Cheat sheet
City & Guilds 2391-51 Cheat Sheet
Periodic Requirements
- 13% of exam
- Qualification Map Source Hierarchy Scope Planning Assessment Materials EICR Documents
Safety Management
- 5% of exam
- Safe Isolation Instrument Control GS38 Leads Risk Assessment Live Testing
Periodic Inspection
- 17% of exam
- Inspection Evidence EICR Codes Extent Limitations Sampling
Periodic Testing
- 65% of exam
- Continuity Polarity Insulation Resistance Earthing Loop Fault RCD Functional Phase Test Selection Results Interpretation
Quick Facts
- Qualification City & Guilds 2391-51
- Award Level 3 Award
- Scope Existing electrical installations
- Mandatory unit 2391-501
- Online test 2391-051
- Online items 40 multiple-choice questions
- Online time 90 minutes
- Online condition Open book; invigilated
- Online pass Approximately 75%
- Pass adjustment Reliability adjusted
- Visual task 30 minutes
- Practical task 150 minutes
- Short-answer task 60 minutes
- Guided learning 41 hours
- Total time 55 hours
- Entry profile Experienced electrotechnical candidates
- BS 7671 edition Check live assessment materials
Report Pack RE
- Report, inspections, circuits, results, recipient guidance.
- EICR Inspection schedule Circuit schedule Test results Recipient guidance
2391-51 vs 2391-50 RE
2391-51
- Existing installations
- Periodic condition reporting
- EICR focus
2391-50
- New or altered work
- Initial verification
- EIC focus
- Match award to installation stage
Assessment Reference Picker RE
- Taking online test → Paper references only
- Taking visual Task A → No references
- Performing practical Task B → No reference materials ( During testing )
- Confirming Task B results → Permitted references ( After testing )
- Taking short-answer Task C → Permitted paper references
- Using calculations → Non-programmable calculator
- Selecting publication edition → Follow assessment instructions
- Adding navigation aids → Use compliant page tabs
Qualification Map RE
- 2391-51 Periodic inspection award Exact scope
- 2391-501 Mandatory unit Pass required
- 2391-051 Online multiple-choice test Pass required
- Assessment Online test plus assignment
- Qualification level Level 3
- GLH 41 guided hours
- TQT 55 total hours
- Candidate profile Experienced electrical practitioner
- Newcomers Qualification not suitable
Assignment Tasks RE
- Visual thirty; practical one-fifty; written sixty.
- Task A visual Task B practical Task C short-answer
2391-51 vs 2391-52 RE
2391-51
- Periodic pathway only
- Existing installations
2391-52
- Combined pathway
- Initial plus periodic
- Do not borrow combined content
Online Blueprint RE
- Requirements 5 questions 13%
- Safety management 2 questions 5%
- Periodic inspection 7 questions 17%
- Periodic testing 26 questions 65%
- Online total 40 questions
- Online duration 90 minutes
- Online format Multiple-choice
- Online result Pass or fail
- Indicative pass Approximately 75%
Extent vs Limitation RE
Extent
- Planned coverage
- Agreed before work
Limitation
- Restricts planned coverage
- Reason must be recorded
- Do not disguise reduced scope
Source Hierarchy RE
- EAWR Workplace electrical safety law
- Health-safety law Statutory duties
- BS 7671 National wiring standard
- Guidance Note 3 Inspection-testing guidance
- GS38 Electrical test equipment guidance
- Existing records Planning evidence
- Previous certificates Installation history
- Manufacturer data Equipment-specific criteria
Scope Planning RE
- Purpose Continued-service safety assessment
- Extent Agreed inspection coverage
- Limitation Recorded excluded access
- Sampling Representative inspection selection
- Defects found Expand sampling appropriately
- Operational constraints Plan disruption controls
- Records review Identify installation history
- Client agreement Confirm extent beforehand
- Inspector duty Record accurate findings
EICR Documents RE
- EICR Condition assessment report
- Inspection schedule Inspected-item record
- Circuit details Circuit identification schedule
- Test results Measured-values schedule
- Recipient guidance Report-use instructions
- Extent entry Coverage clearly stated
- Limitations entry Restrictions clearly justified
- Next inspection Recommended interval recorded
Assessment Materials RE
- Online test Paper references permitted
- Online references BS7671 OSG GN3
- Electronic references Not permitted online
- Visual Task A No references
- Practical Task B Confirm results only
- Short-answer Task C Paper references permitted
- Calculator Non-programmable scientific permitted
- Personal notes Not permitted
- Highlighting Permitted
- Page tabs Paper markers permitted
- Short cross-references Permitted
- A4:2026 Published current amendment
- A3:2024 Valid through 15 October 2026
- Installation transition Either edition through 15 Oct 2026
- Assessment edition Follow live City & Guilds materials
Isolation Sequence SA
- Identify, inform, isolate, secure, prove, test, reprove.
