruction, corrosion )
- Electric pump churn → Monthly ( 10 minutes )
- Diesel pump churn → Weekly ( 30 minutes )
Sprinkler Temperature Colors SY
- Ordinary 135-170°F, uncolored or black
- Intermediate 175-225°F, white frame
- High 250-300°F, blue frame
- Extra high 325-375°F, red frame
- Orange bulb 135°F rating
- Red bulb 155°F rating
- Yellow bulb 175°F rating
- Green bulb 200°F rating
- Blue bulb 286°F rating
Inspection vs Testing SY
Inspection
- Visual, nothing operated
- Confirms nothing changed
- Often owner performed
Testing
- Component is operated
- Confirms it functions
- Qualified person required
- Maintenance repairs or replaces
NFPA 25 ITM Intervals SY
- Dry, preaction gauges Weekly inspection
- Wet system gauges Monthly inspection
- Sealed control valves Weekly inspection
- Locked control valves Monthly inspection
- Supervised control valves Quarterly inspection
- Fire department connection Quarterly inspection
- Main drain test Annually at each riser
- Waterflow switch test Semiannual, vane or pressure
- Dry valve trip test Annual partial, 3-year full
- Internal pipe assessment Every 5 years
- Antifreeze concentration Tested annually
- Electric pump churn Monthly no-flow test
- Diesel pump churn Weekly no-flow test
- Fire pump flow test Annual, three curve points
- Pump at 150% 65% of rated pressure
- ITM responsibility Building owner, always
NFPA 72 Alarm Facts SY
- Secondary power 24 hours standby, 5 alarm
- Voice system power 24 hours standby, 15 alarm
- Pull station height 42-48 inches above floor
- Pull station location Within 5 feet of exit
- Pull station spacing Travel under 200 feet
- Public mode audible 15 dBA above average ambient
- Sleeping area audible 75 dBA at pillow
- Low-frequency signal 520 Hz, sleeping rooms
- Strobe flash rate 1 to 2 Hz
- Rate-of-rise detector 12-15°F per minute
- Photoelectric detector Better for smoldering fires
- Ionization detector Better for flaming fires
- Duct smoke detector Required above 2,000 CFM
- Annual test All devices, 100 percent
Extinguisher Placement Rules SY
- Class A travel 75 feet maximum
- Class B travel 30 or 50 feet
- Class C travel Follows A or B
- Class D travel 75 feet maximum
- Class K travel 30 feet from appliance
- 40 lb or less Top within 5 feet
- Over 40 lb Top within 3.5 feet
- Floor clearance At least 4 inches
- Monthly inspection Quick visual check
- Annual maintenance Technician thorough exam
- 6-year internal exam Stored-pressure dry chemical
- Hydrostatic test 5 or 12 years
- 1-A rating About 1.25 gallons water
- 20-B rating Square feet, liquid fire
Standpipes and FDCs SY
- Class I 2½ in., fire department
- Class II 1½ in., occupant use
- Class III Both hose connection sizes
- Class I pressure 100 psi, most remote
- Class II pressure 65 psi, most remote
- Class I flow 500 gpm, first standpipe
- Each added standpipe 250 gpm more
- Manual dry standpipe Fire department supplies water
- FDC clear space 3 feet all around
- FDC inlet height 18 to 48 inches
- FDC signage States systems it serves
- Dry standpipe hydrostatic Every 5 years
NFPA 704 Positions HA
- Blue left, red top, yellow right, white bottom
- Blue: health Red: flammability Yellow: instability White: special hazard
Flammable vs Combustible Liquid HA
Flammable
- Class I only
- Flash below 100°F
- Gasoline, acetone, ether
Combustible
- Class II and III
- Flash 100°F or above
- Diesel, heating oil
- 100°F flash point splits
Hazmat Compliance Picker HA
- Flash below 100°F → Flammable, Class I ( NFPA 30 )
- Flash 100-140°F → Combustible, Class II ( Diesel fuel )
- Storage exceeds MAQ → Require permit ( Or add control area )
- Liquids in cabinet → 60 gallons maximum ( Class I and II )
- Reading 704 diamond → Blue, red, yellow, white ( Left, top, right, bottom )
- Cylinder lying loose → Cite securement violation ( Upright and capped )
Flammable Liquid Classes HA
- Class IA Flash under 73°F, boil under 100°F
- Class IB Flash under 73°F, boil 100°F up
- Class IC Flash 73-100°F
- Class II Flash 100-140°F
