Cheat sheet

RETA CARO Cheat Sheet

Practice this exam

Fundamentals & Cycle

  • 30% of exam
  • Refrigeration Fundamentals Vapor-Compression Cycle Ammonia Properties Saturated P-T Tables

Compressors & Lubrication

  • 32% of exam
  • Compressor Types Operation & Maintenance Lubrication Troubleshooting

Heat Exchangers & Purging

  • 26% of exam
  • Evaporators Condensers & Receivers Purging Defrost

Safety & Compliance

  • 12% of exam
  • Ammonia Exposure Limits PSM & RMP IIAR Standards Emergency Response

Quick Facts

  • Exam RETA CARO
  • Credential Asst Refrigeration Operator
  • Time 3 hours
  • Pass 70%
  • Questions 110 multiple-choice
  • Refrigerant R-717 (ammonia)
  • Level Entry, no experience
  • Fee 2026 $570 member, $865 nonmember

Cycle Flow Order FU

  • Compress, Condense, Expand, Evaporate, repeat
  • Compressor: raise pressure Condenser: reject heat Expansion valve: drop pressure Evaporator: absorb heat

High Side vs Low Side FU

High side

  • Compressor discharge to TXV inlet
  • Condenser, receiver, discharge line
  • Higher pressure and temperature

Low side

  • TXV outlet to compressor suction
  • Evaporator, suction line, accumulator
  • Lower pressure and temperature
  • Split is at metering device

Which Component Handles This FU

  • Need to absorb heat → Evaporator
  • Need to reject heat → Condenser
  • Need pressure/temp boost → Compressor
  • Need pressure drop to low side → Expansion valve
  • Store high-pressure liquid → Receiver
  • Remove oil from discharge gas → Oil separator
  • Remove trapped air/non-condensables → Purger
  • Prevent liquid entering compressor → Accumulator

Refrigeration Fundamentals FU

  • Ton 12,000 Btu/hr
  • Btu Heat unit
  • Sensible heat Changes temperature
  • Latent heat Changes state, not temp
  • Superheat Above saturation, vapor side
  • Subcooling Below saturation, liquid side

Pressure-Temperature Law FU

  • Higher pressure always means higher saturation temp
  • Use for troubleshooting Read gauge, find temp Confirms proper charge level

Vapor-Compression Cycle FU

  • Compressor Raises pressure and temp
  • Condenser Rejects heat, high side
  • Expansion valve Drops pressure to low side
  • Evaporator Absorbs heat, low side
  • Flow order Comp-Cond-Expand-Evap-Comp

Ammonia Physical Properties FU

  • ASHRAE ID R-717
  • Boiling point -28°F at atmospheric
  • Vapor density 0.6, lighter than air
  • Liquid specific gravity 0.62, lighter than water
  • Ignition temp 1,204°F
  • Flammable range 15-28% in air
  • Odor threshold 5-50 ppm
  • Refrigerant-grade purity 99.95%+ ammonia

Saturated Pressure-Temperature FU

  • 28°F 0 psig, atmospheric boil
  • 0°F 16 psig
  • 68°F 110 psig
  • 100°F 198 psig
  • P-T rule Higher temp = higher pressure

Refrigerant Purity Limits CO

  • Water 33 ppm max, oil 2 ppm max
  • Water: freezes, cracks piping Oxygen: stress-corrosion risk Oil: fouls heat transfer Test periodically for purity

Reciprocating vs Screw Compressor CO

Reciprocating

  • Pistons, positive displacement
  • Best at high pressure ratios
  • Unloaders step capacity

Screw

  • Rotors, continuous compression
  • Best at high volume flow
  • Slide valve modulates capacity
  • Piston strokes vs rotor mesh

Troubleshooting Symptom Picker CO

  • High head pressure, clean condenser → Check for non-condensables ( Purge system )
  • Low suction, frosted coil → Check TXV or charge
  • Compressor short cycles rapidly → Check low-pressure control
  • Knocking noise at startup → Suspect liquid slugging
  • Low net oil pressure → Check oil charge, filter
  • Rising pressure, condenser clean → Suspect trapped air
  • Cooler warm, coil iced → Check defrost cycle

Compressor Types CO

  • Reciprocating Piston, positive displacement
  • Screw (rotary) Continuous, oil-flooded rotors
  • Centrifugal High-volume, low-pressure-rise
  • Scroll Orbiting spiral, small capacity

Oil Separator vs Purger CO

Oil separator

  • Removes oil from hot gas
  • Located after compressor discharge
  • Returns oil to system

Purger

  • Removes air/non-condensables
  • Located at condenser/receiver high point
  • Vents gas, saves ammonia
  • Oil vs trapped air removal

Compressor Operation & Controls CO

  • Compression ratio Absolute discharge / absolute suction
  • Volumetric efficiency Actual / theoretical displacement
  • Unloaders Reduce startup/part-load capacity
  • Slide valve Screw compressor capacity control
  • Liquid slugging Liquid enters cylinder, damages valves
  • Short cycling Frequent start-stop, control fault

Lubrication & Oil Management CO

  • Ammonia-oil miscibility Not miscible, oil settles
  • Oil separator Removes oil from discharge gas
  • Oil pot Low-point oil collection, draining
  • Net oil pressure Discharge minus crankcase pressure
  • Safe oil draining Relieve pressure, PPE, slow bleed
  • Synthetic oil Better low-temp flow

Flooded vs DX Evaporator HE

Flooded

  • Liquid-full coil, float control
  • High efficiency, needs surge drum
  • Common on large systems

DX (dry expansion)

  • TXV controls superheat, not level
  • Simpler, less ammonia charge
  • Common on smaller systems
  • Control point: level vs superheat

