Cheat sheet
ICC P2 Commercial Plumbing Inspector Cheat Sheet
General Requirements
- 5% of exam
- Code Official & Permits Inspection Sequence Material Listing Construction Documents
Piping Protection
- 2% of exam
- Freeze Protection Nail Plates Vehicle Impact Dielectric Fittings
Piping Installation & Testing
- 3% of exam
- Hanger Spacing DWV Testing Condensate Disposal Approved Joints
Fixtures, Faucets & Fittings
- 15% of exam
- Fixture Flow Rates Accessible Clearances Fixture Counts Scald Protection
Water Heaters
- 10% of exam
- T&P Relief Valves Drain Pans Thermal Expansion Combustion Air
Water Supply & Distribution
- 14% of exam
- Fixture Unit Sizing Backflow Prevention Air Gaps Pipe Materials
Sanitary Drainage
- 18% of exam
- DFU Values Drain Sizing & Slope Cleanouts Indirect Waste
Vents
- 15% of exam
- Vent Sizing Trap Arm Distance Vent Types Air Admittance Valves
Traps, Interceptors & Special Piping
- 11% of exam
- Trap Rules Grease & Oil Interceptors Chemical Waste Medical Gas
Storm Drainage
- 7% of exam
- Roof Drain Sizing Secondary Drainage Storm Materials System Separation
Quick Facts
- Exam P2
- Credential Commercial Plumbing Inspector
- Questions 60 multiple-choice
- Time 2.5 hours
- Pass Score 75 (scaled)
- Format Open book
- Code Basis 2024 IPC + IFGC
- Accessibility Std ICC A117.1-2017
Inspection Sequence Check GE
- Work about to be concealed → Rough-in inspection first
- Piping installed below grade → Underground inspection first
- All systems fully complete → Final inspection
- DWV before it is covered → Water or air test
- Gas piping before use → 3 psi for 10 min
Code Official & Permits GE
- Code official Enforces & interprets code
- Construction docs Required when official demands
- Rough-in inspection Before work is concealed
- Underground inspection Before backfill covers piping
- Final inspection After all systems tested
- Listed materials Third-party tested and labeled
Piping Protection Rules PI
- Water service depth 12 in minimum below grade
- Frost protection depth 6 in below frost line
- Stud clearance zone Under 1-1/4 in needs plate
- Shield plate gauge 16 gauge, 0.0575 in steel
- Vehicle impact zones Guard post or bollard required
- Dissimilar metal joints Dielectric union prevents corrosion
Installation & Testing PI
- Copper DWV hanger 10 ft horizontal spacing
- PVC DWV hanger 4 ft horizontal spacing
- DWV water test 10 ft head, 15 min
- DWV air test 5 psi for 15 min
- Condensate discharge Indirect waste connection only
Flush & Flow Limits FI
- Water closets flush most, faucets sip water
- WC 1.6 gpf Urinal 0.5 gpf Lav 0.5-2.2 gpm Shower 2.5 gpm
Fixture Flow & Flush Rates FI
- Public lavatory faucet 0.5 gpm at 60 psi
- Private lavatory faucet 2.2 gpm at 60 psi
- Showerhead limit 2.5 gpm at 80 psi
- Water closet flush 1.6 gpf maximum
- Urinal flush 1.0 gpf IPC maximum
- Public metering faucet 0.25 gal per cycle
A117.1 Accessible Heights FI
- Seat, rim, and grab bar each keep their own range
- Seat 17-19 in Rim 34 in max Grab bar 33-36 in Knee space 27 in
Fixture & Accessible Clearances FI
- WC front clearance 21 in minimum
- WC centerline to wall 15 in minimum
- WC centerline spacing 30 in apart minimum
- Accessible WC centerline 16-18 in from wall A117.1
- Accessible WC seat height 17-19 in above floor A117.1
- Grab bar height 33-36 in above floor A117.1
- Accessible lavatory rim 34 in maximum height A117.1
- Lavatory knee clearance 27 in high, 8 deep
Water Heater Safety Devices WA
- T&P discharge height 6 in max above floor
- T&P valve rating Match water heater input
- Drain pan trigger Leakage would damage building
- Drain pan pipe 3/4 in minimum diameter
- Thermal expansion device Required on closed systems
