4.4 Fats, Oils, and Grease (FOG) Control Programs

ABC Wastewater Collection Operator Class I Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Gravity Sewers, System Components & Materials

1.1 Gravity Sewer Principles & System Layout 1.2 Sewer Pipe Materials, Sizing & Joining Methods 1.3 Manholes, Drop Structures & Appurtenances 1.4 Gravity Sewer Hydraulics, Slope & Scour Velocity

2 Chapter 2: Lift Stations, Pumping Systems & Force Mains

2.1 Lift Station Design: Wet Well vs Dry Well Systems 2.2 Wastewater Pumps & Operating Principles 2.3 Level Controls, Pump Sequencing & SCADA Telemetry 2.4 Force Mains, Valves & Surge Protection 2.5 Lift Station Emergency Power, Maintenance & Operation

3 Chapter 3: Sewer Inspection, Testing & Cleaning

3.1 Hydraulic Jetting & High-Velocity Cleaning 3.2 Mechanical Rodding, Bucketing & Clearing Methods 3.3 Closed-Circuit Television (CCTV) Inspection & NASSCO PACP 3.4 Sewer Testing Methods: Smoke, Dye & Acoustic 3.5 Root, Grease & Debris Management

4 Chapter 4: Inflow & Infiltration (I/I), SSOs & FOG Management

4.1 Inflow vs Infiltration Fundamentals & RDII 4.2 Sanitary Sewer Overflows (SSOs) & Combined Sewer Overflows (CSOs) 4.3 SSO Emergency Response, Containment & NPDES Reporting 4.4 Fats, Oils, and Grease (FOG) Control Programs 4.5 Sewer System Rehabilitation & Trenchless Methods

5 Chapter 5: Safety, Confined Space Entry & Environmental Hazards

5.1 OSHA 1910.146 Permit-Required Confined Space Standards 5.2 Atmospheric Testing, Monitoring & Calibration Sequence 5.3 Ventilation, PPE & Emergency Rescue Equipment 5.4 Hydrogen Sulfide (H2S), Toxic Gases & Crown Corrosion 5.5 Trenching, Excavation & Traffic Safety (MUTCD & 811)

6 Chapter 6: Operator Math, Hydraulics & System Administration

6.1 Flow, Velocity & Cross-Sectional Area Calculations 6.2 Lift Station Hydraulics, Pumping Rate & Drawdown Math 6.3 Sewer Slope, Invert Elevations & Grade Calculations 6.4 Chemical Dosing, Feed Rate & Quantity Calculations 6.5 Regulatory Framework, Recordkeeping & System Mapping

7 Chapter 7: Equipment Operation, Tools & Preventive Maintenance

7.1 Gas Detectors, Flow Meters & Blowers: Operation and Calibration 7.2 Balling, Flushing, Poly Pigs & Cleaning-Method Selection 7.3 Heavy Equipment, Excavation & Hydro Excavation 7.4 Electrical Equipment: VFDs, Motor Control Centers & Low-Voltage Devices 7.5 Preventive Maintenance Programs, SOP/OEM Compliance & Support Tools

8 Chapter 8: System Restoration, Mapping & Emergency Operations

8.1 Manhole, Tap & Lateral Rehabilitation and Exfiltration Control 8.2 Appurtenance Inspection: Air Release Valves, Siphons, Regulators & Outfalls 8.3 Blueprints, GIS, Asset Management & System Mapping 8.4 Emergency Bypass Pumping & System Failure Response 8.5 New Pipe Installation Inspection & Acceptance Testing

9 Chapter 9: Monitoring, Safety Programs & System Administration

9.1 Flow Monitoring, Flow Meters & Sensor Calibration 9.2 Wastewater Characteristics & Abnormal Discharge Identification 9.3 Chemical Handling, Inventory, Feed Systems & Spill Response 9.4 Electrical Safety, Lockout/Tagout, Fire Safety & Occupational Health 9.5 Customer Service, Safety Programs, Operator Training & Regulatory Administration

4.4 Fats, Oils, and Grease (FOG) Control Programs

Key Takeaways Explain This Topic AI

FOG enters sewers as hot liquid waste and cools inside mains, where saponification with calcium forms hardened metallic soap deposits ('fatbergs').

Food Service Establishments (FSEs) are regulated via Hydromechanical Grease Interceptors (HGIs, 20–100 gpm) or large outdoor Gravity Grease Interceptors (GGIs, 750–2,000+ gal).

The universal maintenance benchmark is the 25% Rule: interceptors must be fully pumped when the combined floating grease cap and settled sludge reach 25% of total liquid depth.