Evaporators & Cooling Units HE

  • DX evaporator Superheat-controlled by TXV
  • Flooded evaporator Liquid-full, float level control
  • Frost buildup Insulates, reduces heat transfer
  • Defrost Removes frost, restores capacity
  • Accumulator Traps liquid before compressor

Defrost Methods HE

  • Hot gas defrost Discharge gas heats coil
  • Water defrost Spray water over coil
  • Electric defrost Resistance heaters melt frost
  • Air defrost Fans only, mild loads

Condensers & Receivers HE

  • Evaporative condenser Water spray plus airflow
  • Air-cooled condenser Fans only, no water
  • High-pressure receiver Stores liquid after condenser
  • King valve Receiver liquid outlet valve
  • Relief valve Vents overpressure to atmosphere/flare

Purging Non-Condensables HE

  • Non-condensables Air, trapped gas in system
  • Symptom High head pressure, poor cooling
  • Purger Automatically vents trapped air
  • Verification Check purge log, discharge rate

Exposure Limit Ladder SA

  • Odor, then PEL, STEL, IDLH rising
  • Odor: 5-50 ppm warns PEL: 50 ppm 8-hr STEL: 35 ppm 15-min IDLH: 300 ppm, escape now

PSM vs RMP SA

OSHA PSM

  • 29 CFR 1910.119
  • Protects workers on-site
  • Enforced by OSHA

EPA RMP

  • 40 CFR Part 68
  • Protects surrounding community
  • Enforced by EPA
  • Same 10,000 lb trigger, different focus

Ammonia Leak Response SA

  • Detector alarm, low level → Investigate, increase ventilation ( Below PEL )
  • Smell ammonia, unknown source → Don SCBA, evacuate area ( Odor threshold ~5ppm )
  • Small controllable leak → Isolate valve, ventilate space
  • Large uncontrolled release → Evacuate, sound alarm, call ERT
  • Concentration near IDLH → SCBA only, no filter mask
  • Ammonia vapor cloud, fire risk → Apply water fog, not stream
  • Victim exposed, skin/eyes → Flush 15+ min, remove clothing

Ammonia Exposure Limits SA

  • PEL 50 ppm, 8-hour TWA
  • STEL 35 ppm, 15-minute
  • IDLH 300 ppm
  • Odor threshold 5-50 ppm, self-warning

PEL vs IDLH SA

PEL

  • 50 ppm, 8-hour average
  • Routine daily exposure limit
  • Below this, normal operation

IDLH

  • 300 ppm
  • Immediate danger to life
  • Escape without injury only
  • Daily limit vs escape limit

PPE & Detection SA

  • SCBA Required above IDLH
  • Chemical suit Splash/vapor protection, high exposure
  • Fixed detectors Continuous ammonia monitoring, alarms
  • Water fog Knocks down vapor, dilutes
  • Eye/face protection Goggles plus face shield

PSM & RMP Compliance SA

  • Trigger quantity 10,000 lb ammonia
  • PSM authority OSHA 29 CFR 1910.119
  • RMP authority EPA 40 CFR 68
  • PHA Process hazard analysis
  • MOC Management of change
  • Mechanical integrity Inspect, test, maintain equipment

IIAR & Code Standards SA

  • IIAR 2 Safe system design
  • IIAR 6 Inspection, testing, maintenance
  • IIAR 7 Operating procedures
  • IIAR 9 Minimum safety, existing systems
  • ASHRAE 15 Refrigeration safety standard

Common Traps

Ammonia and Oil

  • Ammonia dissolves easily in water ≠ Ammonia does not mix with oil

PSM vs RMP Focus

  • PSM protects workers on-site ≠ RMP protects the surrounding community

PEL vs IDLH Meaning

  • PEL is a routine daily limit ≠ IDLH means leave immediately

High Side vs Low Side

  • High side runs hot and high-pressure ≠ Low side runs cold and low-pressure

Flooded vs DX Control

  • Flooded evaporator controls liquid level ≠ DX evaporator controls suction superheat

Oil Separator vs Purger Job

  • Oil separator returns oil, not gas ≠ Purger vents air, not oil

Compression Ratio vs Efficiency

  • Ratio compares absolute pressures only ≠ Efficiency compares actual to swept volume

Last Minute

  • 1. 110 questions, 3 hours, 70% pass
  • 2. Ammonia = R-717; boils -28°F
  • 3. PEL 50 ppm, IDLH 300 ppm
  • 4. PSM/RMP trigger = 10,000 lb ammonia
  • 5. Ammonia is NOT miscible with oil
  • 6. High side: compressor to TXV inlet
  • 7. Flooded = liquid level control; DX = superheat
  • 8. SCBA required above IDLH concentration
  • 9. Water fog knocks down ammonia vapor
  • 10. Purger vents air; separator removes oil
  • 11. Fee 2026: $570 member / $865 nonmember
  • 12. No experience required; entry-level exam

RETA CARO Certified Assistant Refrigeration Operator

  • Practice Questions 114 questions Study Guide 31 topics Cheat Sheet 78 facts Flashcards 50 cards Shorts 1 short Blogs 1 blog Free CE Podcast

Same family resources

  • Explore More RETA Refrigeration Operator Certifications
  • Continue into nearby exams from the same family. Each card keeps practice questions, study guides, flashcards, videos, and articles in one place.

RETA CIRO Certified Industrial Refrigeration Operator

  • Practice Questions 146 questions Study Guide 68 topics Free CE

More From This Family

  • Videos and articles for deeper review.
  • Article RETA CARO Exam Guide 2026: Ammonia Safety and Operator Prep 5 min read