Cheat sheet
City & Guilds 2079-11 F-Gas Category I Cheat Sheet
Refrigeration Cycle & p-h Diagrams
- 32% of exam
- Compressor+condenser Expansion+evaporator Superheat vs sub-cool p-h diagram basics Leak-indicator components
Refrigerants, F-Gas & ODS Regs
- 20% of exam
- EU 517/2014 retained law CO2e = mass x GWP 2020 HFC service ban HFC phase-down quota 5-year record keeping
System Components
- 20% of exam
- TEV/TXV + filter drier Manifold gauges red/blue Liquid receiver + sight glass Zeotropic vs azeotropic blends Deep vacuum ~500 microns
Leak Detection & Repair
- 5% of exam
- Direct vs indirect methods 5g/year detector sensitivity 12/6/3-month check bands Fixed detector doubles interval 1-month follow-up check
Recovery, Recycling & Reclamation
- 5% of exam
- 80% cylinder fill limit Recycling vs reclamation AHRI 700 standard No venting, ever Separate cylinders per gas
Environmental Impact (GWP/ODP)
- 5% of exam
- GWP: CO2=1 reference ODP: R-11=1 reference HFC high GWP, zero ODP Montreal 1987 ozone treaty Kigali 2016 HFC phase-down
Safety & Legislation
- 13% of exam
- HASAWA 1974 general duty COSHH hazardous substances OFN for purge + testing Cardiac sensitisation risk Cold burns + asphyxiation
Quick Facts
- Exam C&G 2079-11
- Category Category I (any size)
- Questions 40 MCQ
- Time 80 minutes
- Pass 60% (24/40)
- Practical Separate pass required
- Regulation EU 517/2014 (GB retained)
- Blueprint May 2025 (v2.5)
Cycle Order RE
- Compressor, condenser, expansion device, evaporator, repeat
- Compressor: raises pressure Condenser: rejects heat Expansion: drops pressure Evaporator: absorbs heat
Superheat vs Sub-cooling RE
Superheat
- Vapour above saturation temp
- Protects compressor suction
Sub-cooling
- Liquid below saturation temp
- Prevents flash gas
- Vapour side vs liquid side
Cycle Components RE
- Compressor Raises P and T
- Condenser Rejects heat, condenses
- Expansion device Throttles, isenthalpic
- Evaporator Absorbs heat, boils
- Superheat Vapour above saturation temp
- Sub-cooling Liquid below saturation temp
- Flash gas Forms before expansion device
p-h Diagram Basics RE
- Saturation dome Liquid and vapour coexist
- Left of dome Sub-cooled liquid region
- Right of dome Superheated vapour region
- Throttling line Vertical, constant enthalpy
- Evaporation line Horizontal, low pressure
- Condensation line Horizontal, high pressure
- Compression line Pressure, temperature both rise
Leak-Indication Components RE
- Service valves Check points for leaks
- Pressure relief valve Releases excess system pressure
- Thermostats Control temp, flag faults
- Sight glass bubbling Signals flash gas
- Defrost controls Manage evaporator ice buildup
- Overloads Protect compressor motor windings
- Oil separator Returns oil, flags faults
- High-pressure receiver Stores liquid, monitors charge
- Low-pressure accumulator Prevents liquid floodback
CO2e Formula FG
- CO2e = tonnes charge x GWP value
- Mass in tonnes x GWP number = CO2 equivalent
517/2014 vs 842/2006 FG
517/2014 (current)
- Retained EU law today
- GB via SI 2015/310
842/2006 (superseded)
- Predecessor regulation
- Replaced in EU by 517/2014
- Old rule replaced by new
Regulation & CO2e Triggers FG
- Servicing with virgin HFC → Check GWP under 2500 ( Below 40t CO2e ban )
- Any deliberate release → Always illegal, recover instead ( No exceptions )
- Repair just completed → Follow-up check required ( Within 1 month )
- Calculating CO2e → Multiply mass by GWP ( Tonnes x GWP factor )
- Choosing low-GWP refrigerant → Check HFC phase-down quota ( Falling toward 2030 )
F-Gas Legal Framework FG
- EU 517/2014 Retained EU law, GB
- SI 2015/310 GB domestic implementation
- Fluorinated GHG Regs 2015 Domestic UK statute
- Deliberate venting Always illegal, any size
- Category I Legally any charge size
- Operator duty Arrange checks and records
Category I vs Category II-IV FG