- Class IIIA Flash 140-200°F
- Class IIIB Flash 200°F and above
- Flammable liquid Class I only
- Combustible liquid Class II and III
- Gasoline Class IB example
- Diesel fuel Class II example
- Motor oil Class IIIB example
- Vapor density Above 1.0 sinks, travels
Flash Point Split HA
- Under 100°F flammable, at or above combustible
- Class IA, IB, IC Class II: 100-140°F Class IIIA: 140-200°F Class IIIB: 200°F up
NFPA 704 Diamond HA
- Blue, left Health hazard
- Red, top Flammability hazard
- Yellow, right Instability hazard
- White, bottom Special hazard symbol
- Rating 0 Minimal hazard
- Rating 4 Severe hazard
- OX Oxidizer
- W with slash Reacts with water
- SA Simple asphyxiant gas
- GHS scale Category 1 is worst
- Safety data sheet 16 standard sections
Hazmat Storage Limits HA
- Storage cabinet 60 gallons, Class I-II
- Cabinet, Class III 120 gallons maximum
- Control area Rated space holding MAQ
- Cabinet increase MAQ doubled
- Sprinkler increase MAQ doubled again
- Both increases Four times baseline MAQ
- Secondary containment 110% of largest container
- LP-gas relief valve Opens near 250 psi
- Compressed cylinders Upright, secured, capped
- Cryogenic expansion Roughly 700 to 800 times
Hot Work and Dust HA
- Hot work clearance 35 feet of combustibles
- IFC fire watch 30 minutes after work
- NFPA 51B fire watch 60 minutes after work
- Post-watch monitoring Up to 3 more hours
- Dust accumulation 1/32 inch over 5%
- Dust pentagon Adds dispersion and confinement
- Dust hazard analysis Required by NFPA 652
- Spray booth airflow 100 feet per minute
- Spray booth wiring Class I, Division 1
Means of Egress Parts OC
- Access, exit, discharge, then public way
- Exit access: to the door Exit: rated enclosure Exit discharge: to outside Public way: 10 feet
Exit Access vs Exit OC
Exit access
- Room to the exit door
- Usually not rated
- Travel distance applies
Exit
- Rated enclosure
- 1 hour under 4 stories
- 2 hours at 4 stories
- Discharge ends at public way
Egress Requirement Picker OC
- Need occupant load → Area divided by factor ( Net or gross )
- Need stair width → Load times 0.3 inch ( NFPA 101 )
- Need door width → Load times 0.2 inch ( Level component )
- Load over 500 → Three exits ( Minimum count )
- Load over 1,000 → Four exits ( Minimum count )
- Checking exit spacing → Half the diagonal ( One third sprinklered )
- Corridor serves 50 → 44 inches clear ( 36 under fifty )
- Door serves 50 → Swing with travel ( Panic hardware likely )
Construction Types OC
- Type I Noncombustible, fire-resistive frame
- Type II Noncombustible, lower ratings
- Type III Masonry walls, wood interior
- Type IV Heavy timber, no concealed
- Type V Wood frame throughout
- Subtype A Protected, higher ratings
- Subtype B Unprotected, lower ratings
- Type IV columns 8x8 inch nominal minimum
- Rating test ASTM E119 or UL 263
- Unexposed side limit 250°F average rise
- Firestop F-rating Resists flame passage
- Firestop T-rating Limits temperature rise
Egress Width Factors OC
- Stairs 0.3, level 0.2, per occupant
- Stairs: 0.3 inch Level: 0.2 inch Multiply by occupant load Then check minimum widths
Fire Wall vs Fire Barrier OC
Fire wall
- Foundation through roof
- Structurally independent
- Creates separate buildings
Fire barrier
- Floor slab to slab
- Not structurally independent
- Shafts, exits, separations
- One side may collapse
Occupant Load Factors OC
- Assembly, concentrated 7 net square feet
- Assembly, less concentrated 15 net square feet
- Classroom 20 net square feet
- Shops, laboratories 50 net square feet
- Day care 35 net square feet
- Business 150 gross square feet
- Mercantile, street floor 30 gross square feet
- Mercantile, above street 60 gross square feet
- Health care sleeping 120 gross square feet
- Residential 200 gross square feet
- Industrial 100 gross square feet
- Storage in mercantile 300 gross square feet
- Storage, other occupancies 500 gross square feet
- Net versus gross Net excludes walls, fixtures
NFPA 101 vs IBC Width OC
NFPA 101
