Cheat sheet

Tennessee LLE Electrician Cheat Sheet

Practice this exam

General Knowledge

  • 10% of exam
  • Article 100 Ohm's Law Power Calcs NEC Layout Units + Prefixes

Installation Requirements

  • 7-8% of exam
  • Listing + Labeling Working Space Workmanship OSHA 1926 Identification

Services + Feeders + Branch

  • 17-18% of exam
  • Load Calculations Article 230 Service Article 210 Branch Article 215 Feeder GFCI/AFCI

Overcurrent Protection

  • 5% of exam
  • Article 240 Breaker Sizing Fuse Sizing 240.4(D) Small Wire Next-Size-Up

Grounding + Bonding

  • 12-13% of exam
  • Article 250 GEC Sizing EGC Sizing Electrodes Bonding Jumpers

Conductors + Cables

  • 10% of exam
  • Article 310 Ampacity Insulation Types Terminal Temp Correction Factors Conductor Colors

Raceways + Boxes

  • 12-13% of exam
  • Chapter 3 Methods Conduit Fill Box Fill 314.16 Support Spacing Bend Limits

Hazardous Locations

  • 12-13% of exam
  • Article 500 Class I/II/III Divisions Seals Explosion-Proof

Low Voltage + Comms

  • 5% of exam
  • Article 725 Article 760 Alarm Article 800 Comms Power-Limited Separation Rules

Lighting + Signs + Equipment

  • 7-8% of exam
  • Article 410 Luminaires Article 600 Signs Article 422 Appliances Clearances Listed Equipment

Quick Facts

  • Exam TN LLE
  • Provider Prov
  • Questions 40 MCQ
  • Time 2 hours
  • Pass 73% (29 of 40)
  • Format Open book
  • Code NEC 2017
  • Fee $53 (Prov)
  • License scope Under $25,000
  • Retakes Unlimited, no wait

Ohm's Law Triangle GE

  • V on top; I and R below
  • V = I x R I = V/R R = V/I

Series vs Parallel GE

Series

  • One current path
  • Resistances add
  • Drops sum to source

Parallel

  • Shared voltage
  • Currents add
  • Resistance below smallest
  • One path vs many

NEC Layout GE

  • Article 90 Purpose + scope
  • Article 100 Definitions
  • Chapters 1-4 General rules
  • Chapter 5 Special occupancies
  • Chapter 6 Special equipment
  • Chapter 7 Special conditions
  • Chapter 8 Communications
  • Chapter 9 Tables + notes

NEC Chapter Map GE

  • 90 scope, 100 defs, 110 install, then chapters
  • 90: purpose 100: definitions 110: install rules Ch 3: methods

Ohm's Law + Power GE

  • V = IR Ohm's law
  • I = V/R Solve current
  • P = VI Resistive power
  • P = I2R Power from current
  • E = Pt Energy over time
  • kWh Billing energy unit
  • milli (m) x0.001

Installation + Safety IN

  • Listed Third-party approved
  • Labeled Marked by evaluator
  • Working space 3 ft typical 110.26
  • Readily accessible Reach without obstacles
  • OSHA 1926 Job-site safety
  • Disconnect marking Identify purpose
  • Guarding Protect live parts

GFCI vs AFCI SE

GFCI

  • Shock protection
  • Ground-fault current
  • Wet + damp areas

AFCI

  • Fire protection
  • Arc-fault current
  • Dwelling living areas
  • Shock vs fire

GFCI vs AFCI Picker SE

  • Kitchen countertop receptacle → GFCI required ( 210.8(A)(6) )
  • Bathroom receptacle → GFCI required ( 210.8(A)(1) )
  • Garage or outdoor receptacle → GFCI required ( 210.8(A)(2)(5) )
  • Basement or laundry area → GFCI required ( 210.8(A)(7)(10) )
  • Dwelling bedroom circuit → AFCI required ( 210.12(A) )
  • Shock and arc risk both → Use dual-function device ( Combination protection )
  • Extend circuit into covered area → AFCI still applies ( 210.12(A) extension )
  • Commercial kitchen countertop → GFCI required ( 210.8(B) )