Category I
- Any charge size
- Full scope: all activities
Category II-IV
- Limited charge or scope
- Narrower legal permissions
- Broadest tier vs narrower tiers
CO2e & Service Rules FG
- CO2e formula Mass(t) x GWP
- 2020 HFC ban Virgin gas GWP 2500 plus
- Ban threshold 40t CO2e charge size
- Recycled/reclaimed HFC Still permitted after 2020
- Phase-down target About one-fifth by 2030
- Records kept At least 5 years
- Record contents Type, quantity, dates, technician
Refrigerant Charging Method Picker SY
- Zeotropic blend (e.g. R-404A) → Charge as liquid ( Prevents fractionation )
- Azeotropic blend (e.g. R-507A) → Charge as liquid ( Behaves like pure fluid )
- Sight glass bubbling → Check for undercharge ( Or restriction )
- System evacuation needed → Pull deep vacuum ( About 500 microns )
- Charging any refrigerant → Weigh on scales ( Charge by mass )
Core Hardware SY
- TEV/TXV Modulates flow, targets superheat
- Filter drier Removes moisture, acid, debris
- Liquid receiver Stores surplus liquid charge
- Manifold gauges Red high side, blue low
- Vacuum pump Removes air and moisture
- Vacuum level About 500 microns deep
- Weighing scales Charge measured by mass
- Zeotropic blend Charge as liquid only
- Azeotropic blend Behaves like single substance
Leak Band Numbers LE
- 5, 50, 500 tonnes set check frequency
- 5t = 12-monthly 50t = 6-monthly 500t = 3-monthly + detector
Direct vs Indirect Leak Detection LE
Direct methods
- Find the gas
- Sniffer, UV dye, bubbles
Indirect methods
- Infer from parameters
- Pressure and temperature checks
- Gas found vs signs read
Leak-Check Interval Picker LE
- Charge 5 to <50t → Check every 12 months ( No fixed detector )
- Charge 50 to <500t → Check every 6 months ( No fixed detector )
- Charge 500t or more → Check every 3 months ( Fixed detector mandatory )
- Fixed detector fitted → Double the interval ( Below 500t only )
- Hermetic, labelled, under 10t → No routine check needed ( Exemption only )
Detection Methods LE
- Electronic sniffer Direct detection method
- UV dye and lamp Direct detection method
- Bubble/soap solution Direct detection method
- Indirect method Infers from operating parameters
- Halide torch Unsuitable for modern HFCs
- Detector sensitivity 5 grams per year
- Detector calibration Checked every 12 months
Fixed Detector Present vs Absent LE
Fixed detector present
- Doubles check interval
- Mandatory above 500t
No fixed detector
- Standard interval applies
- 5t, 50t, 500t bands
- Detector halves inspection frequency
Leak-Check Frequencies LE
- 5 to under 50t 12-monthly checks required
- 50 to under 500t 6-monthly checks required
- 500t or more 3-monthly plus fixed detector
- Fixed detector fitted Doubles the check interval
- 5t band with detector Becomes 24-monthly checks
- 50t band with detector Becomes 12-monthly checks
- Hermetic exemption Below 10t, labelled only
- Follow-up check Within 1 month of repair
Recycling vs Reclamation RE
Recycling
- Basic filter and dry
- Reused on-site often
Reclamation
- Distilled to AHRI 700
- Resold as new
- Site clean-up vs full reprocessing
Recovery Cylinder Decision RE
- Filling recovery cylinder → Stop at 80% full ( Leaves ullage space )
- Refrigerant lightly contaminated → Recycle on site ( Filter and dry )
- Refrigerant needs resale → Send for reclamation ( Must meet AHRI 700 )
- Different refrigerant types → Use separate cylinders ( Avoid cross-contamination )
- Refrigerant too contaminated → Send for destruction ( Licensed facility only )
Recovery Rules RE
- Recovery Capture gas before disposal
- Cylinder fill limit Max 80% liquid fill
- Ullage space About 20% for expansion
- Recycling Basic filter and dry
- Reclamation Distilled, tested to AHRI 700
- Cross-contamination Blocks recycling and reclaiming
- Unusable refrigerant Sent for licensed destruction
- Separate cylinders One refrigerant type each
