Cheat sheet

NICET Fire Alarm Level I Cheat Sheet

Practice this exam

System Fundamentals & Devices

  • 30-40% of exam
  • Smoke Detectors Heat Detectors Pull Stations Waterflow FACP Signal Types

Circuits & Power

  • 25-30% of exam
  • Circuit Classes IDC/SLC/NAC NEC 760 Primary Power Battery Standby Supervision

Installation & Mounting

  • 15-20% of exam
  • Mounting Heights Detector Spacing Candela Spacing Audibility Plan Symbols

Codes, Testing & Inspection

  • 10-15% of exam
  • NFPA 72 Chapters AHJ Test Frequency Sensitivity Record of Completion

Quick Facts

  • Exam NICET FAS-I
  • Questions 85 MCQ
  • Time 110 min
  • Pass 500/700
  • Format Open book
  • Codes NFPA 72/70
  • Fee $230
  • Level Entry technician

Signal Priority DE

  • Alarm beats Supervisory beats Trouble
  • Alarm: fire Supervisory: impairment Trouble: fault Highest: alarm

Ionization vs Photoelectric DE

Ionization

  • Flaming fires
  • Small particles
  • Radioactive source

Photoelectric

  • Smoldering fires
  • Large particles
  • Light scatter
  • Flaming vs smoldering

Which Detector Type? DE

  • Smoldering fire risk → Photoelectric ( Visible particles )
  • Flaming fire risk → Ionization ( Small particles )
  • Large open hall → Beam detector ( Long range )
  • Dusty/dirty area → Heat detector ( Avoid false alarm )
  • High-value early warning → Aspirating ( Air sampling )
  • Rapid temperature jump → ROR heat ( Rate change )
  • Steady high heat → Fixed-temp heat ( Setpoint )
  • HVAC smoke spread → Duct detector ( Shut fan )

Smoke Detectors DE

  • Ionization Fast flaming fires
  • Photoelectric Slow smoldering fires
  • Beam Large open areas
  • Aspirating Air-sample very-early warning
  • Duct detector Sample HVAC airflow
  • Spacing 30 ft on-center
  • Off wall 4 in minimum

Smoke Memory DE

  • Ion flames fast, Photo smolders slow
  • Ion: flaming Photo: smoldering

Fixed-temp vs ROR Heat DE

Fixed-temp

  • Reaches setpoint
  • 135-174 F
  • Will not reset

ROR

  • Rate of change
  • 12-15 F/min
  • Self-restoring
  • Setpoint vs rate

Heat Detectors DE

  • Fixed-temp Activates at setpoint
  • ROR Rate-of-rise change
  • ROR rate 12-15 F/min rise
  • Ordinary rating 135-174 F
  • Line-type Cable senses length
  • Combination Fixed plus ROR

Alarm vs Super vs Trouble DE

Alarm

  • Fire detected
  • Smoke or waterflow
  • Highest priority

Super / Trouble

  • Super: tamper, impairment
  • Trouble: open, ground
  • Lower priority
  • Fire vs fault

Manual & Sprinkler DE

  • Pull station Manual alarm initiation
  • Single-action One pull motion
  • Double-action Push-then-pull
  • Near exits Within 5 ft
  • Waterflow Sprinkler flow alarm
  • Tamper switch Valve supervisory signal
  • Retard chamber Ignores surge transients

Notification Appliances DE

  • Horn Audible only
  • Strobe Visible candela flash
  • Horn/strobe Audible plus visible
  • Speaker Voice EVACS output
  • Temporal-3 Standard evacuation pattern
  • 520 Hz Sleeping-area low frequency
  • Sync Strobes flash together

Control Unit & Signals DE

  • FACP Fire alarm control panel
  • Conventional Zone-based addressing
  • Addressable Per-device point ID
  • Alarm Fire condition signal
  • Supervisory System impairment signal
  • Trouble Fault or open signal
  • Annunciator Remote status display

Battery Calc CI

  • 24 h standby plus 5 min alarm
  • Standby Ah Alarm Ah Add both Times 1.2

Class A vs Class B CI

Class A

  • Return loop
  • Survives one open
  • No EOL resistor

Class B

  • No return
  • Open stops devices
  • EOL resistor
  • Redundant vs simple

Class A vs Class B? CI

  • Survive single open → Class A ( Return loop )
  • Simple, lower cost → Class B ( EOL resistor )
  • Need fault isolation → Class X ( Short tolerant )
  • Network backbone → Class N ( Ethernet )
  • End-of-line on B → EOL resistor ( Supervision )
  • Both wire paths used → Class A ( Out and back )

