Cheat sheet

Oklahoma Journeyman Electrician Cheat Sheet

Practice this exam

General Knowledge

  • 4% of exam
  • Permits & Inspections Structural Integrity Estimating & Bids Contractor Liability

General Electrical Knowledge

  • 10% of exam
  • Ohm's Law 3-Phase Power Voltage Drop NEC Navigation Temporary Wiring

Electrical Installation Requirements

  • 10% of exam
  • Working Space Equipment Listing Termination Ratings Over 600V Rules

Services, Feeders & Branch Circuits

  • 10% of exam
  • Service Disconnects Continuous Loads Multiwire Circuits Feeder Taps

Overcurrent Protection

  • 9% of exam
  • Standard Ratings Small Conductor Rule Tap Rules Restricted Locations

Grounding & Bonding

  • 10% of exam
  • Grounding Electrodes GEC Sizing EGC Sizing Bonding Jumpers

Conductors & Cables

  • 8% of exam
  • THHN vs THWN Cable Types Underground Conductors Medium Voltage

Raceways & Boxes

  • 7% of exam
  • Box Fill Conduit Fill Bend Limits Raceway Selection

Special Occupancies & Equipment

  • 10% of exam
  • Hazardous Locations Swimming Pools Health Care Mobile Homes

Low Voltage & Communications

  • 2% of exam
  • Class 1/2/3 Circuits Fire Alarms Fiber & PV Low-Voltage Lighting

Lighting & Signs

  • 10% of exam
  • Closet Clearance Damp & Wet Zones IC-Rated Fixtures Sign Disconnects

Safety

  • 4% of exam
  • Fall Protection Trench Safety PPE Basics Job-Site Hazards

Motors & Transformers

  • 6% of exam
  • Motor FLC Sizing Motor Disconnects Transformer Protection In Sight Rule

Quick Facts

  • Exam OK Unlimited Journeyman
  • Items 100 scored
  • Time 240 min
  • Pass 70%
  • Code 2023 NEC
  • Format Open book
  • Retake 30 days
  • Experience 8,000 hours

Permits & Estimating GE

  • Permit puller Licensed contractor of record
  • Inspection Required before energizing work
  • Needs analysis Scope before estimating a job
  • Estimating Labor, material, and code compliance

NEC Article Finder GE

  • Need working space depth → 110.26(A)(1) ( Table by ground volts )
  • Need working space width → 110.26(A)(2) ( 30 in or equipment )
  • Need working space height → 110.26(A)(3) ( 6.5 ft headroom )
  • Check termination temp rating → 110.14(C) ( 60C at or under 100A )
  • Confirm equipment install rules → 110.3(B) ( Follow the listing instructions )
  • Need fire-rated penetration rule → 300.21 ( Firestop the opening )

Ohm's & Watt's Law GE

  • E = I x R Volts from amps, ohms
  • P = E x I Watts from volts, amps
  • Series R Add all resistances
  • Parallel R Lowest R gets most current
  • kWh Cost kW x hours x rate
  • Voltage Drop 3% branch, 5% total note

AC & 3-Phase Basics GE

  • Wye (Y) Line = phase x 1.732
  • Delta Line equals phase voltage
  • 208Y/120V 120 x 1.732 = 208
  • Power Factor True power vs apparent
  • RMS Voltage Effective AC value
  • Frequency 60 Hz U.S. standard

Listed vs Labeled IN

Listed

  • On a tester's published list
  • Includes follow-up inspection

Labeled

  • Physical mark on the product
  • Meets an identified standard
  • List entry vs physical mark

Working Space & Listing IN

  • 110.26(A)(1) Depth by ground voltage
  • 110.26(A)(2) Width: 30 in or equipment
  • 110.26(A)(3) Height: 6.5 ft minimum
  • 110.14(C) 60C at or under 100A
  • 110.3(B) Follow the listing instructions
  • 300.21 Firestop fire-rated penetrations

125% Rule SE

  • 125% covers every continuous load calc
  • Branch conductor: 210.19 OCPD: 210.20(A) Motor conductor: 430.22

Service & Feeder Finder SE

  • How many service disconnects → 230.71 ( 1 default, 2-6 in (B) )
  • Size a continuous load → 210.19 & 210.20 ( 125% conductor and OCPD )
  • Multiwire circuit disconnect rule → 210.4(B) ( Simultaneous, all ungrounded conductors )
  • Check voltage drop target → 210.19 & 215.2 notes ( 3% branch, 5% total )
  • Feeder tap under 10 ft → 240.21(B)(1) ( Ampacity of the load )
  • Feeder tap under 25 ft → 240.21(B)(2) ( One-third feeder OCPD size )

