Iran Nezam Electrical Design Exam

Iran Construction Engineering Org — Electrical Design

Backup Power Lightning ProtectionEnglish
Exam overview

Practice session

A standby diesel generator must power a continuous emergency building load of 150 kW at 0.80 power factor (base load S_base = 187.5 kVA). The largest single motor starting under emergency mode is a 45 kW three-phase fire booster pump started direct-on-line (DOL), demanding an inrush starting apparent power of S_start = 6 * 45 = 270 kVA. To limit generator transient voltage dip to <= 20% during motor start, empirical generator sizing requires S_gen >= S_base + (S_start / 2). What is the minimum standard generator commercial rating (kVA) to be specified?

Loading your practice session…