Cheat sheet

HVAC Excellence Cheat Sheet

Practice this exam

CORE: Electrical Theory

  • Not published of exam
  • Electrical Theory Electrical Components Ohm's Law Contactor vs Relay

CORE: Refrigeration Theory

  • Not published of exam
  • Refrigeration Cycle Refrigerant Safety Charging Method Picker Superheat vs Subcooling

Combustion Analysis & Gas Heat

  • Not published of exam
  • Combustion Analysis Gas Heat Components Gas Heat Fault Picker Standing Pilot vs Hot Surface Ignition Category I vs Category IV Venting

Electric Heat

  • Not published of exam
  • Electric Heat Heat Sequencer kW to Btu/h CFM Formula

Heat Pumps (Installer & Service)

  • Not published of exam
  • Heat Pump Fundamentals Heat Pump Service Heat Pump Mode Fault Picker Auxiliary vs Emergency Heat O Terminal vs B Terminal

Residential Air Conditioning

  • Not published of exam
  • Residential Air Conditioning TXV vs Fixed Orifice SEER2 Minimum Memory Line Nitrogen Purge

Light Commercial Air Conditioning

  • Not published of exam
  • Light Commercial Air Conditioning Rooftop Unit Economizer Compressor Staging

Light Commercial Refrigeration

  • Not published of exam
  • Light Commercial Refrigeration EPR vs CPR Valve Sweating vs Frosting Head Pressure Control

Residential & Light Commercial Hydronic Heat

  • Not published of exam
  • Hydronic Heat Aquastat Expansion Tank Zone Valve

Quick Facts

  • Body HVAC Excellence (ESCO Group)
  • Level Professional Level Technician
  • Exams 10 separate written exams
  • Questions 100 per exam
  • Format Closed-book written exam
  • Prerequisite CORE exam required first
  • Experience 2 years verified field work
  • Pass score Not published
  • Time limit Not published
  • Fee Not published
  • Validity Not published

Electrical Theory CO

  • Ohm's Law E = I x R
  • Watt's Law P = E x I
  • Series Circuit One current path only
  • Parallel Circuit Same voltage, split current
  • kVA vs kW Apparent power vs real
  • Ladder Diagram Numbered rungs, standard symbols

Electrical Components CO

  • Relay Light-duty control switch
  • Contactor Heavy-duty load switch
  • Motor Starter Contactor plus overload protection
  • Run Capacitor Continuous phase-shift duty
  • Start Capacitor Momentary extra starting torque
  • Control Transformer Steps line voltage to 24V
  • PSC Motor Permanent split-capacitor design

Refrigeration Cycle Order CO

  • Compress, Condense, Meter, Evaporate
  • Compressor raises pressure Condenser rejects heat Metering device drops pressure Evaporator absorbs heat

Superheat vs Subcooling CO

Superheat

  • Checks fixed-orifice charge
  • Vapor above boiling point
  • Measured on suction line

Subcooling

  • Checks TXV charge
  • Liquid below condensing point
  • Measured on liquid line
  • Vapor rise vs liquid drop

Charging Method Picker CO

  • TXV system → Check subcooling ( Target from mfr chart )
  • Fixed orifice system → Check superheat ( Target from mfr chart )
  • Heat pump heating mode → Manufacturer's heating chart ( Not superheat or subcool )
  • No chart available → Weigh in nameplate charge ( Plus line-length adjustment )
  • Long line set run → Add per mfr adjustment ( Ounces per extra foot )
  • Charge totally unknown → Recover then weigh in ( Most reliable method )

Refrigeration Cycle CO

  • Compressor Raises pressure and temperature
  • Condenser Rejects heat, condenses vapor
  • Metering Device Drops pressure, meters flow
  • Evaporator Absorbs heat, boils refrigerant
  • High Side Compressor outlet to metering device
  • Low Side Metering device to compressor inlet
  • Latent Heat Heat with no temperature change

Refrigerant Safety Classes CO

  • A1 safest, A3 most flammable
  • A1 means R-410A, no flame A2L means R-32 or R-454B A3 means R-290, propane B class means higher toxicity

Refrigerant Safety CO

  • A1 Class Lower toxicity, no flame
  • A2L Class Lower toxicity, mild flame
  • A3 Class Lower toxicity, high flame
  • R-410A A1 refrigerant, common R-22 replacement
  • R-32 / R-454B A2L, replacing R-410A
  • R-290 Propane; A3, highly flammable
  • EPA Section 608 Recovery certification required