- Public lav tempered water 110 F max ASSE 1070
- Shower/tub delivery 120 F max ASSE 1016
Water Heater Venting & Air WA
- Indoor combustion air 50 cu ft per 1000 Btu
- Zero-clearance heaters Only if listed for it
- Solar freeze protection Drain-back or nontoxic fluid
- Bathing facility trigger Overnight-stay occupancies only
Hazard Level to Device WA
- High hazard needs RP, low hazard needs double check
- High = RP/RPZ Low = double check Air gap = universal fix
RP vs Double Check WA
RP Assembly
- High hazard
- Contamination risk
- Continuous pressure ok
Double Check
- Low hazard
- Pollution risk only
- Hazard level decides device
Backflow Device Selector WA
- High hazard, continuous pressure → RP/RPZ assembly
- Low hazard, continuous pressure → Double check valve
- Air gap achievable → Physical air gap
- Hose bibb, outdoors → Non-removable vacuum breaker
- Irrigation with chemical injection → RP or air gap
- PVB installed outdoors → 12 in above outlet ( Not continuous pressure )
Water Supply Sizing WA
- Public flushometer WC 10 water supply fixture units
- Tank-type public WC 5 water supply fixture units
- Private flushometer WC 2.5 water supply fixture units
- Min static pressure 15 psi, 20 for flushometers
- Max static pressure 80 psi before PRV required
- PRV side effect Creates a closed system
- Flushometer WC branch 1 in minimum size
- Hot water recirc trigger Over 50 ft developed length
Backsiphonage vs Backpressure WA
Backsiphonage
- Supply pressure drops
- Vacuum pulls water back
Backpressure
- Downstream pressure rises
- Pushes water upstream
- Direction of pressure change
Backflow Prevention Devices WA
- High hazard cross-connection RP/RPZ assembly required
- Low hazard cross-connection Double check valve assembly
- Air gap, no wall 2x diameter, 1 in min
- Air gap, near wall 3x diameter, 1.5 in min
- PVB install height 12 in above highest outlet
- Hose bibb protection Non-removable vacuum breaker
- Chemical feed systems RP assembly or air gap
- Water hammer trigger Any quick-closing valve
Pipe Materials & Valves WA
- Underground water service Type K copper preferred
- Interior distribution copper Type L copper standard
- PEX tubing standard ASTM F877 or CSA B137.5
- Nonpotable pipe color Purple, marked lavender
- Full-open shutoff valves At service entry and heaters
Air Gap vs Air Break SA
Air Gap
- Physical vertical separation
- Required for food equipment
Air Break
- Below flood rim
- Not compliant for food
- Food waste needs true gap
Drainage Fixture Unit Values SA
- Public WC, 1.6 gpf 4 dfu
- Public WC, over 1.6 gpf 6 dfu
- Urinal 2 dfu
- Public lavatory 1 dfu
- Kitchen sink 2 dfu
- Floor drain 2 dfu minimum
- Service sink 2 dfu
Building Drain vs Branch Table SA
Table 710.1(1)
- Building drains & sewers
- Sized by slope
Table 710.1(2)
- Branches & stacks
- Sized by pipe only
- Match table to pipe type
Drain Sizing & Slope SA
- Slope, 2.5 in or less 1/4 in per ft
- Slope, 3 to 6 in 1/8 in per ft
- Slope, 8 in or larger 1/16 in per ft
- 4-in drain, 1/4 slope 216 dfu capacity
- Min building sewer size 3 in diameter
- Cleanout interval 100 ft maximum spacing
- Cleanout direction change Required over 45 degrees
- Cleanout minimum size Equals pipe, 4 in max
Special Drainage Systems SA
- Backwater valve trigger Rim below upstream manhole
- Sewage ejector discharge 2 in minimum size
- Grinder pump discharge 1-1/4 in minimum size
- Sump cover Gas-tight and vented
- Food equipment waste Air gap always required
- Double sanitary tee Prohibited for horizontal use
- Chemical waste material Acid-resistant, chemical-specific
Trap Arm Growth Pattern VE
- Bigger trap arm allows a longer run to vent
- 1-1/4 in = 5 ft 1-1/2 in = 6 ft 2 in = 8 ft 3 in = 12 ft 4 in = 16 ft
