VA Board Regulations (18VAC50-30)

  • 14% of exam
  • Licensing & Renewal Standards & Conduct Reciprocity State Overrides National

General Knowledge & Fundamentals

  • 10% of exam
  • Ohm's & Watt's Law Series vs Parallel AC vs DC NEC Chapter Map

Branch Circuits & Load Calcs

  • 9% of exam
  • AFCI/GFCI Locations SABC Rules Continuous Load 80% Load Calculations

Services & Feeders

  • 7% of exam
  • Service Disconnects Dwelling Minimum 100A Service vs Feeder General Lighting Load

Grounding & Bonding

  • 9% of exam
  • Grounding Electrodes GEC & EGC Sizing Grounding vs Bonding Electrode Picker

Conductors & Cables

  • 10% of exam
  • Table 310.16 Ampacity vs OCPD Insulation Types Adjustment Factors

Raceways & Boxes

  • 10% of exam
  • Box Fill Conduit Fill % Bend Limit Raceway Picker

Motors, Transformers & Controls

  • 7% of exam
  • Overload Sizing Branch-Circuit Sizing Motor Circuit Picker Transformer Protection

Special Occupancies & Equipment

  • 9% of exam
  • Hazardous Locations Pools Healthcare Spaces Signs

Utilization, Lighting & Low-Voltage

  • 13% of exam
  • Luminaire Clearances Appliance Disconnects Class 2/3 Circuits Emergency vs Standby

Electrical Safety

  • 6% of exam
  • Working Space Arc Flash Boundaries NFPA 70E PPE Headroom Rule

Quick Facts

  • Exam VA Journeyman Electrician
  • Questions 70 multiple-choice
  • Time 210 min (3.5 hrs)
  • Pass 49 of 70 (70%)
  • Format Open book
  • Code NEC 2020
  • Admin PSI for DPOR
  • Fee $100 + $171.75

Journeyman vs Master Scope RE

Journeyman

  • Works under supervision
  • Performs installations
  • Passes journeyman exam

Master

  • Can supervise/contract
  • Broader scope of work
  • Separate master exam
  • Supervised work vs oversight

Licensing & Renewal RE

  • Governing reg 18VAC50-30
  • License term 3 years
  • Renewal CE 3 hrs code update
  • Reinstatement window 24 months, else new app
  • License transfer Not assignable
  • Address change Report within 30 days
  • Administrator PSI for DPOR
  • Apprenticeship Exempts journeyman exam

Standards, Conduct & Reciprocity RE

  • Abandonment 30+ days unjustified stop
  • Discipline triggers Negligence, incompetence, misrepresentation
  • Reference rule State overrides national
  • Open book No exam-day writing
  • Tabs Permanent only, no loose
  • Reciprocity (journeyman) DC, KY, WV
  • Reciprocity (master) AL, MD, NC, OH
  • Universal recognition 3+ yr license, no discipline

NEC Chapter Map FU

  • Ch2 Wiring, Ch3 Methods, Ch4 Equipment
  • Ch 2: wiring/protection Ch 3: methods/materials Ch 4: equipment Ch 5: special occupancies

Which NEC Article Covers It? FU

  • Grounding/bonding question → Article 250
  • Branch-circuit rule → Article 210
  • Feeder/load calc → Article 220
  • Service equipment → Article 230
  • Conductor ampacity → Article 310
  • Box or conduit fill → Art 314 / Ch 9
  • Motor circuit → Article 430
  • Swimming pool → Article 680
  • Healthcare patient space → Article 517
  • Hazardous classified location → Article 500

Electrical Theory FU

  • Ohm's Law E = I x R
  • Watt's Law P = E x I
  • Series circuit R adds, current shared
  • Parallel circuit R drops, voltage shared
  • AC Reverses direction, 60 Hz
  • DC One direction only
  • Power factor True power / apparent

Feeder vs Branch Circuit BR

Feeder

  • Supplies panelboards
  • No utilization equipment
  • Sized by demand load

Branch circuit

  • Supplies outlets/equipment
  • Ends at utilization equipment
  • Sized by connected load
  • Distribution vs final circuit

Branch Circuit Protection BR

  • AFCI rooms Bedrooms, living areas, kitchens
  • AFCI exclusions Baths, garages, unfinished basement
  • SABC count 2 circuits, 20A each
  • SABC scope Kitchen/pantry/dining receptacles only
  • Continuous load Max 80% of rating
  • 100%-rated ckt Needs listed equipment
  • Multiwire branch Shared neutral, common trip
  • 14 AWG limit 15A circuits only

