Cheat sheet
Tennessee LLE Electrician Cheat Sheet
General Knowledge
- 10% of exam
- Article 100 Ohm's Law Power Calcs NEC Layout Units + Prefixes
Installation Requirements
- 7-8% of exam
- Listing + Labeling Working Space Workmanship OSHA 1926 Identification
Services + Feeders + Branch
- 17-18% of exam
- Load Calculations Article 230 Service Article 210 Branch Article 215 Feeder GFCI/AFCI
Overcurrent Protection
- 5% of exam
- Article 240 Breaker Sizing Fuse Sizing 240.4(D) Small Wire Next-Size-Up
Grounding + Bonding
- 12-13% of exam
- Article 250 GEC Sizing EGC Sizing Electrodes Bonding Jumpers
Conductors + Cables
- 10% of exam
- Article 310 Ampacity Insulation Types Terminal Temp Correction Factors Conductor Colors
Raceways + Boxes
- 12-13% of exam
- Chapter 3 Methods Conduit Fill Box Fill 314.16 Support Spacing Bend Limits
Hazardous Locations
- 12-13% of exam
- Article 500 Class I/II/III Divisions Seals Explosion-Proof
Low Voltage + Comms
- 5% of exam
- Article 725 Article 760 Alarm Article 800 Comms Power-Limited Separation Rules
Lighting + Signs + Equipment
- 7-8% of exam
- Article 410 Luminaires Article 600 Signs Article 422 Appliances Clearances Listed Equipment
Quick Facts
- Exam TN LLE
- Provider Prov
- Questions 40 MCQ
- Time 2 hours
- Pass 73% (29 of 40)
- Format Open book
- Code NEC 2017
- Fee $53 (Prov)
- License scope Under $25,000
- Retakes Unlimited, no wait
Ohm's Law Triangle GE
- V on top; I and R below
- V = I x R I = V/R R = V/I
Series vs Parallel GE
Series
- One current path
- Resistances add
- Drops sum to source
Parallel
- Shared voltage
- Currents add
- Resistance below smallest
- One path vs many
NEC Layout GE
- Article 90 Purpose + scope
- Article 100 Definitions
- Chapters 1-4 General rules
- Chapter 5 Special occupancies
- Chapter 6 Special equipment
- Chapter 7 Special conditions
- Chapter 8 Communications
- Chapter 9 Tables + notes
NEC Chapter Map GE
- 90 scope, 100 defs, 110 install, then chapters
- 90: purpose 100: definitions 110: install rules Ch 3: methods
Ohm's Law + Power GE
- V = IR Ohm's law
- I = V/R Solve current
- P = VI Resistive power
- P = I2R Power from current
- E = Pt Energy over time
- kWh Billing energy unit
- milli (m) x0.001
Installation + Safety IN
- Listed Third-party approved
- Labeled Marked by evaluator
- Working space 3 ft typical 110.26
- Readily accessible Reach without obstacles
- OSHA 1926 Job-site safety
- Disconnect marking Identify purpose
- Guarding Protect live parts
GFCI vs AFCI SE
GFCI
- Shock protection
- Ground-fault current
- Wet + damp areas
AFCI
- Fire protection
- Arc-fault current
- Dwelling living areas
- Shock vs fire
GFCI vs AFCI Picker SE
- Kitchen countertop receptacle → GFCI required ( 210.8(A)(6) )
- Bathroom receptacle → GFCI required ( 210.8(A)(1) )
- Garage or outdoor receptacle → GFCI required ( 210.8(A)(2)(5) )
- Basement or laundry area → GFCI required ( 210.8(A)(7)(10) )
- Dwelling bedroom circuit → AFCI required ( 210.12(A) )
- Shock and arc risk both → Use dual-function device ( Combination protection )
- Extend circuit into covered area → AFCI still applies ( 210.12(A) extension )
- Commercial kitchen countertop → GFCI required ( 210.8(B) )
Load Calculations SE
- General lighting 3 VA/ft2 220.12
- Small appliance 1500 VA each, min 2
- Laundry circuit 1500 VA, one 20A
- Range demand Table 220.55
- Dryer demand 5000W or nameplate 220.54
- Continuous load Use 125%
- Service calc Standard or optional method
Branch Circuit vs Feeder SE
Branch circuit
- After final OCPD
- Supplies outlets
- Article 210
Feeder
- Before final OCPD
- Supplies panels
- Article 215
- After vs before OCPD
Services + Feeders + Branch SE
- Article 230 Service conductors
- Article 215 Feeder sizing
- Article 210 Branch circuits
- Service disconnect Max 6 handles
- Feeder OCPD At least calc load
- Multiwire circuit Shared neutral
- Receptacle spacing 12 ft rule 210.52
GFCI + AFCI Locations SE
- GFCI Kitchen countertops
- GFCI Bathrooms
- GFCI Garage + outdoor
- GFCI Basement + laundry
- AFCI Bedrooms + living areas
- Dual-function Shock + arc
Ampacity vs OCPD Rating OV
Ampacity
- Conductor current limit
- Table 310.15(B)(16)
- Heat-based rating
OCPD rating
- Breaker or fuse size
- Table 240.6(A)
- Protects the conductor
- Wire limit vs device size
OCPD + Conductor Picker OV
- Continuous load calculated → Apply 125% factor ( 210.19(A) )
- Conductor size needed → Read Table 310.15(B)(16) ( Match ampacity )
- Terminals rated 60C → Use 60C column ( Typical 100A or less )
- Terminals rated 75C → Use 75C column ( Typical over 100A )