Circuit Classes CI

  • Class B No return path
  • Class A Redundant return loop
  • Class X Loop with fault isolation
  • Class N Ethernet network path
  • EOL resistor Class B supervision end
  • Single fault Class A keeps operating

Circuit Classes CI

  • A loops, B ends, X isolates, N networks
  • A: redundant B: EOL X: fault isolate N: ethernet

IDC vs SLC vs NAC CI

IDC / SLC

  • IDC: conventional inputs
  • SLC: addressable poll
  • Both initiate

NAC

  • Drives appliances
  • Horns and strobes
  • Polarized output
  • Input vs output

Battery Sizing Steps CI

  • Sum standby current → Standby amps ( Quiescent )
  • Multiply by 24 h → Standby Ah ( Ah )
  • Sum alarm current → Alarm amps ( All NACs )
  • Multiply by 5 min → Alarm Ah ( 5/60 hour )
  • Add both totals → Required Ah ( Subtotal )
  • Apply derating → Times 1.2 ( Safety factor )

Pathways & Wiring CI

  • IDC Initiating device circuit
  • SLC Signaling line circuit
  • NAC Notification appliance circuit
  • Polarity NAC devices polarized
  • Survivability Pathway protected from fire
  • Ground fault Unwanted earth path
  • Supervision Detects opens/shorts

NEC 760 Cable CI

  • FPL, then Riser, then Plenum
  • FPL: general FPLR: riser FPLP: plenum

Primary vs Secondary Power CI

Primary

  • Utility branch
  • Dedicated circuit
  • Normal supply

Secondary

  • Standby battery
  • 24 h plus 5 min
  • AC-loss backup
  • Mains vs backup

NEC Article 760 CI

  • PLFA Power-limited fire alarm
  • NPLFA Non-power-limited fire alarm
  • FPL General cable type
  • FPLR Riser-rated cable
  • FPLP Plenum-rated cable
  • Separation Apart from power
  • Red jacket Common FA marking

Power & Battery CI

  • Primary Utility branch circuit
  • Secondary Standby battery backup
  • Standby 24 h supervisory load
  • Alarm load 5 min after standby
  • Safety factor Multiply 1.2 result
  • Charger Supervised, recharges battery
  • AC loss Trouble signal generated

Mounting Heights IN

  • Pull handle 42-60 in AFF
  • Reach max 48 in ADA
  • Wall strobe 80-96 in lens
  • Ceiling strobe Per listed spacing
  • Smoke spacing 30 ft on-center
  • Beam ceiling Reduce spacing per depth
  • Off wall Detector 4 in min

Audibility & Candela IN

  • Public mode Plus 15 dB ambient
  • Private mode Plus 10 dB ambient
  • Max ceiling Approx 110 dBA limit
  • Sleeping mode 75 dBA at pillow
  • Candela Strobe light intensity
  • Spacing table Room size vs candela
  • Sync rule Avoid seizure flash rate

Codes & Testing CO

  • Ch 10 Fundamentals and power
  • Ch 14 Inspection, testing, maintenance
  • Ch 17 Initiating devices
  • Ch 18 Notification appliances
  • Ch 23 Protected premises pathways
  • AHJ Authority having jurisdiction
  • Smoke sensitivity Tested every 2 years
  • Record of Completion Documents installed system

Common Traps

Ionization vs photoelectric

  • Ion senses flaming ≠ Photo senses smoldering

Fixed-temp vs ROR

  • Fixed hits setpoint ≠ ROR senses rate

Class A vs Class B

  • Class A loops back ≠ Class B uses EOL

Supervisory vs trouble

  • Supervisory is impairment ≠ Trouble is wiring fault

Public vs private mode

  • Public adds 15 dB ≠ Private adds 10 dB

Initiating vs notification

  • Chapter 17 inputs ≠ Chapter 18 outputs

Standby vs alarm time

  • Standby is 24 h ≠ Alarm is 5 min

Last Minute

  • 1. Open book: NFPA 72 + 70 on-screen
  • 2. 85 questions in 110 minutes
  • 3. Pass = 500 on 0-700 scale
  • 4. Priority: alarm > supervisory > trouble
  • 5. Ion = flaming; photo = smoldering
  • 6. Fixed = setpoint; ROR = rate change
  • 7. Class A = loop; B = EOL
  • 8. Battery: 24 h standby + alarm
  • 9. Apply 1.2 battery safety factor
  • 10. Public mode = ambient + 15 dB
  • 11. Pull station handle 42-60 in
  • 12. Wall strobe lens 80-96 in

NICET Fire Alarm Systems Level I

  • Practice Questions 100 questions Study Guide 8 topics Cheat Sheet 83 facts Flashcards 50 cards Free CE Podcast