GFCI vs AFCI BR

GFCI

  • Detects ground fault
  • Protects from shock
  • Wet/damp locations

AFCI

  • Detects arc fault
  • Protects from fire
  • Habitable rooms
  • Shock protection vs fire protection

Load Calculations BR

  • General lighting 3 VA per sq ft
  • Floor area Outside dimensions
  • Excluded areas Porches, garages, unfinished space
  • Standard method Article 220 Part III
  • Optional method 220.82, single dwelling
  • Range demand Table 220.55

Service vs Feeder SE

Service

  • Utility to disconnect
  • Ends at service equipment
  • One set per building

Feeder

  • Disconnect to branch OCPD
  • Can start anywhere downstream
  • Multiple feeders allowed
  • Where the run starts

Services & Feeders Basics SE

  • Service Utility to disconnect
  • Feeder Disconnect to branch OCPD
  • Disconnect count 1 default, up to 6
  • Grouping rule Separate enclosures required
  • Dwelling minimum 100A, 3-wire
  • Service conductors Sized to calculated load

Grounding Electrode Order GR

  • Water pipe, then Ufer, ring, or rod
  • Use what's already present Ufer: rebar in footing Ring: buried bare copper Rod: 8 ft driven

Grounding vs Bonding GR

Grounding

  • Connects to earth
  • Uses an electrode
  • Limits voltage to ground

Bonding

  • Joins metal parts
  • Keeps continuity
  • Clears fault current
  • Earth path vs metal path

Pick a Grounding Electrode GR

  • Metal water pipe present → Use as electrode ( 10 ft+ contact )
  • Rebar in footing → Ufer ground ( 20 ft min )
  • No natural electrode → Driven ground rod ( 8 ft min )
  • Only gas piping present → Not a valid electrode
  • Multiple electrodes exist → Bond them together ( 250.50 )

Grounding Electrodes GR

  • Water pipe 10 ft+ underground contact
  • Ufer ground 20 ft rebar or wire
  • Ground ring 20 ft bare copper loop
  • Ground rod 8 ft, 5/8 in min
  • Listed rod Smaller diameter allowed
  • Gas piping Not a valid electrode
  • Multiple electrodes Must bond together

Bonding & Conductor Sizing GR

  • Grounding System-to-earth connection
  • Bonding Metal parts joined, continuous
  • GEC size Table 250.66, by service
  • EGC size Table 250.122, by OCPD
  • Main bonding jumper At service only
  • System bonding jumper Separately derived systems

Ampacity vs OCPD Rating CO

Ampacity

  • Table 310.16 value
  • Based on insulation temp
  • Conductor's safe current

OCPD rating

  • Breaker or fuse size
  • Rounds to standard size
  • Protects the conductor
  • What wire carries vs what trips

Conductor Ampacity CO

  • Table 310.16 Base ampacity table
  • 60/75/90C columns Match insulation rating
  • Termination cap 110.14(C) limits final rating
  • 100A rule 60C unless otherwise marked
  • Adjustment (4-6) 80% of table value
  • Adjustment (7-9) 70% of table value
  • Ambient correction Table 310.15(B)(1)

Conductor & Insulation Types CO

  • THHN 90C dry/damp only
  • THWN 75C wet locations
  • THWN-2 90C wet and dry
  • 12 AWG Cu Min for 20A circuit
  • 14 AWG Cu Min for 15A circuit
  • Grounded conductor White or gray
  • EGC Green or bare

Box Fill Build Order RA

  • Wires, then devices x2, clamps and EGC as one
  • Conductors: actual count Device: 2x its size Clamps: one allowance EGC: one allowance

Choose a Raceway RA

  • Wet, corrosive, underground → PVC conduit ( needs separate EGC )
  • Need extra physical protection → RMC
  • Standard indoor branch wiring → EMT ( metal path bonds )
  • Flexible near vibration, wet → LFMC
  • Flexible, dry locations only → ENT

Box Fill RA

  • 14 AWG 2.00 in3 per conductor
  • 12 AWG 2.25 in3 per conductor
  • 10 AWG 2.50 in3 per conductor
  • Device (switch/recep) 2x largest connected wire
  • All EGCs 1 allowance, largest size
  • All clamps 1 allowance total
  • Fixture stud/hickey 1 allowance per size

