Cheat sheet
VA Journeyman Electrician Cheat Sheet
VA Board Regulations (18VAC50-30)
- 14% of exam
- Licensing & Renewal Standards & Conduct Reciprocity State Overrides National
General Knowledge & Fundamentals
- 10% of exam
- Ohm's & Watt's Law Series vs Parallel AC vs DC NEC Chapter Map
Branch Circuits & Load Calcs
- 9% of exam
- AFCI/GFCI Locations SABC Rules Continuous Load 80% Load Calculations
Services & Feeders
- 7% of exam
- Service Disconnects Dwelling Minimum 100A Service vs Feeder General Lighting Load
Grounding & Bonding
- 9% of exam
- Grounding Electrodes GEC & EGC Sizing Grounding vs Bonding Electrode Picker
Conductors & Cables
- 10% of exam
- Table 310.16 Ampacity vs OCPD Insulation Types Adjustment Factors
Raceways & Boxes
- 10% of exam
- Box Fill Conduit Fill % Bend Limit Raceway Picker
Motors, Transformers & Controls
- 7% of exam
- Overload Sizing Branch-Circuit Sizing Motor Circuit Picker Transformer Protection
Special Occupancies & Equipment
- 9% of exam
- Hazardous Locations Pools Healthcare Spaces Signs
Utilization, Lighting & Low-Voltage
- 13% of exam
- Luminaire Clearances Appliance Disconnects Class 2/3 Circuits Emergency vs Standby
Electrical Safety
- 6% of exam
- Working Space Arc Flash Boundaries NFPA 70E PPE Headroom Rule
Quick Facts
- Exam VA Journeyman Electrician
- Questions 70 multiple-choice
- Time 210 min (3.5 hrs)
- Pass 49 of 70 (70%)
- Format Open book
- Code NEC 2020
- Admin PSI for DPOR
- Fee $100 + $171.75
Journeyman vs Master Scope RE
Journeyman
- Works under supervision
- Performs installations
- Passes journeyman exam
Master
- Can supervise/contract
- Broader scope of work
- Separate master exam
- Supervised work vs oversight
Licensing & Renewal RE
- Governing reg 18VAC50-30
- License term 3 years
- Renewal CE 3 hrs code update
- Reinstatement window 24 months, else new app
- License transfer Not assignable
- Address change Report within 30 days
- Administrator PSI for DPOR
- Apprenticeship Exempts journeyman exam
Standards, Conduct & Reciprocity RE
- Abandonment 30+ days unjustified stop
- Discipline triggers Negligence, incompetence, misrepresentation
- Reference rule State overrides national
- Open book No exam-day writing
- Tabs Permanent only, no loose
- Reciprocity (journeyman) DC, KY, WV
- Reciprocity (master) AL, MD, NC, OH
- Universal recognition 3+ yr license, no discipline
NEC Chapter Map FU
- Ch2 Wiring, Ch3 Methods, Ch4 Equipment
- Ch 2: wiring/protection Ch 3: methods/materials Ch 4: equipment Ch 5: special occupancies
Which NEC Article Covers It? FU
- Grounding/bonding question → Article 250
- Branch-circuit rule → Article 210
- Feeder/load calc → Article 220
- Service equipment → Article 230
- Conductor ampacity → Article 310
- Box or conduit fill → Art 314 / Ch 9
- Motor circuit → Article 430
- Swimming pool → Article 680
- Healthcare patient space → Article 517
- Hazardous classified location → Article 500
Electrical Theory FU
- Ohm's Law E = I x R
- Watt's Law P = E x I
- Series circuit R adds, current shared
- Parallel circuit R drops, voltage shared
- AC Reverses direction, 60 Hz
- DC One direction only
- Power factor True power / apparent
Feeder vs Branch Circuit BR
Feeder
- Supplies panelboards
- No utilization equipment
- Sized by demand load
Branch circuit
- Supplies outlets/equipment
- Ends at utilization equipment
- Sized by connected load
- Distribution vs final circuit
Branch Circuit Protection BR
- AFCI rooms Bedrooms, living areas, kitchens
- AFCI exclusions Baths, garages, unfinished basement
- SABC count 2 circuits, 20A each
- SABC scope Kitchen/pantry/dining receptacles only
- Continuous load Max 80% of rating
- 100%-rated ckt Needs listed equipment