- 0.3 inch stairs
- 0.2 inch level components
- Table 7.3.3.1
IBC
- 0.3 inch stairways
- 0.2 inch other components
- Reduced with sprinkler, voice
- Check the adopted code
Egress Dimensions OC
- Stair capacity factor 0.3 inch per occupant
- Level capacity factor 0.2 inch per occupant
- Corridor, 50 or more 44 inches clear
- Corridor, under 50 36 inches clear
- Door clear width 32 inches minimum
- Door leaf maximum 48 inches wide
- Two exits Required for most spaces
- Three exits Over 500 occupants
- Four exits Over 1,000 occupants
- Exit remoteness Half the overall diagonal
- Sprinklered remoteness One third the diagonal
- Door swing With travel at 50
- Unlatch force 15 pounds maximum
- Panic hardware IBC 50; NFPA 101 100
Travel and Dead Ends OC
- Business travel 200 feet, 300 sprinklered
- Assembly travel 200 feet, 250 sprinklered
- High hazard travel 75 feet, 100 sprinklered
- Common path 75 feet typical limit
- Common path, sprinklered 100 feet, business
- Dead-end corridor 20 feet typical limit
- Dead end, sprinklered 50 feet allowed
- Public way 10 feet clear minimum
Walls and Barriers OC
- Fire wall Foundation through roof, independent
- Fire wall parapet 30 inches above roof
- Fire barrier Floor slab to slab
- Fire partition Corridors and tenant separations
- Smoke barrier Continuous, limits smoke movement
- Smoke partition Resists smoke, usually unrated
- Exit enclosure, under 4 1-hour rating
- Exit enclosure, 4 up 2-hour rating
- Fire damper 165°F fusible link typical
- Smoke damper Closed by smoke detector
Exit Signs and Lighting OC
- Exit sign letters 6 inches high minimum
- Letter stroke 3/4 inch minimum
- Viewing distance 100 feet maximum
- Emergency light duration 90 minutes minimum
- Initial illumination 1 foot-candle average
- End illumination 0.6 foot-candle average
- Transfer time 10 seconds maximum
- Class A finish Flame spread 0-25
- Class B finish Flame spread 26-75
- Class C finish Flame spread 76-200
- Smoke developed limit 450 for all classes
- Decorative materials NFPA 701 flame propagation
Occupancy Classifications OC
- Assembly 50 or more gathering
- Educational 6 or more, through 12th
- Day care Clients receiving supervised care
- Health care Occupants incapable of self-preservation
- Detention, correctional Occupants under restraint
- Residential Sleeping, not health care
- Mercantile Display and sale
- Business Offices and services
- Industrial Manufacturing and processing
- Storage Goods, not manufacturing
Common Traps
Adopted edition, not newest
- Cite the adopted edition ≠ A newer edition is unenforceable
Business factor changed
- NFPA 101 2018: 150 gross ≠ Older editions used 100
Instability, not reactivity
- Yellow means instability ≠ 704 dropped reactivity wording
Recognize versus perform
- Inspector I recognizes the need ≠ Inspector II performs review
Fire watch duration differs
- IFC says 30 minutes ≠ NFPA 51B says 60 minutes
Inspection is not testing
- Inspection is visual only ≠ Testing operates the device
Pro Board sets no score
- Pro Board accredits agencies ≠ Agencies set their cut scores
Class III is combined
- Class III has both sizes ≠ Not a third pressure
GHS scale is inverted
- NFPA 704: 4 is worst ≠ GHS: Category 1 worst
Clearance is below deflector
- 18 inches below deflector ≠ Not measured from ceiling
CFI-I is being retired
- No new applications after 2026 ≠ Testing ends June 30, 2027
Last Minute
- 1. Systems 30%, Occupancy 30%, Administration 25%
- 2. Hazardous materials is smallest, 15%
- 3. Exam is open book, 4 hours
- 4. Stairs 0.3 inch, level 0.2
- 5. Business occupant factor is 150 gross
- 6. Three exits above 500 occupants
- 7. Four exits above 1,000 occupants
- 8. Class A extinguisher within 75 feet
- 9. Class K within 30 feet
- 10. Flammable liquid flashes below 100°F
- 11. 704: blue, red, yellow, white
- 12. Main drain test is annual
- 13. Dead end 20 feet, 50 sprinklered
- 14. Notice needs edition, section, deadline
- 15. Inspector II does plans review
Certified Fire Inspector I/II