Cheat sheet

ICC P2 Commercial Plumbing Inspector Cheat Sheet

Practice this exam

General Requirements

  • 5% of exam
  • Code Official & Permits Inspection Sequence Material Listing Construction Documents

Piping Protection

  • 2% of exam
  • Freeze Protection Nail Plates Vehicle Impact Dielectric Fittings

Piping Installation & Testing

  • 3% of exam
  • Hanger Spacing DWV Testing Condensate Disposal Approved Joints

Fixtures, Faucets & Fittings

  • 15% of exam
  • Fixture Flow Rates Accessible Clearances Fixture Counts Scald Protection

Water Heaters

  • 10% of exam
  • T&P Relief Valves Drain Pans Thermal Expansion Combustion Air

Water Supply & Distribution

  • 14% of exam
  • Fixture Unit Sizing Backflow Prevention Air Gaps Pipe Materials

Sanitary Drainage

  • 18% of exam
  • DFU Values Drain Sizing & Slope Cleanouts Indirect Waste

Vents

  • 15% of exam
  • Vent Sizing Trap Arm Distance Vent Types Air Admittance Valves

Traps, Interceptors & Special Piping

  • 11% of exam
  • Trap Rules Grease & Oil Interceptors Chemical Waste Medical Gas

Storm Drainage

  • 7% of exam
  • Roof Drain Sizing Secondary Drainage Storm Materials System Separation

Quick Facts

  • Exam P2
  • Credential Commercial Plumbing Inspector
  • Questions 60 multiple-choice
  • Time 2.5 hours
  • Pass Score 75 (scaled)
  • Format Open book
  • Code Basis 2024 IPC + IFGC
  • Accessibility Std ICC A117.1-2017

Inspection Sequence Check GE

  • Work about to be concealed → Rough-in inspection first
  • Piping installed below grade → Underground inspection first
  • All systems fully complete → Final inspection
  • DWV before it is covered → Water or air test
  • Gas piping before use → 3 psi for 10 min

Code Official & Permits GE

  • Code official Enforces & interprets code
  • Construction docs Required when official demands
  • Rough-in inspection Before work is concealed
  • Underground inspection Before backfill covers piping
  • Final inspection After all systems tested
  • Listed materials Third-party tested and labeled

Piping Protection Rules PI

  • Water service depth 12 in minimum below grade
  • Frost protection depth 6 in below frost line
  • Stud clearance zone Under 1-1/4 in needs plate
  • Shield plate gauge 16 gauge, 0.0575 in steel
  • Vehicle impact zones Guard post or bollard required
  • Dissimilar metal joints Dielectric union prevents corrosion

Installation & Testing PI

  • Copper DWV hanger 10 ft horizontal spacing
  • PVC DWV hanger 4 ft horizontal spacing
  • DWV water test 10 ft head, 15 min
  • DWV air test 5 psi for 15 min
  • Condensate discharge Indirect waste connection only

Flush & Flow Limits FI

  • Water closets flush most, faucets sip water
  • WC 1.6 gpf Urinal 0.5 gpf Lav 0.5-2.2 gpm Shower 2.5 gpm

Fixture Flow & Flush Rates FI

  • Public lavatory faucet 0.5 gpm at 60 psi
  • Private lavatory faucet 2.2 gpm at 60 psi
  • Showerhead limit 2.5 gpm at 80 psi
  • Water closet flush 1.6 gpf maximum
  • Urinal flush 1.0 gpf IPC maximum
  • Public metering faucet 0.25 gal per cycle

A117.1 Accessible Heights FI

  • Seat, rim, and grab bar each keep their own range
  • Seat 17-19 in Rim 34 in max Grab bar 33-36 in Knee space 27 in

Fixture & Accessible Clearances FI

  • WC front clearance 21 in minimum
  • WC centerline to wall 15 in minimum
  • WC centerline spacing 30 in apart minimum
  • Accessible WC centerline 16-18 in from wall A117.1
  • Accessible WC seat height 17-19 in above floor A117.1
  • Grab bar height 33-36 in above floor A117.1
  • Accessible lavatory rim 34 in maximum height A117.1
  • Lavatory knee clearance 27 in high, 8 deep

Water Heater Safety Devices WA

  • T&P discharge height 6 in max above floor
  • T&P valve rating Match water heater input
  • Drain pan trigger Leakage would damage building
  • Drain pan pipe 3/4 in minimum diameter
  • Thermal expansion device Required on closed systems
  • Public lav tempered water 110 F max ASSE 1070
  • Shower/tub delivery 120 F max ASSE 1016