Load Calculations SE

  • General lighting 3 VA/ft2 220.12
  • Small appliance 1500 VA each, min 2
  • Laundry circuit 1500 VA, one 20A
  • Range demand Table 220.55
  • Dryer demand 5000W or nameplate 220.54
  • Continuous load Use 125%
  • Service calc Standard or optional method

Branch Circuit vs Feeder SE

Branch circuit

  • After final OCPD
  • Supplies outlets
  • Article 210

Feeder

  • Before final OCPD
  • Supplies panels
  • Article 215
  • After vs before OCPD

Services + Feeders + Branch SE

  • Article 230 Service conductors
  • Article 215 Feeder sizing
  • Article 210 Branch circuits
  • Service disconnect Max 6 handles
  • Feeder OCPD At least calc load
  • Multiwire circuit Shared neutral
  • Receptacle spacing 12 ft rule 210.52

GFCI + AFCI Locations SE

  • GFCI Kitchen countertops
  • GFCI Bathrooms
  • GFCI Garage + outdoor
  • GFCI Basement + laundry
  • AFCI Bedrooms + living areas
  • Dual-function Shock + arc

Ampacity vs OCPD Rating OV

Ampacity

  • Conductor current limit
  • Table 310.15(B)(16)
  • Heat-based rating

OCPD rating

  • Breaker or fuse size
  • Table 240.6(A)
  • Protects the conductor
  • Wire limit vs device size

OCPD + Conductor Picker OV

  • Continuous load calculated → Apply 125% factor ( 210.19(A) )
  • Conductor size needed → Read Table 310.15(B)(16) ( Match ampacity )
  • Terminals rated 60C → Use 60C column ( Typical 100A or less )
  • Terminals rated 75C → Use 75C column ( Typical over 100A )
  • Ampacity between std sizes → Round up OCPD ( 240.4(B) )
  • 14/12/10 AWG copper → Cap at 15/20/30A ( 240.4(D) overrides )
  • Motor branch circuit → Apply Table 430.52 ( Not general OCPD rule )
  • Over 3 current-carrying conductors → Apply adjustment factor ( 310.15(C)(1) )

Overcurrent Protection OV

  • Article 240 Overcurrent devices
  • Standard sizes 240.6(A) list
  • Next-size-up 240.4(B) rounding
  • Small conductor rule 240.4(D) caps size
  • Motor OCPD Table 430.52 multiplier
  • Tap rule 240.21 exceptions

Grounding vs Bonding GR

Grounding

  • Connects to earth
  • Stabilizes voltage
  • GEC route

Bonding

  • Joins metal parts
  • Creates fault path
  • EGC route
  • Earth vs continuity

Grounding Electrode Picker GR

  • Metal water pipe 10ft+ → Use as electrode ( 250.52(A)(1) )
  • Concrete-encased rebar present → Use ufer ground ( 250.52(A)(3) )
  • Ground ring 20ft or more → Use as electrode ( 250.52(A)(4) )
  • Single rod exceeds 25 ohms → Add second rod ( 250.53(A)(2) )
  • Multiple electrodes present → Bond into one system ( 250.50 )
  • No qualifying electrode present → Install made electrode ( Rod, plate, or ring )

Grounding + Bonding GR

  • GEC sizing Table 250.66
  • EGC sizing Table 250.122
  • Water pipe electrode 10 ft in earth 250.52(A)(1)
  • Concrete-encased electrode Ufer ground 250.52(A)(3)
  • Ground rod 8 ft minimum
  • Rod resistance 25 ohm or add rod 250.53(A)(2)
  • Bonding jumper Table 250.102(C)(1)
  • Main bonding jumper Neutral-to-ground bond