- Identify source Inform users Secure isolation Prove-test-reprove
Dead vs Live Tests SA
Dead tests
- Supply securely isolated
- Continuity and insulation
- Prove dead first
Live tests
- Supply energised
- Loop and prospective current
- Additional controls required
- Never energise dead-test instruments
Safe Isolation Path SA
- Work area confirmed → Identify every source
- Affected users identified → Inform before isolation
- Correct circuit confirmed → Operate isolation device
- Circuit isolated → Lock against reconnection
- Warning needed → Attach caution notice
- Tester selected → Prove on known source
- Tester proven → Confirm conductors dead
- Dead confirmed → Reprove voltage indicator
- Alternative source possible → Repeat source controls
Safe Isolation SA
- Identify Correct supply and circuit
- Inform Notify affected persons
- Isolate Disconnect every relevant source
- Secure Prevent reconnection
- Prove tester Verify before testing
- Test conductors Confirm dead safely
- Reprove tester Verify after testing
- Stored energy Discharge and control
- Alternative supplies Identify every source
Calibration vs Before-Use Check SA
Calibration
- Periodic accuracy assurance
- Traceable maintenance record
Before-use check
- Immediate condition check
- Required each use
- One never replaces the other
Instrument Control SA
- Correct function Match intended measurement
- Measurement category Match electrical environment
- Voltage rating Suit expected system voltage
- GS38 leads Protected probes and leads
- Before-use check Inspect instrument condition
- Calibration Maintain verified accuracy
- Known source Prove voltage indicator
- Instrument identifier Record traceable details
- Live measurement Apply additional controls
Code Order IN
- Danger, potential, improve, investigate—code actual risk.
- C1 = danger C2 = potential C3 = improve FI = investigate
EICR vs EIC IN
EICR
- Reports current condition
- Uses classification codes
- Periodic inspection output
EIC
- Certifies installation work
- Initial verification output
- No condition codes
- 2391-51 centres on EICR
Observation Code Picker IN
- Danger exists now → C1 ( Immediate action )
- Potential danger exists → C2 ( Urgent remediation )
- Safety improvement advised → C3 ( Recommendation )
- Danger possibly concealed → FI ( Investigate promptly )
- Only C3 observations → Satisfactory ( No C1 C2 FI )
- Any C1 found → Unsatisfactory ( Danger present )
- Any C2 found → Unsatisfactory ( Potential danger )
- Any FI found → Unsatisfactory ( Risk unresolved )
Inspection Evidence IN
- Visual inspection Observe accessible condition
- Touch Check looseness or heat safely
- Hearing Detect abnormal operation
- Smell Detect overheating evidence
- IP suitability Match environmental exposure
- Damage Assess safety significance
- Deterioration Assess continued service
- Alterations Check safety impact
- Accessibility Record genuine restrictions
- Inspection first Inform test selection
C1 vs C2 IN
C1
- Danger present
- Immediate action required
C2
- Potentially dangerous
- Urgent remedial action
- Distinguish present from potential
Sampling and Limitation Picker IN
- Scope is negotiable → Agree extent first
- Sampling is proposed → Choose representative sample
- Defect appears → Increase sample appropriately
- Access is impossible → Record genuine limitation
- Shutdown is restricted → Record operational limitation
- Test risks damage → Adapt test method
- Test must be omitted → Document exact reason
- Evidence remains insufficient → Consider FI coding
EICR Codes IN
- C1 Danger present Immediate action
- C2 Potentially dangerous Urgent action
- C3 Improvement recommended Advisory
- FI Further investigation required Without delay
- Unsatisfactory Any C1 C2 FI
- C3 only May remain satisfactory
- Code basis Actual safety risk
- Observation State defect precisely
- Recommendation Match identified risk
C3 vs FI IN
C3
- Improvement recommended
- Risk already assessable
- Can remain satisfactory
FI
- Risk unresolved
- Investigation required promptly
- Makes report unsatisfactory
- Uncertainty about danger means FI
Inspection vs Testing IN
Inspection
- Uses senses
- Finds visible condition
- Guides test selection
Testing
- Uses instruments
- Produces measured evidence
- Confirms electrical performance
- Inspect before choosing periodic tests
Test Evidence TE
- Predict, measure, compare, interpret, record.
