Cheat sheet
Oklahoma Journeyman Electrician Cheat Sheet
General Knowledge
- 4% of exam
- Permits & Inspections Structural Integrity Estimating & Bids Contractor Liability
General Electrical Knowledge
- 10% of exam
- Ohm's Law 3-Phase Power Voltage Drop NEC Navigation Temporary Wiring
Electrical Installation Requirements
- 10% of exam
- Working Space Equipment Listing Termination Ratings Over 600V Rules
Services, Feeders & Branch Circuits
- 10% of exam
- Service Disconnects Continuous Loads Multiwire Circuits Feeder Taps
Overcurrent Protection
- 9% of exam
- Standard Ratings Small Conductor Rule Tap Rules Restricted Locations
Grounding & Bonding
- 10% of exam
- Grounding Electrodes GEC Sizing EGC Sizing Bonding Jumpers
Conductors & Cables
- 8% of exam
- THHN vs THWN Cable Types Underground Conductors Medium Voltage
Raceways & Boxes
- 7% of exam
- Box Fill Conduit Fill Bend Limits Raceway Selection
Special Occupancies & Equipment
- 10% of exam
- Hazardous Locations Swimming Pools Health Care Mobile Homes
Low Voltage & Communications
- 2% of exam
- Class 1/2/3 Circuits Fire Alarms Fiber & PV Low-Voltage Lighting
Lighting & Signs
- 10% of exam
- Closet Clearance Damp & Wet Zones IC-Rated Fixtures Sign Disconnects
Safety
- 4% of exam
- Fall Protection Trench Safety PPE Basics Job-Site Hazards
Motors & Transformers
- 6% of exam
- Motor FLC Sizing Motor Disconnects Transformer Protection In Sight Rule
Quick Facts
- Exam OK Unlimited Journeyman
- Items 100 scored
- Time 240 min
- Pass 70%
- Code 2023 NEC
- Format Open book
- Retake 30 days
- Experience 8,000 hours
Permits & Estimating GE
- Permit puller Licensed contractor of record
- Inspection Required before energizing work
- Needs analysis Scope before estimating a job
- Estimating Labor, material, and code compliance
NEC Article Finder GE
- Need working space depth → 110.26(A)(1) ( Table by ground volts )
- Need working space width → 110.26(A)(2) ( 30 in or equipment )
- Need working space height → 110.26(A)(3) ( 6.5 ft headroom )
- Check termination temp rating → 110.14(C) ( 60C at or under 100A )
- Confirm equipment install rules → 110.3(B) ( Follow the listing instructions )
- Need fire-rated penetration rule → 300.21 ( Firestop the opening )
Ohm's & Watt's Law GE
- E = I x R Volts from amps, ohms
- P = E x I Watts from volts, amps
- Series R Add all resistances
- Parallel R Lowest R gets most current
- kWh Cost kW x hours x rate
- Voltage Drop 3% branch, 5% total note
AC & 3-Phase Basics GE
- Wye (Y) Line = phase x 1.732
- Delta Line equals phase voltage
- 208Y/120V 120 x 1.732 = 208
- Power Factor True power vs apparent
- RMS Voltage Effective AC value
- Frequency 60 Hz U.S. standard
Listed vs Labeled IN
Listed
- On a tester's published list
- Includes follow-up inspection
Labeled
- Physical mark on the product
- Meets an identified standard
- List entry vs physical mark
Working Space & Listing IN
- 110.26(A)(1) Depth by ground voltage
- 110.26(A)(2) Width: 30 in or equipment
- 110.26(A)(3) Height: 6.5 ft minimum
- 110.14(C) 60C at or under 100A
- 110.3(B) Follow the listing instructions
- 300.21 Firestop fire-rated penetrations
125% Rule SE
- 125% covers every continuous load calc
- Branch conductor: 210.19 OCPD: 210.20(A) Motor conductor: 430.22
Service & Feeder Finder SE
- How many service disconnects → 230.71 ( 1 default, 2-6 in (B) )
- Size a continuous load → 210.19 & 210.20 ( 125% conductor and OCPD )
- Multiwire circuit disconnect rule → 210.4(B) ( Simultaneous, all ungrounded conductors )
- Check voltage drop target → 210.19 & 215.2 notes ( 3% branch, 5% total )
