Cheat sheet
NICET Fire Alarm Level I Cheat Sheet
System Fundamentals & Devices
- 30-40% of exam
- Smoke Detectors Heat Detectors Pull Stations Waterflow FACP Signal Types
Circuits & Power
- 25-30% of exam
- Circuit Classes IDC/SLC/NAC NEC 760 Primary Power Battery Standby Supervision
Installation & Mounting
- 15-20% of exam
- Mounting Heights Detector Spacing Candela Spacing Audibility Plan Symbols
Codes, Testing & Inspection
- 10-15% of exam
- NFPA 72 Chapters AHJ Test Frequency Sensitivity Record of Completion
Quick Facts
- Exam NICET FAS-I
- Questions 85 MCQ
- Time 110 min
- Pass 500/700
- Format Open book
- Codes NFPA 72/70
- Fee $230
- Level Entry technician
Signal Priority DE
- Alarm beats Supervisory beats Trouble
- Alarm: fire Supervisory: impairment Trouble: fault Highest: alarm
Ionization vs Photoelectric DE
Ionization
- Flaming fires
- Small particles
- Radioactive source
Photoelectric
- Smoldering fires
- Large particles
- Light scatter
- Flaming vs smoldering
Which Detector Type? DE
- Smoldering fire risk → Photoelectric ( Visible particles )
- Flaming fire risk → Ionization ( Small particles )
- Large open hall → Beam detector ( Long range )
- Dusty/dirty area → Heat detector ( Avoid false alarm )
- High-value early warning → Aspirating ( Air sampling )
- Rapid temperature jump → ROR heat ( Rate change )
- Steady high heat → Fixed-temp heat ( Setpoint )
- HVAC smoke spread → Duct detector ( Shut fan )
Smoke Detectors DE
- Ionization Fast flaming fires
- Photoelectric Slow smoldering fires
- Beam Large open areas
- Aspirating Air-sample very-early warning
- Duct detector Sample HVAC airflow
- Spacing 30 ft on-center
- Off wall 4 in minimum
Smoke Memory DE
- Ion flames fast, Photo smolders slow
- Ion: flaming Photo: smoldering
Fixed-temp vs ROR Heat DE
Fixed-temp
- Reaches setpoint
- 135-174 F
- Will not reset
ROR
- Rate of change
- 12-15 F/min
- Self-restoring
- Setpoint vs rate
Heat Detectors DE
- Fixed-temp Activates at setpoint
- ROR Rate-of-rise change
- ROR rate 12-15 F/min rise
- Ordinary rating 135-174 F
- Line-type Cable senses length
- Combination Fixed plus ROR
Alarm vs Super vs Trouble DE
Alarm
- Fire detected
- Smoke or waterflow
- Highest priority
Super / Trouble
- Super: tamper, impairment
- Trouble: open, ground
- Lower priority
- Fire vs fault
Manual & Sprinkler DE
- Pull station Manual alarm initiation
- Single-action One pull motion
- Double-action Push-then-pull
- Near exits Within 5 ft
- Waterflow Sprinkler flow alarm
- Tamper switch Valve supervisory signal
- Retard chamber Ignores surge transients
Notification Appliances DE
- Horn Audible only
- Strobe Visible candela flash
- Horn/strobe Audible plus visible
- Speaker Voice EVACS output
- Temporal-3 Standard evacuation pattern
- 520 Hz Sleeping-area low frequency
- Sync Strobes flash together
Control Unit & Signals DE
- FACP Fire alarm control panel
- Conventional Zone-based addressing
- Addressable Per-device point ID
- Alarm Fire condition signal
- Supervisory System impairment signal
- Trouble Fault or open signal
- Annunciator Remote status display
Battery Calc CI
- 24 h standby plus 5 min alarm
- Standby Ah Alarm Ah Add both Times 1.2
Class A vs Class B CI
Class A
- Return loop
- Survives one open
- No EOL resistor
Class B
- No return
- Open stops devices
- EOL resistor
- Redundant vs simple
Class A vs Class B? CI
- Survive single open → Class A ( Return loop )
- Simple, lower cost → Class B ( EOL resistor )
- Need fault isolation → Class X ( Short tolerant )
- Network backbone → Class N ( Ethernet )
- End-of-line on B → EOL resistor ( Supervision )