- Multiwire branch Shared neutral, common trip
- 14 AWG limit 15A circuits only
GFCI vs AFCI BR
GFCI
- Detects ground fault
- Protects from shock
- Wet/damp locations
AFCI
- Detects arc fault
- Protects from fire
- Habitable rooms
- Shock protection vs fire protection
Load Calculations BR
- General lighting 3 VA per sq ft
- Floor area Outside dimensions
- Excluded areas Porches, garages, unfinished space
- Standard method Article 220 Part III
- Optional method 220.82, single dwelling
- Range demand Table 220.55
Service vs Feeder SE
Service
- Utility to disconnect
- Ends at service equipment
- One set per building
Feeder
- Disconnect to branch OCPD
- Can start anywhere downstream
- Multiple feeders allowed
- Where the run starts
Services & Feeders Basics SE
- Service Utility to disconnect
- Feeder Disconnect to branch OCPD
- Disconnect count 1 default, up to 6
- Grouping rule Separate enclosures required
- Dwelling minimum 100A, 3-wire
- Service conductors Sized to calculated load
Grounding Electrode Order GR
- Water pipe, then Ufer, ring, or rod
- Use what's already present Ufer: rebar in footing Ring: buried bare copper Rod: 8 ft driven
Grounding vs Bonding GR
Grounding
- Connects to earth
- Uses an electrode
- Limits voltage to ground
Bonding
- Joins metal parts
- Keeps continuity
- Clears fault current
- Earth path vs metal path
Pick a Grounding Electrode GR
- Metal water pipe present → Use as electrode ( 10 ft+ contact )
- Rebar in footing → Ufer ground ( 20 ft min )
- No natural electrode → Driven ground rod ( 8 ft min )
- Only gas piping present → Not a valid electrode
- Multiple electrodes exist → Bond them together ( 250.50 )
Grounding Electrodes GR
- Water pipe 10 ft+ underground contact
- Ufer ground 20 ft rebar or wire
- Ground ring 20 ft bare copper loop
- Ground rod 8 ft, 5/8 in min
- Listed rod Smaller diameter allowed
- Gas piping Not a valid electrode
- Multiple electrodes Must bond together
Bonding & Conductor Sizing GR
- Grounding System-to-earth connection
- Bonding Metal parts joined, continuous
- GEC size Table 250.66, by service
- EGC size Table 250.122, by OCPD
- Main bonding jumper At service only
- System bonding jumper Separately derived systems
Ampacity vs OCPD Rating CO
Ampacity
- Table 310.16 value
- Based on insulation temp
- Conductor's safe current
OCPD rating
- Breaker or fuse size
- Rounds to standard size
- Protects the conductor
- What wire carries vs what trips
Conductor Ampacity CO
- Table 310.16 Base ampacity table
- 60/75/90C columns Match insulation rating
- Termination cap 110.14(C) limits final rating
- 100A rule 60C unless otherwise marked
- Adjustment (4-6) 80% of table value
- Adjustment (7-9) 70% of table value
- Ambient correction Table 310.15(B)(1)
Conductor & Insulation Types CO
- THHN 90C dry/damp only
- THWN 75C wet locations
- THWN-2 90C wet and dry
- 12 AWG Cu Min for 20A circuit
- 14 AWG Cu Min for 15A circuit
- Grounded conductor White or gray
- EGC Green or bare
Box Fill Build Order RA
- Wires, then devices x2, clamps and EGC as one
- Conductors: actual count Device: 2x its size Clamps: one allowance EGC: one allowance
Choose a Raceway RA
- Wet, corrosive, underground → PVC conduit ( needs separate EGC )
- Need extra physical protection → RMC
- Standard indoor branch wiring → EMT ( metal path bonds )
- Flexible near vibration, wet → LFMC
- Flexible, dry locations only → ENT
Box Fill RA
- 14 AWG 2.00 in3 per conductor
- 12 AWG 2.25 in3 per conductor
- 10 AWG 2.50 in3 per conductor
- Device (switch/recep) 2x largest connected wire
- All EGCs 1 allowance, largest size
- All clamps 1 allowance total
- Fixture stud/hickey 1 allowance per size
Conduit Fill & Bends RA
- 1 conductor 53% fill max