- Ampacity between std sizes → Round up OCPD ( 240.4(B) )
- 14/12/10 AWG copper → Cap at 15/20/30A ( 240.4(D) overrides )
- Motor branch circuit → Apply Table 430.52 ( Not general OCPD rule )
- Over 3 current-carrying conductors → Apply adjustment factor ( 310.15(C)(1) )
Overcurrent Protection OV
- Article 240 Overcurrent devices
- Standard sizes 240.6(A) list
- Next-size-up 240.4(B) rounding
- Small conductor rule 240.4(D) caps size
- Motor OCPD Table 430.52 multiplier
- Tap rule 240.21 exceptions
Grounding vs Bonding GR
Grounding
- Connects to earth
- Stabilizes voltage
- GEC route
Bonding
- Joins metal parts
- Creates fault path
- EGC route
- Earth vs continuity
Grounding Electrode Picker GR
- Metal water pipe 10ft+ → Use as electrode ( 250.52(A)(1) )
- Concrete-encased rebar present → Use ufer ground ( 250.52(A)(3) )
- Ground ring 20ft or more → Use as electrode ( 250.52(A)(4) )
- Single rod exceeds 25 ohms → Add second rod ( 250.53(A)(2) )
- Multiple electrodes present → Bond into one system ( 250.50 )
- No qualifying electrode present → Install made electrode ( Rod, plate, or ring )
Grounding + Bonding GR
- GEC sizing Table 250.66
- EGC sizing Table 250.122
- Water pipe electrode 10 ft in earth 250.52(A)(1)
- Concrete-encased electrode Ufer ground 250.52(A)(3)
- Ground rod 8 ft minimum
- Rod resistance 25 ohm or add rod 250.53(A)(2)
- Bonding jumper Table 250.102(C)(1)
- Main bonding jumper Neutral-to-ground bond
Wire Color Code CO
- White/gray grounded; green/bare ground; black hot
- White/gray: neutral Green/bare: EGC Black/red: ungrounded
THHN vs THWN CO
THHN
- Dry locations only
- 90C rated
- Thermoplastic + nylon
THWN
- Wet locations rated
- 75C typical
- Moisture-resistant nylon
- Dry vs wet rating
Conductors + Ampacity CO
- Ampacity table 310.15(B)(16)
- 60C terminals Typical 100A or less
- 75C terminals Typical over 100A
- THHN Dry, 90C rated
- THWN Wet-rated
- Adjustment factor Over 3 current-carrying wires
- White/gray Grounded conductor
- Green/bare Equipment grounding conductor
Conduit Fill Steps RA
- 1 wire 53%; 2 wires 31%; 3+ 40%
- 1 conductor: 53% 2 conductors: 31% 3+ conductors: 40%
Raceway + Conduit Fill RA
- 1 conductor 53% fill
- 2 conductors 31% fill
- 3+ conductors 40% fill
- EMT Thin-wall metal raceway
- PVC Nonmetallic raceway
- Burial depth Table 300.5
Box Fill Rules RA
- Box fill Table 314.16(B)
- Device yoke Counts as 2
- Internal clamp Counts as 1
- EGCs Counted as 1 total
- Fixture stud/hickey Counts as 1
Hazard Class Order HA
- I gas, II dust, III fibers
- Class I: gas/vapor Class II: dust Class III: fibers/flyings
Hazardous Location Classes HA
- Class I Flammable gas/vapor
- Class II Combustible dust
- Class III Ignitable fibers/flyings
- Division 1 Normal hazard presence
- Division 2 Abnormal/accidental presence
- Seal fitting Stops gas migration
- Explosion-proof Contains internal ignition
Low Voltage + Comms LO
- Article 725 Class 1/2/3 circuits
- Power-limited Reduced fire/shock risk
- Article 760 Fire alarm circuits
- Article 800 Communications systems
- Separation rule Power vs low-voltage
Lighting + Signs + Equipment LI
- Article 410 Luminaires
- Storage clearance 410.16 minimum
- Article 600 Electric signs
- Sign disconnect 600.6 required
- Article 422 Fixed appliances
- Listed equipment Follow install instructions
Common Traps
Ampacity vs OCPD
- Ampacity rates the wire ≠ OCPD sizes the device
Grounding vs Bonding
- Grounding connects to earth ≠ Bonding joins metal parts
Continuous vs Noncontinuous Load
- Continuous runs 3+ hours ≠ Noncontinuous needs no 125%
Service vs Feeder
- Service comes from utility ≠ Feeder follows service equipment
Class I vs Class II
- Class I is gas/vapor ≠ Class II is dust
GFCI vs AFCI
- GFCI stops shock ≠ AFCI stops arcing fires
Box Fill vs Conduit Fill
- Box fill counts volume ≠ Conduit fill uses percent area
Last Minute
- 1. 40 questions; 2-hour time limit
- 2. 73% passing score (29 of 40)
- 3. NEC 2017 controls all answers
- 4. Open book: NEC + Ugly's + OSHA
- 5. LLE license caps at $25,000
- 6. Unlimited retakes, no waiting period
- 7. GFCI = shock; AFCI = arc
- 8. Continuous loads always get 125%
- 9. Table 310.15(B)(16) sets ampacity
- 10. Table 250.122 sizes grounding conductors
- 11. Table 250.66 sizes grounding electrode conductor
- 12. Conduit fill: 53/31/40 percent
- 13. Motor OCPD uses Table 430.52
- 14. Confirm current NEC edition first
Tennessee Limited Licensed Electrician (LLE)
- Practice Questions 100 questions Study Guide 40 topics Cheat Sheet 93 facts Flashcards 50 cards Shorts 1 short Videos 1 video Blogs 1 blog Free CE Podcast