SCE PE Fire Protection

SCE Practice of Engineering (PE) — Fire Protection Engineering (Saudi Arabia)

Non Water Based Fire SuppressionEnglish
Exam overview

Practice session

For a 200 m³ HFC-227ea enclosure, use W = (V/S)C/(100 − C) at specified concentration C = 7.9%. Specific vapor volume is 0.13716 m³/kg at 20°C and 0.14229 m³/kg at 30°C. Before other corrections, what agent masses achieve that concentration at each temperature, and which temperature requires more agent?

Loading your practice session…