Gas Furnace Start Sequence CO

  • Inducer, Switch, Ignite, Valve, Flame, Blower
  • Inducer starts the draft Switch proves that draft Igniter or pilot fires Valve opens the fuel Flame sensor proves fire Blower delivers warm air

Standing Pilot vs Hot Surface Ignition CO

Standing Pilot

  • Burns continuously, always lit
  • Thermocouple proves the flame

Hot Surface Ignition

  • Electric igniter, no pilot
  • Fires only on each call
  • Continuous flame vs on-demand

Gas Heat Fault Picker CO

  • Inducer will not start → Check board and wiring ( First sequence step )
  • Inducer runs, no ignition → Check pressure switch ( Proves adequate draft )
  • Igniter will not glow → Check igniter resistance ( Replace if open )
  • Flame lights then drops → Check flame sensor signal ( Weak microamp reading )
  • Sooty, yellow flame → Check primary air setting ( Risk of CO )
  • Nuisance limit trips → Check airflow and filter ( Not a gas fault )

Combustion Analysis CO

  • Primary Air Mixes with fuel first
  • Secondary Air Completes combustion at flame
  • Excess Air Extra air beyond ideal
  • Carbon Monoxide Colorless, toxic, incomplete combustion
  • Draft Moves flue gas outward
  • Stack Temperature Flue gas exit reading
  • Combustion Efficiency Calculated from O2 and CO2

Manifold Pressure Memory Line CO

  • Natural gas 3.5, propane about 10
  • Natural gas runs about 3.5 wc Propane runs about 10 wc Always confirm the nameplate value Wrong pressure misfires the burner

Category I vs Category IV Venting CO

Category I

  • Negative pressure, non-condensing
  • Conventional furnace venting

Category IV

  • Positive pressure, condensing
  • Needs sealed plastic vent
  • Natural draft vs fan-forced vent

Combustion Analyzer Reading Picker CO

  • CO reading is high → Check burner and exchanger ( Incomplete combustion sign )
  • O2 reading is high → Check for excess air ( Draft or setting )
  • Stack temp too high → Check for over-firing ( Or a fouled exchanger )
  • Draft reading is weak → Check vent and exhaust fans ( Depressurization risk )

Gas Heat Components CO

  • Thermocouple About 25-30 mV signal
  • Hot Surface Ignition Electric igniter, no pilot
  • Flame Rectification Flame conducts AC to DC
  • Manifold Pressure About 3.5 in wc natural
  • LP Manifold Pressure About 10 in wc propane
  • Limit Switch Opens circuit on overheat
  • Category IV Venting Positive pressure, condensing, sealed

Electric Heat EL

  • Heat Sequencer Stages elements on then off
  • Fusible Link One-time backup safety device
  • Limit Switch Auto-reset overheat protection
  • kW to Btu/h Multiply kW by 3412
  • Amp Draw Watts divided by volts
  • CFM Formula Btu/h / (1.08 x dT)

Auxiliary vs Emergency Heat HE

Auxiliary Heat

  • Stages on automatically
  • Runs together with compressor

Emergency Heat

  • Manual thermostat setting
  • Locks the compressor out
  • Automatic help vs manual override

Heat Pump Mode Fault Picker HE

  • Heats on a cool call → Check O and B wiring ( Wrong terminal energized )
  • Defrost never starts → Check timer or sensor ( Time-temp or demand type )
  • Reversing valve will not shift → Check for pressure difference ( Needs compressor running )
  • Below the balance point → Confirm aux heat stages ( Compressor alone insufficient )
  • Compressor short-cycles when cold → Check crankcase heater ( Oil dilution risk )

Heat Pump Fundamentals HE

  • Reversing Valve Swaps coil roles by mode
  • Balance Point Heat loss equals HP output
  • Defrost Cycle Briefly cools, melts coil frost
  • Crankcase Heater Prevents refrigerant oil migration
  • Auxiliary Heat Automatic backup heat stage
  • Emergency Heat Manual setting, compressor locked out
  • O Terminal Energizes valve in cooling
  • B Terminal Energizes valve in heating