- Expected value Actual value Current criterion Reasoned conclusion
Ze vs Zs TE
Ze
- External loop impedance
- Measured near origin
Zs
- Complete circuit loop
- Includes circuit conductors
- Calculated Zs uses Ze plus R1R2
Periodic Test Picker TE
- Verify protective paths → Continuity test ( Dead test )
- Verify ring conductors → End-to-end tests ( Dead test )
- Detect insulation damage → Insulation resistance ( Protect electronics )
- Verify conductor identity → Polarity checks ( Context controls )
- Verify electrode resistance → Earth electrode test
- Measure external loop → Ze test ( Live precautions )
- Measure complete loop → Zs test ( Live precautions )
- Find prospective current → PFC test ( Record highest )
- Verify RCD performance → RCD instrument ( Apply current criteria )
- Verify three-phase rotation → Phase sequence tester
- Verify device operation → Functional test
- Assess voltage drop → Measured conductor resistance
Continuity Polarity TE
- Protective continuity Verify protective conductor paths
- Main bonding Confirm continuity
- Ring line Measure end-to-end continuity
- Ring neutral Measure end-to-end continuity
- Ring CPC Measure end-to-end continuity
- Cross-connections Reveal ring irregularities
- R1 plus R2 Circuit protective path
- Polarity Confirm correct conductor connection
- Dead continuity Never test energised
R1+R2 vs r1+r2 TE
R1+R2
- Circuit protective path
- Point-specific value
r1+r2
- Ring end-to-end sum
- Whole ring conductors
- Capital and lowercase differ
Insulation Resistance TE
- Purpose Detect insulation deterioration
- Dead test Isolate before testing
- Sensitive equipment Protect before test
- SPDs Disconnect when practicable
- Connected equipment Prevent test damage
- Separated circuits Verify required separation
- Parallel paths Interpret measured resistance carefully
- Test voltage Select current standard value
- Result Compare current permitted criteria
Earthing Loop Fault TE
- Earth electrode Measure electrode resistance
- Ze External loop impedance
- Zs Complete circuit loop impedance
- Zs relationship Ze plus R1 plus R2
- PEFC Prospective earth fault current
- PSCC Prospective short-circuit current
- PFC Highest relevant prospective current
- Loop test Live-test precautions required
- Result comparison Use current permitted limits
RCD Functional Phase TE
- RCD instrument test Verify disconnection performance
- RCD test button Functional operation only
- RCD type Select compatible test method
- Fault protection Verify applicable criteria
- Additional protection Verify applicable criteria
- Phase sequence Confirm correct rotation
- Functional testing Operate controls and devices
- Isolation devices Confirm effective operation
- Manufacturer instructions Apply device-specific guidance
Test Selection TE
- Fixed sequence Not recommended periodically
- Inspection findings Drive test choices
- Installation condition Adapt testing safely
- Installation use Consider operational risk
- Extent Apply agreed coverage
- Limitations Document constrained testing
- Omitted test Record reason clearly
- Temperature Correct affected results
- Conductor length Interpret resistance proportionally
- Parallel conductors Account for parallel paths
- Connected load Prevent false readings
- Nulling Compensate test leads
Results Interpretation TE
- Expected result Predict before testing
- Measured result Record actual value
- Permitted limit Use current assessment reference
- Unexpected value Investigate before coding
- Temperature correction Apply where relevant
- Parallel path May lower resistance
- Voltage drop Use measured conductor resistance
- Circuit load Include design conditions
- Documentation Transfer results accurately
Common Traps
Universal Test Sequence
- Memorised fixed order ≠ Risk-selected periodic testing
Age-Based Coding
- Old installation automatically defective ≠ Code actual safety risk
C3 Outcome
- C3 automatically unsatisfactory ≠ C3-only may be satisfactory
RCD Test Button
- Button proves disconnection time ≠ Instrument verifies performance
Reference Access
- Same rules every task ≠ Task-specific material permissions
Electronic Books
- Electronic references online ≠ Paper references online
C1 and C2
- Both mean immediate danger ≠ Present versus potential danger
Inspection Timing
- Test everything first ≠ Inspect then select tests
Calibration Assurance
- Calibration replaces checks ≠ Check condition before use
Prospective Fault Current
- Record lowest reading ≠ Record highest relevant value
Limitations
- Silent exclusions acceptable ≠ Record and justify restrictions
Award Identity
- 2391-51 equals wiring exam ≠ 2391-51 assesses periodic work
Last Minute
- 1. Confirm 2391-51 periodic scope
- 2. Testing carries 65% online
- 3. Requirements carry 13% online
- 4. Inspection carries 17% online
- 5. Safety carries 5% online
- 6. Carry permitted paper references
- 7. Check live assessment edition
- 8. Remove prohibited personal notes
- 9. Know task-specific reference rules
- 10. Visual Task A forbids references
- 11. Prove voltage indicator twice
- 12. Lock isolation against reconnection
- 13. Identify every possible supply
- 14. Inspect before selecting tests
- 15. Record agreed extent and limitations
- 16. Increase sampling after defects
- 17. Use suitable instrument category
- 18. Check leads meet GS38
- 19. Record instrument identifiers
- 20. Verify calibration status
- 21. Classify actual safety risk
- 22. C1 means danger present
- 23. C2 means potentially dangerous
- 24. C3 means improvement recommended
- 25. FI requires further investigation
- 26. C1 C2 FI mean unsatisfactory
- 27. No universal periodic test sequence
- 28. Document adapted or omitted tests
- 29. Compare results using current criteria
- 30. Complete every EICR schedule
City & Guilds 2391-51 Periodic Inspection & Testing of Electrical Installations
- Practice Questions 233 questions Study Guide 27 topics Cheat Sheet 152 facts Flashcards 50 cards Podcast