Cheat sheet
RETA CARO Cheat Sheet
Fundamentals & Cycle
- 30% of exam
- Refrigeration Fundamentals Vapor-Compression Cycle Ammonia Properties Saturated P-T Tables
Compressors & Lubrication
- 32% of exam
- Compressor Types Operation & Maintenance Lubrication Troubleshooting
Heat Exchangers & Purging
- 26% of exam
- Evaporators Condensers & Receivers Purging Defrost
Safety & Compliance
- 12% of exam
- Ammonia Exposure Limits PSM & RMP IIAR Standards Emergency Response
Quick Facts
- Exam RETA CARO
- Credential Asst Refrigeration Operator
- Time 3 hours
- Pass 70%
- Questions 110 multiple-choice
- Refrigerant R-717 (ammonia)
- Level Entry, no experience
- Fee 2026 $570 member, $865 nonmember
Cycle Flow Order FU
- Compress, Condense, Expand, Evaporate, repeat
- Compressor: raise pressure Condenser: reject heat Expansion valve: drop pressure Evaporator: absorb heat
High Side vs Low Side FU
High side
- Compressor discharge to TXV inlet
- Condenser, receiver, discharge line
- Higher pressure and temperature
Low side
- TXV outlet to compressor suction
- Evaporator, suction line, accumulator
- Lower pressure and temperature
- Split is at metering device
Which Component Handles This FU
- Need to absorb heat → Evaporator
- Need to reject heat → Condenser
- Need pressure/temp boost → Compressor
- Need pressure drop to low side → Expansion valve
- Store high-pressure liquid → Receiver
- Remove oil from discharge gas → Oil separator
- Remove trapped air/non-condensables → Purger
- Prevent liquid entering compressor → Accumulator
Refrigeration Fundamentals FU
- Ton 12,000 Btu/hr
- Btu Heat unit
- Sensible heat Changes temperature
- Latent heat Changes state, not temp
- Superheat Above saturation, vapor side
- Subcooling Below saturation, liquid side
Pressure-Temperature Law FU
- Higher pressure always means higher saturation temp
- Use for troubleshooting Read gauge, find temp Confirms proper charge level
Vapor-Compression Cycle FU
- Compressor Raises pressure and temp
- Condenser Rejects heat, high side
- Expansion valve Drops pressure to low side
- Evaporator Absorbs heat, low side
- Flow order Comp-Cond-Expand-Evap-Comp
Ammonia Physical Properties FU
- ASHRAE ID R-717
- Boiling point -28°F at atmospheric
- Vapor density 0.6, lighter than air
- Liquid specific gravity 0.62, lighter than water
- Ignition temp 1,204°F
- Flammable range 15-28% in air
- Odor threshold 5-50 ppm
- Refrigerant-grade purity 99.95%+ ammonia
Saturated Pressure-Temperature FU
- 28°F 0 psig, atmospheric boil
- 0°F 16 psig
- 68°F 110 psig
- 100°F 198 psig
- P-T rule Higher temp = higher pressure
Refrigerant Purity Limits CO
- Water 33 ppm max, oil 2 ppm max
- Water: freezes, cracks piping Oxygen: stress-corrosion risk Oil: fouls heat transfer Test periodically for purity
Reciprocating vs Screw Compressor CO
Reciprocating
- Pistons, positive displacement
- Best at high pressure ratios
- Unloaders step capacity
Screw
- Rotors, continuous compression
- Best at high volume flow
- Slide valve modulates capacity
- Piston strokes vs rotor mesh
Troubleshooting Symptom Picker CO
- High head pressure, clean condenser → Check for non-condensables ( Purge system )
- Low suction, frosted coil → Check TXV or charge
- Compressor short cycles rapidly → Check low-pressure control
- Knocking noise at startup → Suspect liquid slugging
- Low net oil pressure → Check oil charge, filter
- Rising pressure, condenser clean → Suspect trapped air
- Cooler warm, coil iced → Check defrost cycle
Compressor Types CO
- Reciprocating Piston, positive displacement
- Screw (rotary) Continuous, oil-flooded rotors
- Centrifugal High-volume, low-pressure-rise
- Scroll Orbiting spiral, small capacity
Oil Separator vs Purger CO
Oil separator
- Removes oil from hot gas
- Located after compressor discharge
- Returns oil to system
Purger
- Removes air/non-condensables
- Located at condenser/receiver high point
- Vents gas, saves ammonia
- Oil vs trapped air removal
Compressor Operation & Controls CO
- Compression ratio Absolute discharge / absolute suction
- Volumetric efficiency Actual / theoretical displacement
- Unloaders Reduce startup/part-load capacity
- Slide valve Screw compressor capacity control
- Liquid slugging Liquid enters cylinder, damages valves
- Short cycling Frequent start-stop, control fault
Lubrication & Oil Management CO
- Ammonia-oil miscibility Not miscible, oil settles
- Oil separator Removes oil from discharge gas
- Oil pot Low-point oil collection, draining
- Net oil pressure Discharge minus crankcase pressure
- Safe oil draining Relieve pressure, PPE, slow bleed
- Synthetic oil Better low-temp flow
Flooded vs DX Evaporator HE
Flooded
- Liquid-full coil, float control
- High efficiency, needs surge drum
- Common on large systems
DX (dry expansion)