Common Vent vs Circuit Vent VE
Common Vent
- Two fixtures only
- Same level connection
Circuit Vent
- Up to 8 fixtures
- One horizontal branch
- Fixture count decides choice
Vent Type Selector VE
- Two fixtures, same level → Common vent
- Up to 8 fixtures → Circuit vent
- Drain also serves as vent → Wet vent
- Island sink, no wall → Loop or combo waste-vent
- Avoiding a roof penetration → AAV plus one open vent
Vent Sizing & Installation VE
- Min vent diameter 1-1/4 in absolute minimum
- Vent rise before offset 6 in above flood rim
- Vent through roof 6 in minimum above roof
- Vent near opening 10 ft, or 2 ft above
- Vent connection angle 45 degrees minimum from horizontal
- Horizontal vent slope 1/8 in per ft
- Vent stack trigger 5 or more branch intervals
Vent Types & Trap Arm VE
- Trap arm, 1-1/4 in 5 ft max to vent
- Trap arm, 1-1/2 in 6 ft max to vent
- Trap arm, 2 in 8 ft max to vent
- Trap arm, 3 in 12 ft max to vent
- Trap arm, 4 in 16 ft max to vent
- Common vent 2 fixtures, same level
- Circuit vent Up to 8 fixtures
- Wet vent Drain doubles as vent
- AAV requirement Needs one open-air vent
Grease vs Oil Interceptor TR
Grease Interceptor
- Food-service kitchens
- Sized by gpm flow
Oil Separator
- Garages & fuel facilities
- Sized by drainage area
- Food vs vehicle waste
Interceptor & Waste Selector TR
- Food-service grease waste → Grease interceptor
- Vehicle or fuel service → Oil separator
- Lab acid or chemical waste → Neutralization tank
- Chemical feed cross-connection → RP backflow device
- Medical or oxygen piping → Follow NFPA 99 or 55
Trap Rules TR
- Trap seal depth 2 to 4 in
- Fixture-to-weir drop 24 in maximum
- Prohibited traps S-traps, drum, and bell traps
- Each fixture rule Separate, self-scouring trap required
S-Trap vs P-Trap TR
S-Trap
- Self-siphons seal
- Prohibited by IPC
P-Trap
- Vented trap arm
- Code-required design
- S-trap always fails inspection
Interceptors & Medical Gas TR
- Grease interceptor sizing By gpm drainage flow
- Oil separator use Garages and fuel facilities
- Lab acid waste Neutralize before sanitary sewer
- Medical gas standard NFPA 99
- Bulk oxygen standard NFPA 55
- Medical gas pipe Cleaned Type K or L copper
Storm Drainage Rules ST
- Design rainfall basis 100-year, 1-hour rate
- Secondary drain trigger Parapet could trap water
- Subsoil drain discharge Storm system, never sanitary
- Storm/sanitary connection Never permitted, always separate
- Storm pipe materials Own table, not sanitary table
Common Traps
Air Gap vs Air Break
- Gap is above rim ≠ Break is below rim
S-Trap Looks Like P-Trap
- S-trap self-siphons ≠ P-trap holds seal
Grease vs Oil Interceptor
- Grease serves kitchens ≠ Oil serves vehicles
Backsiphonage vs Backpressure
- Siphonage is a pressure drop ≠ Backpressure is a pressure push
Stack Vent vs Vent Stack
- Stack vent extends the stack ≠ Vent stack is separate pipe
Double Sanitary Tee Rules
- Banned for horizontal use ≠ Allowed vertical with conditions
Building Drain vs Branch Table
- Drain table uses slope ≠ Branch table uses pipe size only
Last Minute
- 1. 60 questions, 2.5 hour limit
- 2. Open book: 2024 IPC required
- 3. Passing score is 75 scaled
- 4. High hazard always needs RP
- 5. Trap seal is 2-4 in
- 6. Never connect storm to sanitary
- 7. S-traps are always prohibited
- 8. Food waste needs true air gap
- 9. PRV always requires expansion tank
- 10. Tab your IPC tables first
- 11. Water Supply and Drainage are 32%
- 12. Bring only approved code references
ICC Commercial Plumbing Inspector (P2)
- Practice Questions 122 questions Study Guide 32 topics Cheat Sheet 116 facts Flashcards 50 cards Videos 1 video Blogs 1 blog 1 Job Wiki Free CE Podcast