- 2 conductors 31% fill max
- 3+ conductors 40% fill max
- Bend limit 360 deg between pulls
- EMT Thin-wall, unthreaded
- RMC Thick-wall, threaded
- PVC Nonmetallic, needs separate EGC
Motor Overload Percentage MO
- High SF or low rise: 125%, else 115%
- SF >= 1.15: 125% Temp rise <= 40C: 125% Otherwise: 115% Base = nameplate FLA
Size a Motor Circuit MO
- Need motor FLC → Table 430.247-250 ( Not nameplate )
- Size branch conductor → 125% of FLC ( 430.22 )
- Motor SF >= 1.15 → 125% FLA overload ( 430.32(A)(1) )
- Motor SF < 1.15 → 115% FLA overload
- Place disconnect → Within sight or lockable
- Multiple small motors → Group circuit if listed ( 430.53 )
Motor Sizing MO
- Branch conductor 125% of table FLC
- FLC source Tables 430.247-430.250
- Overload (SF>=1.15) 125% of nameplate FLA
- Overload (SF<1.15) 115% of nameplate FLA
- Disconnect location Within sight or lockable
- Group motors Allowed under 430.53 limits
- Transformer protection Table 450.3 percentages
Class I vs Class II Locations SP
Class I
- Flammable gas or vapor
- Paint booths, fuel areas
Class II
- Combustible dust
- Grain, flour facilities
- Gas/vapor vs dust
Special Occupancies SP
- Class I Flammable gas or vapor
- Class II Combustible dust
- Division 1 Hazard normally present
- Division 2 Hazard abnormal only
- Pool bonding 3 ft perimeter, 4 pts
- Patient care EGC Insulated copper, redundant path
- Sign disconnect Within sight or lockable
Emergency vs Standby Systems UT
Emergency (Art 700)
- Life safety loads
- 10-second transfer
Legally required standby (701)
- Required by code/authority
- Longer transfer allowed
- Life safety vs required backup
Utilization Equipment & Lighting UT
- Closet surface fixture 12 in clearance
- Closet recessed fixture 6 in clearance
- Recessed non-IC housing 3 in from insulation
- Housing clearance 1/2 in from wood
- Appliance disconnect In-sight switch or lockable
- Utilization equipment Uses power, doesn't distribute
Low-Voltage & Communications UT
- Class 2/3 Power-limited, Article 725
- Communications Article 805, primary protector
- Fire alarm NPLFA Non-power-limited, Article 760
- Fire alarm PLFA Power-limited, Article 760
- CATV Article 820
Electrical Safety SA
- 0-150V working space 3 ft, all conditions
- 151-600V Cond 1 3 ft depth
- 151-600V Cond 2 3.5 ft depth
- 151-600V Cond 3 4 ft depth
- Working width 30 in minimum
- Headroom 6.5 ft (78 in)
- Arc flash assessment Before energized-equipment work
- Approach boundaries Limited, restricted, arc flash
Common Traps
Bathroom AFCI assumption
- Bathroom needs GFCI only ≠ AFCI excludes bathrooms
14 AWG on 20A breaker
- 14 AWG maxes at 15A ≠ 20A needs 12 AWG
Nameplate vs table FLC
- Nameplate sizes overload only ≠ Table sizes branch conductor
PVC self-grounding myth
- PVC is nonmetallic ≠ Needs separate EGC wire
Reciprocity assumption
- DC/KY/WV is journeyman only ≠ VA exam still required
Open book misconception
- No writing on exam day ≠ Permanent tabs only
Retake wait myth
- No 3-fail wait period ≠ Just seat availability limit
Last Minute
- 1. 70 questions, 210 minutes, 49 pass
- 2. Open book: bring NEC, 70E, regs
- 3. Permanent tabs only, no loose pages
- 4. State-specific rule beats national rule
- 5. AFCI = habitable rooms; GFCI = wet areas
- 6. 12 AWG minimum on 20A circuits
- 7. Box fill: 14g 2.0in, 12g 2.25in
- 8. Motor branch conductor = 125% table FLC
- 9. Overload 125% high SF, else 115%
- 10. Ground rod: 8 ft, 0.625 in
- 11. License: 3-year term, 3 CE hrs
- 12. Journeyman reciprocity: DC, KY, WV only
Virginia Journeyman Electrician
- Practice Questions 340 questions Study Guide 45 topics Cheat Sheet 117 facts Flashcards 50 cards Shorts 1 short Videos 1 video Blogs 1 blog Free CE Podcast