- Both wire paths used → Class A ( Out and back )
Circuit Classes CI
- Class B No return path
- Class A Redundant return loop
- Class X Loop with fault isolation
- Class N Ethernet network path
- EOL resistor Class B supervision end
- Single fault Class A keeps operating
Circuit Classes CI
- A loops, B ends, X isolates, N networks
- A: redundant B: EOL X: fault isolate N: ethernet
IDC vs SLC vs NAC CI
IDC / SLC
- IDC: conventional inputs
- SLC: addressable poll
- Both initiate
NAC
- Drives appliances
- Horns and strobes
- Polarized output
- Input vs output
Battery Sizing Steps CI
- Sum standby current → Standby amps ( Quiescent )
- Multiply by 24 h → Standby Ah ( Ah )
- Sum alarm current → Alarm amps ( All NACs )
- Multiply by 5 min → Alarm Ah ( 5/60 hour )
- Add both totals → Required Ah ( Subtotal )
- Apply derating → Times 1.2 ( Safety factor )
Pathways & Wiring CI
- IDC Initiating device circuit
- SLC Signaling line circuit
- NAC Notification appliance circuit
- Polarity NAC devices polarized
- Survivability Pathway protected from fire
- Ground fault Unwanted earth path
- Supervision Detects opens/shorts
NEC 760 Cable CI
- FPL, then Riser, then Plenum
- FPL: general FPLR: riser FPLP: plenum
Primary vs Secondary Power CI
Primary
- Utility branch
- Dedicated circuit
- Normal supply
Secondary
- Standby battery
- 24 h plus 5 min
- AC-loss backup
- Mains vs backup
NEC Article 760 CI
- PLFA Power-limited fire alarm
- NPLFA Non-power-limited fire alarm
- FPL General cable type
- FPLR Riser-rated cable
- FPLP Plenum-rated cable
- Separation Apart from power
- Red jacket Common FA marking
Power & Battery CI
- Primary Utility branch circuit
- Secondary Standby battery backup
- Standby 24 h supervisory load
- Alarm load 5 min after standby
- Safety factor Multiply 1.2 result
- Charger Supervised, recharges battery
- AC loss Trouble signal generated
Mounting Heights IN
- Pull handle 42-60 in AFF
- Reach max 48 in ADA
- Wall strobe 80-96 in lens
- Ceiling strobe Per listed spacing
- Smoke spacing 30 ft on-center
- Beam ceiling Reduce spacing per depth
- Off wall Detector 4 in min
Audibility & Candela IN
- Public mode Plus 15 dB ambient
- Private mode Plus 10 dB ambient
- Max ceiling Approx 110 dBA limit
- Sleeping mode 75 dBA at pillow
- Candela Strobe light intensity
- Spacing table Room size vs candela
- Sync rule Avoid seizure flash rate
Codes & Testing CO
- Ch 10 Fundamentals and power
- Ch 14 Inspection, testing, maintenance
- Ch 17 Initiating devices
- Ch 18 Notification appliances
- Ch 23 Protected premises pathways
- AHJ Authority having jurisdiction
- Smoke sensitivity Tested every 2 years
- Record of Completion Documents installed system
Common Traps
Ionization vs photoelectric
- Ion senses flaming ≠ Photo senses smoldering
Fixed-temp vs ROR
- Fixed hits setpoint ≠ ROR senses rate
Class A vs Class B
- Class A loops back ≠ Class B uses EOL
Supervisory vs trouble
- Supervisory is impairment ≠ Trouble is wiring fault
Public vs private mode
- Public adds 15 dB ≠ Private adds 10 dB
Initiating vs notification
- Chapter 17 inputs ≠ Chapter 18 outputs
Standby vs alarm time
- Standby is 24 h ≠ Alarm is 5 min
Last Minute
- 1. Open book: NFPA 72 + 70 on-screen
- 2. 85 questions in 110 minutes
- 3. Pass = 500 on 0-700 scale
- 4. Priority: alarm > supervisory > trouble
- 5. Ion = flaming; photo = smoldering
- 6. Fixed = setpoint; ROR = rate change
- 7. Class A = loop; B = EOL
- 8. Battery: 24 h standby + alarm
- 9. Apply 1.2 battery safety factor
- 10. Public mode = ambient + 15 dB
- 11. Pull station handle 42-60 in
- 12. Wall strobe lens 80-96 in
NICET Fire Alarm Systems Level I