Services & Disconnects SE

  • 230.71(A) One disconnect is the default
  • 230.71(B) Two to six disconnects allowed
  • 210.4(B) Simultaneous multiwire disconnect
  • 210.19 note 3% branch voltage drop
  • 215.2 note 5% total voltage drop
  • 210.19(A) 125% for continuous loads
  • 210.20(A) 125% sizes the breaker too

10-Foot vs 25-Foot Tap OV

10-ft tap

  • Ampacity of the load
  • One-tenth feeder OCPD outside

25-ft tap

  • One-third feeder OCPD size
  • Ends in one breaker
  • Distance sets the ratio

Overcurrent Rating Finder OV

  • Small copper conductor breaker cap → 240.4(D) ( 15A, 20A, 30A caps )
  • No standard size matches → 240.4(B) ( Next higher, 800A or less )
  • Device rated above 800A → 240.4(C) ( Ampacity must meet device )
  • Where breakers are barred → 240.24 ( Bathrooms, closets, stairways )
  • Transformer secondary protection case → 240.4(F) ( 2-wire or delta-delta 3-wire )

Overcurrent Standard Ratings OV

  • 240.4(D) 14 AWG 15A max breaker
  • 240.4(D) 12 AWG 20A max breaker
  • 240.4(D) 10 AWG 30A max breaker
  • 240.4(B) Next size up, 800A or less
  • 240.4(C) Above 800A: match ampacity
  • 240.6(A) Lists standard breaker sizes
  • 240.24 No breakers in bathrooms, closets

Feeder Tap Rules OV

  • 240.21(B)(1) 10 ft tap, ampacity of load
  • 240.21(B)(2) 25 ft tap, one-third feeder OCPD
  • 10-ft outside enclosure One-tenth feeder OCPD minimum
  • 25-ft tap ending Single breaker limits the tap

Rod, Ufer, Pool Numbers GR

  • 8 ft rod, 20 ft Ufer, 4 pool points
  • Rod: 8 ft long Ufer: 20 ft rebar Pool bond: 4 points

Grounding vs Bonding GR

Grounding

  • Ties system to earth
  • Uses electrode conductor

Bonding

  • Joins metal parts together
  • Carries fault current back
  • Earth path vs equipotential

Grounding Table Finder GR

  • Size grounding electrode conductor → Table 250.66 ( By largest service conductor )
  • Size equipment grounding conductor → Table 250.122 ( By breaker ampere rating )
  • Pick a grounding electrode → 250.52(A) ( Rod, Ufer, ring, or pipe )
  • Electrode type that is barred → 250.52(B) ( Gas pipe or aluminum )
  • Bond a swimming pool → 680.26(B) ( 3 ft perimeter, 4 points )

Grounding Electrodes GR

  • 250.52(A)(5) Ground rod: 8 ft, 0.625 in
  • 250.52(A)(3) Ufer: 20 ft rebar or copper
  • 250.52(A)(4) Ground ring: 20 ft, 2 AWG
  • 250.52(A)(1) Water pipe: 10 ft, needs supplement
  • 250.52(B) Gas pipe and aluminum barred

GEC vs EGC GR

GEC

  • Electrode to system
  • Sized from Table 250.66

EGC

  • Equipment back to source
  • Sized from Table 250.122
  • Different sizing tables entirely

GEC & EGC Sizing GR

  • Table 250.66 GEC sized by service conductor
  • Table 250.122 EGC sized by breaker rating
  • System bonding jumper SDS neutral-to-ground bond
  • Main bonding jumper Service panel neutral bond
  • Grounding vs bonding Earth path vs equipotential

THWN vs THWN-2 CO

THWN

  • 75C rating
  • Wet or dry rated

THWN-2

  • 90C rating
  • Wet and dry both
  • Dual marking wins ampacity

Conductor & Cable Types CO

  • THHN 90C, dry and damp
  • THWN 75C, wet locations rated
  • THWN-2 90C, wet and dry
  • UF cable Direct burial rated
  • NM cable Dry locations, no burial
  • AC cable Bonding strip aids grounding path
  • MC cable Separate wire-type EGC
  • MV cable 2,001-35,000 volts, Article 311

NM Cable vs UF Cable CO

NM

  • Dry locations only
  • Barred from underground burial

UF

  • Direct burial rated
  • Moisture-resistant sheath
  • Dry only vs burial rated

Conduit Fill Percentages RA

  • One wire 53, two wires 31, three-plus 40
  • 1 conductor = 53% 2 conductors = 31% 3+ conductors = 40%

