NM CID ES-3

New Mexico CID Low Voltage Special Systems (Under 50 Volts) Examination

Applied Systems DesignEnglish
Exam overview

Practice session

A non-voice fire-alarm panel draws 0.25 A in standby and 2.00 A in alarm. Using NFPA 72-2010 durations (24 h standby + 5 min alarm) and a 20 percent safety factor, what is the minimum battery capacity?

Loading your practice session…