GWP Memory Anchors EN
- CO2 is 1, ammonia is 0
- CO2 (R-744): GWP 1 Ammonia (R-717): GWP 0 R-1234yf: GWP under 1
CFC/HCFC vs HFC/HFO EN
CFC/HCFC
- Contains chlorine
- ODP greater than zero
HFC/HFO
- No chlorine content
- ODP equals zero
- Chlorine present vs chlorine absent
GWP & ODP Values EN
- GWP reference gas CO2 equals 1
- R-410A GWP Approximately 2088
- R-32 GWP Approximately 675
- R-134a GWP Approximately 1430
- R-404A GWP Approximately 3922
- R-1234yf GWP Less than 1
- Ammonia R-717 GWP Zero
- ODP reference gas R-11 equals 1
- CFC and HCFC ODP Greater than zero
- HFC and HFO ODP Equals zero
Protocols & Treaties EN
- Montreal Protocol Signed 1987, ozone treaty
- Kigali Amendment Added 2016, HFC phase-down
- Kyoto Protocol Climate change treaty basis
- TEWI Total equivalent warming impact
Safety Hazards SA
- Cold burns Liquid refrigerant skin contact
- Asphyxiation Displaces oxygen when leaking
- Thermal decomposition Refrigerant meets open flame
- CNS effect Central nervous system depression
- Cardiac sensitisation Heart arrhythmia risk, adrenaline
- Flame brazing hazard Fire and fume risk
- Nitrogen pressure testing Over-pressure and burst risk
Safety Rules & Equipment SA
- HASAWA 1974 General workplace safety duty
- COSHH Controls hazardous substance exposure
- OFN Oxygen-free nitrogen for purging
- Never use Oxygen or compressed air
- PPE required Gloves and eye protection
- Safe isolation Before opening any circuit
Common Traps
GWP vs ODP Confusion
- GWP = warming, not ozone ≠ ODP = ozone, not warming
Superheat vs Sub-cooling Swap
- Superheat = vapour side always ≠ Sub-cooling = liquid side always
5t Threshold Misread
- 5t is CO2e, not kg ≠ Hermetic exempt only under 10t
Fixed Detector Confusion
- Doubles interval below 500t ≠ Mandatory (not optional) at 500t
Recycling vs Reclamation Mixup
- Recycling stays on-site basic ≠ Reclamation meets AHRI 700 spec
Venting Never Legal
- No charge size exemption exists ≠ Always recover, never release
842/2006 vs 517/2014
- 842/2006 is superseded now ≠ 517/2014 is current GB law
Last Minute
- 1. 40 MCQ, 80 minutes, 60% pass
- 2. Pass mark is 24 of 40
- 3. Category I covers any charge size
- 4. CO2e equals tonnes charge times GWP
- 5. Leak bands: 5t, 50t, 500t
- 6. Fixed detector doubles check interval
- 7. Detector must sense 5 g/year
- 8. Follow-up check due within 1 month
- 9. Never vent; always recover refrigerant
- 10. Recovery cylinders fill to 80% max
- 11. Virgin HFCs GWP 2500+ banned 2020
- 12. Keep F-Gas records for 5 years
City & Guilds 2079 Level 2 Award in F-Gas & ODS Regulations (Category I)
- Practice Questions 112 questions Study Guide 21 topics Cheat Sheet 95 facts Flashcards 50 cards Blogs 1 blog Podcast
Same family resources
- Explore More City & Guilds UK Trade Qualifications
- Continue into nearby exams from the same family. Each card keeps practice questions, study guides, flashcards, videos, and articles in one place.
City & Guilds 2391-51 Periodic Inspection & Testing of Electrical Installations
- Cheat Sheet 152 facts Practice Questions 233 questions Study Guide 27 topics Flashcards 50 cards
City & Guilds 2391-52 Combined Inspection & Testing of Electrical Installations
- Practice Questions 167 questions Study Guide 37 topics
City & Guilds 2922 Level 3 Award in Solar PV Systems Installation & Maintenance
- Practice Questions 125 questions Study Guide 46 topics
City & Guilds 2365 Level 2 Diploma in Electrical Installations
- Practice Questions 100 questions Study Guide 59 topics Shorts 2 short s
City & Guilds 2365 Level 3 Diploma in Electrical Installations
- Practice Questions 100 questions Shorts 1 short
City & Guilds 2382-22 18th Edition Wiring Regulations (BS 7671)
- Practice Questions 100 questions
More From This Family
- Videos and articles for deeper review.
- Article Is City & Guilds 2079-11 Still Valid in 2026? 12 min read