Box & Conduit Fill RA

  • 14 AWG box fill 2.00 cubic inches each
  • 12 AWG box fill 2.25 cubic inches each
  • 10 AWG box fill 2.50 cubic inches each
  • 1 conductor fill 53% conduit maximum
  • 2 conductor fill 31% conduit maximum
  • 3+ conductor fill 40% conduit maximum
  • Bend limit 360 degrees between pull points
  • PVC conduit Needs separate wire EGC

Division 1 vs Division 2 SP

Division 1

  • Hazard present under normal use
  • Continuous or likely exposure

Division 2

  • Hazard only if abnormal
  • Failure or rupture triggers it
  • Normal vs abnormal presence

Hazard & Motor Finder SP

  • Flammable gas or vapor present → Class I ( Spray booths, fuel areas )
  • Combustible dust is present → Class II ( Grain or flour handling )
  • Ignitible fibers or flyings → Class III ( Textile or sawmill areas )
  • Size a motor conductor → 430.22 ( 125% of table FLC )
  • Locate a motor disconnect → 430.102(B) ( In sight of motor )

Hazardous & Special Occupancies SP

  • Class I Flammable gas or vapor
  • Class II Combustible dust present
  • Class III Ignitible fibers or flyings
  • Division 1 Hazard present under normal use
  • Division 2 Hazard only if abnormal
  • 680.26(B)(2) Pool perimeter: 3 ft, 4 points
  • 517.13 Hospital: raceway plus wire EGC
  • 550.32 Mobile home service: 30 ft
  • 422.16(B)(5) OK furnace cord: 9 ft

Class Circuit Article Shift LO

  • Class 1 moved to Article 724 now
  • Class 1 = Article 724 Class 2 and 3 = 725

Low Voltage Circuits LO

  • Article 724 Class 1 power-limited circuits
  • Article 725 Class 2 and 3 circuits
  • Class 2 source Listed transformer limits power
  • In sight from Visible, 50 ft or less

Lighting & Signs Rules LI

  • 410.16(C) surface Closet surface fixture: 12 in
  • 410.16(C) recessed Closet recessed fixture: 6 in
  • 410.10(D) Bath zone: 3 ft, 8 ft
  • 410.116(A) Non-IC: 0.5 in from combustibles
  • 600.6(A) Sign disconnect: three locations allowed
  • 410.130(G)(1) Ballast swap needs new disconnect
  • 410.16(B) No open lamps or pendants

OSHA Safety Basics SA

  • 1926.501(b)(1) Fall protection at 6 ft
  • 1926.451(g)(1) Scaffold fall protection at 10 ft
  • 1926.652(a)(1) Excavation protection at 5 ft
  • Competent person Inspects trenches daily
  • Fall arrest Full-body harness required

Motor & Transformer Rules MO

  • 430.22 Motor conductor: 125% of FLC
  • 430.6(A)(1) Use table FLC, not nameplate
  • 430.102(A) Controller disconnect in sight
  • 240.4(F) Primary device protects some secondaries
  • Table 430.250 Three-phase motor FLC values

Common Traps

Voltage To Ground vs Line

  • Table 110.26 uses ground volts ≠ Not line-to-line voltage

Informational Note vs Mandatory Rule

  • 3% and 5% drop is advisory ≠ 240.4(D) caps are mandatory

Listed vs Labeled

  • Listed means on a list ≠ Labeled means a physical mark

Service Disconnect Count

  • 230.71(A) default is one ≠ 230.71(B) allows two to six

Class 1 vs Class 2 and 3

  • Class 1 now sits in 724 ≠ Class 2/3 stays at 725

OK GFCI Amendment

  • Oklahoma exempts lighting and HVAC ≠ Base rule covers all outlets

Last Minute

  • 1. Bound 2023 NEC only, no handbook
  • 2. Continuous loads size at 125%
  • 3. GEC size: use Table 250.66
  • 4. EGC size: use Table 250.122
  • 5. Ground rod: 8 ft, 0.625 in
  • 6. Conduit fill: 3+ wires max 40%
  • 7. Raceway bends: max 360° total
  • 8. OSHA trenches: 5 ft needs protection
  • 9. OSHA falls: 6 ft general trigger
  • 10. Scaffold fall trigger: 10 ft high
  • 11. Class 1: Article 724, not 725
  • 12. OK allows temp cord-connected gas furnace
  • 13. OK GFCI rule skips lighting, HVAC
  • 14. Service disconnects: 1 default, 6 max

Oklahoma Journeyman Electrician