- Feeder tap under 10 ft → 240.21(B)(1) ( Ampacity of the load )
- Feeder tap under 25 ft → 240.21(B)(2) ( One-third feeder OCPD size )
Services & Disconnects SE
- 230.71(A) One disconnect is the default
- 230.71(B) Two to six disconnects allowed
- 210.4(B) Simultaneous multiwire disconnect
- 210.19 note 3% branch voltage drop
- 215.2 note 5% total voltage drop
- 210.19(A) 125% for continuous loads
- 210.20(A) 125% sizes the breaker too
10-Foot vs 25-Foot Tap OV
10-ft tap
- Ampacity of the load
- One-tenth feeder OCPD outside
25-ft tap
- One-third feeder OCPD size
- Ends in one breaker
- Distance sets the ratio
Overcurrent Rating Finder OV
- Small copper conductor breaker cap → 240.4(D) ( 15A, 20A, 30A caps )
- No standard size matches → 240.4(B) ( Next higher, 800A or less )
- Device rated above 800A → 240.4(C) ( Ampacity must meet device )
- Where breakers are barred → 240.24 ( Bathrooms, closets, stairways )
- Transformer secondary protection case → 240.4(F) ( 2-wire or delta-delta 3-wire )
Overcurrent Standard Ratings OV
- 240.4(D) 14 AWG 15A max breaker
- 240.4(D) 12 AWG 20A max breaker
- 240.4(D) 10 AWG 30A max breaker
- 240.4(B) Next size up, 800A or less
- 240.4(C) Above 800A: match ampacity
- 240.6(A) Lists standard breaker sizes
- 240.24 No breakers in bathrooms, closets
Feeder Tap Rules OV
- 240.21(B)(1) 10 ft tap, ampacity of load
- 240.21(B)(2) 25 ft tap, one-third feeder OCPD
- 10-ft outside enclosure One-tenth feeder OCPD minimum
- 25-ft tap ending Single breaker limits the tap
Rod, Ufer, Pool Numbers GR
- 8 ft rod, 20 ft Ufer, 4 pool points
- Rod: 8 ft long Ufer: 20 ft rebar Pool bond: 4 points
Grounding vs Bonding GR
Grounding
- Ties system to earth
- Uses electrode conductor
Bonding
- Joins metal parts together
- Carries fault current back
- Earth path vs equipotential
Grounding Table Finder GR
- Size grounding electrode conductor → Table 250.66 ( By largest service conductor )
- Size equipment grounding conductor → Table 250.122 ( By breaker ampere rating )
- Pick a grounding electrode → 250.52(A) ( Rod, Ufer, ring, or pipe )
- Electrode type that is barred → 250.52(B) ( Gas pipe or aluminum )
- Bond a swimming pool → 680.26(B) ( 3 ft perimeter, 4 points )
Grounding Electrodes GR
- 250.52(A)(5) Ground rod: 8 ft, 0.625 in
- 250.52(A)(3) Ufer: 20 ft rebar or copper
- 250.52(A)(4) Ground ring: 20 ft, 2 AWG
- 250.52(A)(1) Water pipe: 10 ft, needs supplement
- 250.52(B) Gas pipe and aluminum barred
GEC vs EGC GR
GEC
- Electrode to system
- Sized from Table 250.66
EGC
- Equipment back to source
- Sized from Table 250.122
- Different sizing tables entirely
GEC & EGC Sizing GR
- Table 250.66 GEC sized by service conductor
- Table 250.122 EGC sized by breaker rating
- System bonding jumper SDS neutral-to-ground bond
- Main bonding jumper Service panel neutral bond
- Grounding vs bonding Earth path vs equipotential
THWN vs THWN-2 CO
THWN
- 75C rating
- Wet or dry rated
THWN-2
- 90C rating
- Wet and dry both
- Dual marking wins ampacity
Conductor & Cable Types CO
- THHN 90C, dry and damp
- THWN 75C, wet locations rated
- THWN-2 90C, wet and dry
- UF cable Direct burial rated
- NM cable Dry locations, no burial
- AC cable Bonding strip aids grounding path
- MC cable Separate wire-type EGC
- MV cable 2,001-35,000 volts, Article 311
NM Cable vs UF Cable CO
NM
- Dry locations only
- Barred from underground burial
UF
- Direct burial rated
- Moisture-resistant sheath
- Dry only vs burial rated
Conduit Fill Percentages RA
- One wire 53, two wires 31, three-plus 40
- 1 conductor = 53% 2 conductors = 31% 3+ conductors = 40%
Box & Conduit Fill RA
- 14 AWG box fill 2.00 cubic inches each