O Terminal vs B Terminal HE

O Terminal

  • Energizes valve in cooling
  • Most manufacturers' default wiring

B Terminal

  • Energizes valve in heating
  • Used by Rheem and Ruud
  • Cooling-energized vs heating-energized valve

Heat Pump Service HE

  • Demand Defrost Sensor-triggered, not fixed timer
  • Time-Temp Defrost Fixed timer plus coil sensor
  • Line Set Sizing From capacity and length charts
  • Charging Method Weigh in nameplate charge
  • Heating-Mode Charge Use manufacturer's heating chart

SEER2 Minimum Memory Line RE

  • 13.4 North, 14.3 South split AC
  • North region needs 13.4 SEER2 Southeast and Southwest need 14.3 Split heat pumps need 14.3 M1 test raised static pressure

TXV vs Fixed Orifice RE

TXV

  • Sensing bulb feedback control
  • Holds a target superheat
  • Handles changing loads well

Fixed Orifice

  • No moving parts inside
  • Flow follows pressure only
  • Needs an exact charge
  • Modulates flow vs fixed flow

Residential Air Conditioning RE

  • TXV Modulates flow, holds superheat
  • Fixed Orifice No moving parts inside
  • SEER2 2023-plus efficiency test metric
  • SEER2 Minimum 13.4 North, 14.3 South
  • Static Pressure Blower resistance, measured in wc
  • Nitrogen Purge Prevents copper oxide scale
  • Sensible vs Latent Temperature drop vs moisture removal

Light Commercial Air Conditioning LI

  • Rooftop Unit Self-contained, curb-mounted package
  • Economizer Free cooling with outdoor air
  • Compressor Staging Multiple compressors match load
  • Minimum OA Damper Set and measured at commissioning
  • Draw-Through Drain Needs a deep trap depth
  • Float Switch Shuts unit down on overflow

EPR vs CPR Valve LI

EPR Valve

  • At the evaporator outlet
  • Limits low coil temperature

CPR Valve

  • At the compressor inlet
  • Limits high suction pressure
  • Evaporator side vs compressor side

Light Commercial Refrigeration LI

  • EPR Valve Limits low evaporator pressure
  • CPR Valve Limits high suction pressure
  • Head Pressure Control Holds pressure up in cold
  • Off-Cycle Defrost Coolers only, above freezing
  • Hot Gas Defrost Freezers, below freezing point
  • Pump-Down Cycle Stores charge in condenser

Sweating vs Frosting LI

Sweating

  • Humidity or a bad gasket
  • Surface condensation, not ice

Frosting

  • Low airflow or low charge
  • Ice buildup on the coil
  • Humidity issue vs refrigerant issue

Hydronic Heat HY

  • Aquastat Senses water, controls burner
  • Circulator Pump Moves water around closed loop
  • Expansion Tank Absorbs heated water expansion
  • Fill Pressure About 12 psi when cold
  • Relief Valve Opens near 30 psi
  • Zone Valve Opens one zone per call

Common Traps

Superheat vs Subcooling Use

  • Superheat checks fixed orifice ≠ Subcooling checks TXV charge

EPR vs CPR Location

  • EPR limits evaporator pressure ≠ CPR limits compressor suction

Auxiliary vs Emergency Heat

  • Auxiliary stages automatically ≠ Emergency locks out compressor

O vs B Terminal

  • O energizes cooling mode ≠ B energizes heating mode

Sweating vs Frosting Cause

  • Sweating means a humidity issue ≠ Frosting means airflow or charge

Category I vs IV Vent

  • Category I is negative draft ≠ Category IV is positive, sealed

Standing Pilot vs HSI

  • Standing pilot burns continuously ≠ HSI ignites only on call

Last Minute

  • 1. CORE exam required before others
  • 2. Two years field experience required
  • 3. Superheat checks fixed-orifice refrigerant charge
  • 4. Subcooling checks TXV refrigerant charge
  • 5. Natural gas manifold: about 3.5 wc
  • 6. LP manifold pressure: about 10 wc
  • 7. SEER2 minimum: 13.4 or 14.3
  • 8. kW times 3412 equals Btu/h
  • 9. O terminal cools; B terminal heats
  • 10. Hydronic fill 12 psi; relief 30
  • 11. HVAC Excellence publishes no domain weights
  • 12. Master Specialist needs hands-on testing too

HVAC Excellence