- TXV controls superheat, not level
- Simpler, less ammonia charge
- Common on smaller systems
- Control point: level vs superheat
Evaporators & Cooling Units HE
- DX evaporator Superheat-controlled by TXV
- Flooded evaporator Liquid-full, float level control
- Frost buildup Insulates, reduces heat transfer
- Defrost Removes frost, restores capacity
- Accumulator Traps liquid before compressor
Defrost Methods HE
- Hot gas defrost Discharge gas heats coil
- Water defrost Spray water over coil
- Electric defrost Resistance heaters melt frost
- Air defrost Fans only, mild loads
Condensers & Receivers HE
- Evaporative condenser Water spray plus airflow
- Air-cooled condenser Fans only, no water
- High-pressure receiver Stores liquid after condenser
- King valve Receiver liquid outlet valve
- Relief valve Vents overpressure to atmosphere/flare
Purging Non-Condensables HE
- Non-condensables Air, trapped gas in system
- Symptom High head pressure, poor cooling
- Purger Automatically vents trapped air
- Verification Check purge log, discharge rate
Exposure Limit Ladder SA
- Odor, then PEL, STEL, IDLH rising
- Odor: 5-50 ppm warns PEL: 50 ppm 8-hr STEL: 35 ppm 15-min IDLH: 300 ppm, escape now
PSM vs RMP SA
OSHA PSM
- 29 CFR 1910.119
- Protects workers on-site
- Enforced by OSHA
EPA RMP
- 40 CFR Part 68
- Protects surrounding community
- Enforced by EPA
- Same 10,000 lb trigger, different focus
Ammonia Leak Response SA
- Detector alarm, low level → Investigate, increase ventilation ( Below PEL )
- Smell ammonia, unknown source → Don SCBA, evacuate area ( Odor threshold ~5ppm )
- Small controllable leak → Isolate valve, ventilate space
- Large uncontrolled release → Evacuate, sound alarm, call ERT
- Concentration near IDLH → SCBA only, no filter mask
- Ammonia vapor cloud, fire risk → Apply water fog, not stream
- Victim exposed, skin/eyes → Flush 15+ min, remove clothing
Ammonia Exposure Limits SA
- PEL 50 ppm, 8-hour TWA
- STEL 35 ppm, 15-minute
- IDLH 300 ppm
- Odor threshold 5-50 ppm, self-warning
PEL vs IDLH SA
PEL
- 50 ppm, 8-hour average
- Routine daily exposure limit
- Below this, normal operation
IDLH
- 300 ppm
- Immediate danger to life
- Escape without injury only
- Daily limit vs escape limit
PPE & Detection SA
- SCBA Required above IDLH
- Chemical suit Splash/vapor protection, high exposure
- Fixed detectors Continuous ammonia monitoring, alarms
- Water fog Knocks down vapor, dilutes
- Eye/face protection Goggles plus face shield
PSM & RMP Compliance SA
- Trigger quantity 10,000 lb ammonia
- PSM authority OSHA 29 CFR 1910.119
- RMP authority EPA 40 CFR 68
- PHA Process hazard analysis
- MOC Management of change
- Mechanical integrity Inspect, test, maintain equipment
IIAR & Code Standards SA
- IIAR 2 Safe system design
- IIAR 6 Inspection, testing, maintenance
- IIAR 7 Operating procedures
- IIAR 9 Minimum safety, existing systems
- ASHRAE 15 Refrigeration safety standard
Common Traps
Ammonia and Oil
- Ammonia dissolves easily in water ≠ Ammonia does not mix with oil
PSM vs RMP Focus
- PSM protects workers on-site ≠ RMP protects the surrounding community
PEL vs IDLH Meaning
- PEL is a routine daily limit ≠ IDLH means leave immediately
High Side vs Low Side
- High side runs hot and high-pressure ≠ Low side runs cold and low-pressure
Flooded vs DX Control
- Flooded evaporator controls liquid level ≠ DX evaporator controls suction superheat
Oil Separator vs Purger Job
- Oil separator returns oil, not gas ≠ Purger vents air, not oil
Compression Ratio vs Efficiency
- Ratio compares absolute pressures only ≠ Efficiency compares actual to swept volume
Last Minute
- 1. 110 questions, 3 hours, 70% pass
- 2. Ammonia = R-717; boils -28°F
- 3. PEL 50 ppm, IDLH 300 ppm
- 4. PSM/RMP trigger = 10,000 lb ammonia
- 5. Ammonia is NOT miscible with oil
- 6. High side: compressor to TXV inlet
- 7. Flooded = liquid level control; DX = superheat
- 8. SCBA required above IDLH concentration
- 9. Water fog knocks down ammonia vapor
- 10. Purger vents air; separator removes oil
- 11. Fee 2026: $570 member / $865 nonmember
- 12. No experience required; entry-level exam
RETA CARO Certified Assistant Refrigeration Operator
- Practice Questions 114 questions Study Guide 31 topics Cheat Sheet 78 facts Flashcards 50 cards Shorts 1 short Blogs 1 blog Free CE Podcast
Same family resources
- Explore More RETA Refrigeration Operator Certifications
- Continue into nearby exams from the same family. Each card keeps practice questions, study guides, flashcards, videos, and articles in one place.
RETA CIRO Certified Industrial Refrigeration Operator
- Practice Questions 146 questions Study Guide 68 topics Free CE
More From This Family
- Videos and articles for deeper review.
- Article RETA CARO Exam Guide 2026: Ammonia Safety and Operator Prep 5 min read