Water Heater Venting & Air WA

  • Indoor combustion air 50 cu ft per 1000 Btu
  • Zero-clearance heaters Only if listed for it
  • Solar freeze protection Drain-back or nontoxic fluid
  • Bathing facility trigger Overnight-stay occupancies only

Hazard Level to Device WA

  • High hazard needs RP, low hazard needs double check
  • High = RP/RPZ Low = double check Air gap = universal fix

RP vs Double Check WA

RP Assembly

  • High hazard
  • Contamination risk
  • Continuous pressure ok

Double Check

  • Low hazard
  • Pollution risk only
  • Hazard level decides device

Backflow Device Selector WA

  • High hazard, continuous pressure → RP/RPZ assembly
  • Low hazard, continuous pressure → Double check valve
  • Air gap achievable → Physical air gap
  • Hose bibb, outdoors → Non-removable vacuum breaker
  • Irrigation with chemical injection → RP or air gap
  • PVB installed outdoors → 12 in above outlet ( Not continuous pressure )

Water Supply Sizing WA

  • Public flushometer WC 10 water supply fixture units
  • Tank-type public WC 5 water supply fixture units
  • Private flushometer WC 2.5 water supply fixture units
  • Min static pressure 15 psi, 20 for flushometers
  • Max static pressure 80 psi before PRV required
  • PRV side effect Creates a closed system
  • Flushometer WC branch 1 in minimum size
  • Hot water recirc trigger Over 50 ft developed length

Backsiphonage vs Backpressure WA

Backsiphonage

  • Supply pressure drops
  • Vacuum pulls water back

Backpressure

  • Downstream pressure rises
  • Pushes water upstream
  • Direction of pressure change

Backflow Prevention Devices WA

  • High hazard cross-connection RP/RPZ assembly required
  • Low hazard cross-connection Double check valve assembly
  • Air gap, no wall 2x diameter, 1 in min
  • Air gap, near wall 3x diameter, 1.5 in min
  • PVB install height 12 in above highest outlet
  • Hose bibb protection Non-removable vacuum breaker
  • Chemical feed systems RP assembly or air gap
  • Water hammer trigger Any quick-closing valve

Pipe Materials & Valves WA

  • Underground water service Type K copper preferred
  • Interior distribution copper Type L copper standard
  • PEX tubing standard ASTM F877 or CSA B137.5
  • Nonpotable pipe color Purple, marked lavender
  • Full-open shutoff valves At service entry and heaters

Air Gap vs Air Break SA

Air Gap

  • Physical vertical separation
  • Required for food equipment

Air Break

  • Below flood rim
  • Not compliant for food
  • Food waste needs true gap

Drainage Fixture Unit Values SA

  • Public WC, 1.6 gpf 4 dfu
  • Public WC, over 1.6 gpf 6 dfu
  • Urinal 2 dfu
  • Public lavatory 1 dfu
  • Kitchen sink 2 dfu
  • Floor drain 2 dfu minimum
  • Service sink 2 dfu

Building Drain vs Branch Table SA

Table 710.1(1)

  • Building drains & sewers
  • Sized by slope

Table 710.1(2)

  • Branches & stacks
  • Sized by pipe only
  • Match table to pipe type

Drain Sizing & Slope SA

  • Slope, 2.5 in or less 1/4 in per ft
  • Slope, 3 to 6 in 1/8 in per ft
  • Slope, 8 in or larger 1/16 in per ft
  • 4-in drain, 1/4 slope 216 dfu capacity
  • Min building sewer size 3 in diameter
  • Cleanout interval 100 ft maximum spacing
  • Cleanout direction change Required over 45 degrees
  • Cleanout minimum size Equals pipe, 4 in max

Special Drainage Systems SA

  • Backwater valve trigger Rim below upstream manhole
  • Sewage ejector discharge 2 in minimum size
  • Grinder pump discharge 1-1/4 in minimum size
  • Sump cover Gas-tight and vented
  • Food equipment waste Air gap always required
  • Double sanitary tee Prohibited for horizontal use
  • Chemical waste material Acid-resistant, chemical-specific

Trap Arm Growth Pattern VE

  • Bigger trap arm allows a longer run to vent
  • 1-1/4 in = 5 ft 1-1/2 in = 6 ft 2 in = 8 ft 3 in = 12 ft 4 in = 16 ft