Wire Color Code CO

  • White/gray grounded; green/bare ground; black hot
  • White/gray: neutral Green/bare: EGC Black/red: ungrounded

THHN vs THWN CO

THHN

  • Dry locations only
  • 90C rated
  • Thermoplastic + nylon

THWN

  • Wet locations rated
  • 75C typical
  • Moisture-resistant nylon
  • Dry vs wet rating

Conductors + Ampacity CO

  • Ampacity table 310.15(B)(16)
  • 60C terminals Typical 100A or less
  • 75C terminals Typical over 100A
  • THHN Dry, 90C rated
  • THWN Wet-rated
  • Adjustment factor Over 3 current-carrying wires
  • White/gray Grounded conductor
  • Green/bare Equipment grounding conductor

Conduit Fill Steps RA

  • 1 wire 53%; 2 wires 31%; 3+ 40%
  • 1 conductor: 53% 2 conductors: 31% 3+ conductors: 40%

Raceway + Conduit Fill RA

  • 1 conductor 53% fill
  • 2 conductors 31% fill
  • 3+ conductors 40% fill
  • EMT Thin-wall metal raceway
  • PVC Nonmetallic raceway
  • Burial depth Table 300.5

Box Fill Rules RA

  • Box fill Table 314.16(B)
  • Device yoke Counts as 2
  • Internal clamp Counts as 1
  • EGCs Counted as 1 total
  • Fixture stud/hickey Counts as 1

Hazard Class Order HA

  • I gas, II dust, III fibers
  • Class I: gas/vapor Class II: dust Class III: fibers/flyings

Hazardous Location Classes HA

  • Class I Flammable gas/vapor
  • Class II Combustible dust
  • Class III Ignitable fibers/flyings
  • Division 1 Normal hazard presence
  • Division 2 Abnormal/accidental presence
  • Seal fitting Stops gas migration
  • Explosion-proof Contains internal ignition

Low Voltage + Comms LO

  • Article 725 Class 1/2/3 circuits
  • Power-limited Reduced fire/shock risk
  • Article 760 Fire alarm circuits
  • Article 800 Communications systems
  • Separation rule Power vs low-voltage

Lighting + Signs + Equipment LI

  • Article 410 Luminaires
  • Storage clearance 410.16 minimum
  • Article 600 Electric signs
  • Sign disconnect 600.6 required
  • Article 422 Fixed appliances
  • Listed equipment Follow install instructions

Common Traps

Ampacity vs OCPD

  • Ampacity rates the wire ≠ OCPD sizes the device

Grounding vs Bonding

  • Grounding connects to earth ≠ Bonding joins metal parts

Continuous vs Noncontinuous Load

  • Continuous runs 3+ hours ≠ Noncontinuous needs no 125%

Service vs Feeder

  • Service comes from utility ≠ Feeder follows service equipment

Class I vs Class II

  • Class I is gas/vapor ≠ Class II is dust

GFCI vs AFCI

  • GFCI stops shock ≠ AFCI stops arcing fires

Box Fill vs Conduit Fill

  • Box fill counts volume ≠ Conduit fill uses percent area

Last Minute

  • 1. 40 questions; 2-hour time limit
  • 2. 73% passing score (29 of 40)
  • 3. NEC 2017 controls all answers
  • 4. Open book: NEC + Ugly's + OSHA
  • 5. LLE license caps at $25,000
  • 6. Unlimited retakes, no waiting period
  • 7. GFCI = shock; AFCI = arc
  • 8. Continuous loads always get 125%
  • 9. Table 310.15(B)(16) sets ampacity
  • 10. Table 250.122 sizes grounding conductors
  • 11. Table 250.66 sizes grounding electrode conductor
  • 12. Conduit fill: 53/31/40 percent
  • 13. Motor OCPD uses Table 430.52
  • 14. Confirm current NEC edition first

Tennessee Limited Licensed Electrician (LLE)