Conduit Fill & Bends RA

  • 1 conductor 53% fill max
  • 2 conductors 31% fill max
  • 3+ conductors 40% fill max
  • Bend limit 360 deg between pulls
  • EMT Thin-wall, unthreaded
  • RMC Thick-wall, threaded
  • PVC Nonmetallic, needs separate EGC

Motor Overload Percentage MO

  • High SF or low rise: 125%, else 115%
  • SF >= 1.15: 125% Temp rise <= 40C: 125% Otherwise: 115% Base = nameplate FLA

Size a Motor Circuit MO

  • Need motor FLC → Table 430.247-250 ( Not nameplate )
  • Size branch conductor → 125% of FLC ( 430.22 )
  • Motor SF >= 1.15 → 125% FLA overload ( 430.32(A)(1) )
  • Motor SF < 1.15 → 115% FLA overload
  • Place disconnect → Within sight or lockable
  • Multiple small motors → Group circuit if listed ( 430.53 )

Motor Sizing MO

  • Branch conductor 125% of table FLC
  • FLC source Tables 430.247-430.250
  • Overload (SF>=1.15) 125% of nameplate FLA
  • Overload (SF<1.15) 115% of nameplate FLA
  • Disconnect location Within sight or lockable
  • Group motors Allowed under 430.53 limits
  • Transformer protection Table 450.3 percentages

Class I vs Class II Locations SP

Class I

  • Flammable gas or vapor
  • Paint booths, fuel areas

Class II

  • Combustible dust
  • Grain, flour facilities
  • Gas/vapor vs dust

Special Occupancies SP

  • Class I Flammable gas or vapor
  • Class II Combustible dust
  • Division 1 Hazard normally present
  • Division 2 Hazard abnormal only
  • Pool bonding 3 ft perimeter, 4 pts
  • Patient care EGC Insulated copper, redundant path
  • Sign disconnect Within sight or lockable

Emergency vs Standby Systems UT

Emergency (Art 700)

  • Life safety loads
  • 10-second transfer

Legally required standby (701)

  • Required by code/authority
  • Longer transfer allowed
  • Life safety vs required backup

Utilization Equipment & Lighting UT

  • Closet surface fixture 12 in clearance
  • Closet recessed fixture 6 in clearance
  • Recessed non-IC housing 3 in from insulation
  • Housing clearance 1/2 in from wood
  • Appliance disconnect In-sight switch or lockable
  • Utilization equipment Uses power, doesn't distribute

Low-Voltage & Communications UT

  • Class 2/3 Power-limited, Article 725
  • Communications Article 805, primary protector
  • Fire alarm NPLFA Non-power-limited, Article 760
  • Fire alarm PLFA Power-limited, Article 760
  • CATV Article 820

Electrical Safety SA

  • 0-150V working space 3 ft, all conditions
  • 151-600V Cond 1 3 ft depth
  • 151-600V Cond 2 3.5 ft depth
  • 151-600V Cond 3 4 ft depth
  • Working width 30 in minimum
  • Headroom 6.5 ft (78 in)
  • Arc flash assessment Before energized-equipment work
  • Approach boundaries Limited, restricted, arc flash

Common Traps

Bathroom AFCI assumption

  • Bathroom needs GFCI only ≠ AFCI excludes bathrooms

14 AWG on 20A breaker

  • 14 AWG maxes at 15A ≠ 20A needs 12 AWG

Nameplate vs table FLC

  • Nameplate sizes overload only ≠ Table sizes branch conductor

PVC self-grounding myth

  • PVC is nonmetallic ≠ Needs separate EGC wire

Reciprocity assumption

  • DC/KY/WV is journeyman only ≠ VA exam still required

Open book misconception

  • No writing on exam day ≠ Permanent tabs only

Retake wait myth

  • No 3-fail wait period ≠ Just seat availability limit

Last Minute

  • 1. 70 questions, 210 minutes, 49 pass
  • 2. Open book: bring NEC, 70E, regs
  • 3. Permanent tabs only, no loose pages
  • 4. State-specific rule beats national rule
  • 5. AFCI = habitable rooms; GFCI = wet areas
  • 6. 12 AWG minimum on 20A circuits
  • 7. Box fill: 14g 2.0in, 12g 2.25in
  • 8. Motor branch conductor = 125% table FLC
  • 9. Overload 125% high SF, else 115%
  • 10. Ground rod: 8 ft, 0.625 in
  • 11. License: 3-year term, 3 CE hrs
  • 12. Journeyman reciprocity: DC, KY, WV only

Virginia Journeyman Electrician