Common Vent vs Circuit Vent VE

Common Vent

  • Two fixtures only
  • Same level connection

Circuit Vent

  • Up to 8 fixtures
  • One horizontal branch
  • Fixture count decides choice

Vent Type Selector VE

  • Two fixtures, same level → Common vent
  • Up to 8 fixtures → Circuit vent
  • Drain also serves as vent → Wet vent
  • Island sink, no wall → Loop or combo waste-vent
  • Avoiding a roof penetration → AAV plus one open vent

Vent Sizing & Installation VE

  • Min vent diameter 1-1/4 in absolute minimum
  • Vent rise before offset 6 in above flood rim
  • Vent through roof 6 in minimum above roof
  • Vent near opening 10 ft, or 2 ft above
  • Vent connection angle 45 degrees minimum from horizontal
  • Horizontal vent slope 1/8 in per ft
  • Vent stack trigger 5 or more branch intervals

Vent Types & Trap Arm VE

  • Trap arm, 1-1/4 in 5 ft max to vent
  • Trap arm, 1-1/2 in 6 ft max to vent
  • Trap arm, 2 in 8 ft max to vent
  • Trap arm, 3 in 12 ft max to vent
  • Trap arm, 4 in 16 ft max to vent
  • Common vent 2 fixtures, same level
  • Circuit vent Up to 8 fixtures
  • Wet vent Drain doubles as vent
  • AAV requirement Needs one open-air vent

Grease vs Oil Interceptor TR

Grease Interceptor

  • Food-service kitchens
  • Sized by gpm flow

Oil Separator

  • Garages & fuel facilities
  • Sized by drainage area
  • Food vs vehicle waste

Interceptor & Waste Selector TR

  • Food-service grease waste → Grease interceptor
  • Vehicle or fuel service → Oil separator
  • Lab acid or chemical waste → Neutralization tank
  • Chemical feed cross-connection → RP backflow device
  • Medical or oxygen piping → Follow NFPA 99 or 55

Trap Rules TR

  • Trap seal depth 2 to 4 in
  • Fixture-to-weir drop 24 in maximum
  • Prohibited traps S-traps, drum, and bell traps
  • Each fixture rule Separate, self-scouring trap required

S-Trap vs P-Trap TR

S-Trap

  • Self-siphons seal
  • Prohibited by IPC

P-Trap

  • Vented trap arm
  • Code-required design
  • S-trap always fails inspection

Interceptors & Medical Gas TR

  • Grease interceptor sizing By gpm drainage flow
  • Oil separator use Garages and fuel facilities
  • Lab acid waste Neutralize before sanitary sewer
  • Medical gas standard NFPA 99
  • Bulk oxygen standard NFPA 55
  • Medical gas pipe Cleaned Type K or L copper

Storm Drainage Rules ST

  • Design rainfall basis 100-year, 1-hour rate
  • Secondary drain trigger Parapet could trap water
  • Subsoil drain discharge Storm system, never sanitary
  • Storm/sanitary connection Never permitted, always separate
  • Storm pipe materials Own table, not sanitary table

Common Traps

Air Gap vs Air Break

  • Gap is above rim ≠ Break is below rim

S-Trap Looks Like P-Trap

  • S-trap self-siphons ≠ P-trap holds seal

Grease vs Oil Interceptor

  • Grease serves kitchens ≠ Oil serves vehicles

Backsiphonage vs Backpressure

  • Siphonage is a pressure drop ≠ Backpressure is a pressure push

Stack Vent vs Vent Stack

  • Stack vent extends the stack ≠ Vent stack is separate pipe

Double Sanitary Tee Rules

  • Banned for horizontal use ≠ Allowed vertical with conditions

Building Drain vs Branch Table

  • Drain table uses slope ≠ Branch table uses pipe size only

Last Minute

  • 1. 60 questions, 2.5 hour limit
  • 2. Open book: 2024 IPC required
  • 3. Passing score is 75 scaled
  • 4. High hazard always needs RP
  • 5. Trap seal is 2-4 in
  • 6. Never connect storm to sanitary
  • 7. S-traps are always prohibited
  • 8. Food waste needs true air gap
  • 9. PRV always requires expansion tank
  • 10. Tab your IPC tables first
  • 11. Water Supply and Drainage are 32%
  • 12. Bring only approved code references

ICC Commercial Plumbing Inspector (P2)