- 12 AWG box fill 2.25 cubic inches each
- 10 AWG box fill 2.50 cubic inches each
- 1 conductor fill 53% conduit maximum
- 2 conductor fill 31% conduit maximum
- 3+ conductor fill 40% conduit maximum
- Bend limit 360 degrees between pull points
- PVC conduit Needs separate wire EGC
Division 1 vs Division 2 SP
Division 1
- Hazard present under normal use
- Continuous or likely exposure
Division 2
- Hazard only if abnormal
- Failure or rupture triggers it
- Normal vs abnormal presence
Hazard & Motor Finder SP
- Flammable gas or vapor present → Class I ( Spray booths, fuel areas )
- Combustible dust is present → Class II ( Grain or flour handling )
- Ignitible fibers or flyings → Class III ( Textile or sawmill areas )
- Size a motor conductor → 430.22 ( 125% of table FLC )
- Locate a motor disconnect → 430.102(B) ( In sight of motor )
Hazardous & Special Occupancies SP
- Class I Flammable gas or vapor
- Class II Combustible dust present
- Class III Ignitible fibers or flyings
- Division 1 Hazard present under normal use
- Division 2 Hazard only if abnormal
- 680.26(B)(2) Pool perimeter: 3 ft, 4 points
- 517.13 Hospital: raceway plus wire EGC
- 550.32 Mobile home service: 30 ft
- 422.16(B)(5) OK furnace cord: 9 ft
Class Circuit Article Shift LO
- Class 1 moved to Article 724 now
- Class 1 = Article 724 Class 2 and 3 = 725
Low Voltage Circuits LO
- Article 724 Class 1 power-limited circuits
- Article 725 Class 2 and 3 circuits
- Class 2 source Listed transformer limits power
- In sight from Visible, 50 ft or less
Lighting & Signs Rules LI
- 410.16(C) surface Closet surface fixture: 12 in
- 410.16(C) recessed Closet recessed fixture: 6 in
- 410.10(D) Bath zone: 3 ft, 8 ft
- 410.116(A) Non-IC: 0.5 in from combustibles
- 600.6(A) Sign disconnect: three locations allowed
- 410.130(G)(1) Ballast swap needs new disconnect
- 410.16(B) No open lamps or pendants
OSHA Safety Basics SA
- 1926.501(b)(1) Fall protection at 6 ft
- 1926.451(g)(1) Scaffold fall protection at 10 ft
- 1926.652(a)(1) Excavation protection at 5 ft
- Competent person Inspects trenches daily
- Fall arrest Full-body harness required
Motor & Transformer Rules MO
- 430.22 Motor conductor: 125% of FLC
- 430.6(A)(1) Use table FLC, not nameplate
- 430.102(A) Controller disconnect in sight
- 240.4(F) Primary device protects some secondaries
- Table 430.250 Three-phase motor FLC values
Common Traps
Voltage To Ground vs Line
- Table 110.26 uses ground volts ≠ Not line-to-line voltage
Informational Note vs Mandatory Rule
- 3% and 5% drop is advisory ≠ 240.4(D) caps are mandatory
Listed vs Labeled
- Listed means on a list ≠ Labeled means a physical mark
Service Disconnect Count
- 230.71(A) default is one ≠ 230.71(B) allows two to six
Class 1 vs Class 2 and 3
- Class 1 now sits in 724 ≠ Class 2/3 stays at 725
OK GFCI Amendment
- Oklahoma exempts lighting and HVAC ≠ Base rule covers all outlets
Last Minute
- 1. Bound 2023 NEC only, no handbook
- 2. Continuous loads size at 125%
- 3. GEC size: use Table 250.66
- 4. EGC size: use Table 250.122
- 5. Ground rod: 8 ft, 0.625 in
- 6. Conduit fill: 3+ wires max 40%
- 7. Raceway bends: max 360° total
- 8. OSHA trenches: 5 ft needs protection
- 9. OSHA falls: 6 ft general trigger
- 10. Scaffold fall trigger: 10 ft high
- 11. Class 1: Article 724, not 725
- 12. OK allows temp cord-connected gas furnace
- 13. OK GFCI rule skips lighting, HVAC
- 14. Service disconnects: 1 default, 6 max
Oklahoma Journeyman Electrician
- Practice Questions 344 questions Study Guide 62 topics Cheat Sheet 96 facts Flashcards 50 cards Shorts 3 short s Videos 1 video Blogs 8 blogs Free CE Podcast