Municipalities enforce FOG programs through legal sewer use ordinances, FSE discharge limits (typically 100 mg/L), hauler manifest tracking (3-year retention), and kitchen BMPs.

Last updated: September 2026

Fats, Oils, and Grease (FOG) Control Programs

Quick Answer: FOG discharged from commercial kitchens and residential homes cools and undergoes saponification with calcium ions in wastewater to form solid "fatbergs" that clog collection pipes. Utilities control FOG using indoor Hydromechanical Grease Interceptors (HGIs) or outdoor Gravity Grease Interceptors (GGIs) , enforcing the 25% Rule (interceptor must be pumped when grease plus sludge equals 25% of liquid depth), establishing strict sewer use ordinances, and tracking waste hauler manifests.

Fats, Oils, and Grease (FOG) represent the single greatest operational and maintenance challenge in municipal wastewater collection systems. Uncontrolled FOG discharges cause pipe constrictions, accelerate hydrogen sulfide corrosion, create foul odors, overwhelm lift station pumps, and cause premature pump wear. A robust FOG Control Program is essential for maintaining compliance with EPA CMOM guidelines and preventing SSOs.

1. FOG Chemistry & Deposition Dynamics

FOG encompasses animal fats (lard, tallow, butter, meat fats) and vegetable oils (shortening, canola oil, olive oil, fryer oil). When washed down commercial kitchen sinks with hot water and dishwashing detergents, FOG enters the plumbing drainage system as a warm liquid emulsion ( 120 ∘ F − 140 ∘ F 120^\circ\text{F} - 140^\circ\text{F} 12 0 ∘ F − 14 0 ∘ F ). [HOT KITCHEN DISCHARGE]

  • (Liquid FOG + Detergent Emulsion)
  • |
  • v
  • [ENTERS MUNICIPAL GRAVITY SEWER MAIN]
  • (Cools to 50°F - 60°F Ambient)
  • |
  • +---------------------------+---------------------------+
  • | |
  • v v
  • [PHYSICAL CONGEALING] [SAPONIFICATION REACTION]
  • Fats cool below melting point; Free Fatty Acids (FFAs) +
  • stick to pipe crown & walls Calcium Ions (Ca2+) in sewage
  • | |
  • +---------------------------+---------------------------+
  • |
  • v
  • ============================
  • >>> HARDENED FATBERG MASS >>> (Total Pipe Blockage)
  • ============================
  • The Saponification Reaction

Beyond simple cooling and congealing, grease deposits undergo a chemical transformation known as saponification . In the sewer environment, anaerobic microbial activity breaks triglycerides down into free fatty acids (palmitic, stearic, and oleic acids). These fatty acids chemically bond with calcium ions ( C a 2 + Ca^{2+} C a 2 + ) present in domestic hard water and concrete pipe corrosion products. Fatty Acids + Calcium Ions ( C a 2 + ) ⟶ Calcium Fatty Acid Soaps (Fatbergs) \text{Fatty Acids} + \text{Calcium Ions } (Ca^{2+}) \longrightarrow \text{Calcium Fatty Acid Soaps (Fatbergs)} Fatty Acids + Calcium Ions ( C a 2 + ) ⟶ Calcium Fatty Acid Soaps (Fatbergs)

This reaction produces hard, insoluble metallic calcium soaps. These solid deposits will not re-melt with hot water and resist chemical dissolution, requiring mechanical cutting or ultra-high-pressure water jetting ( > 2 , 000 psi >2,000\text{ psi} > 2 , 000 psi ) to dislodge.

2. Grease Interceptor Technology: HGI vs. GGI

Food Service Establishments (FSEs) such as restaurants, commercial bakeries, school cafeterias, and butcher shops are required to install grease removal devices to separate FOG from wastewater prior to entering the public sewer. [TWO-CHAMBER OUTDOOR GRAVITY GREASE INTERCEPTOR (GGI)]

  • [Manhole 1] [Manhole 2]
  • | |
  • ==============+===============================+============== (Surface)
  • | |
  • | +------------+ +------------+ |
  • ==>| | Inlet Tee | | Outlet Tee | |===> Clean
  • | +-----+------+ +-----+------+ | Effluent
  • | | [FLOATING GREASE CAP] (Top) | | To Sewer
  • | | ~~~~~~~~~~~~~~~~~~~~~ | | Main
  • | v | |
  • | [CLEAR WATER ZONE] (HRT >= 30 min) ^ |
  • | | |
  • | ======================= | |
  • | | Compartment Baffle | | |
  • | | Pass-Through | | |
  • | ..........+.....................+..............+....... |
  • | [SETTLED HEAVY SLUDGE BLANKET] (Bottom) |
  • +-----------------------------------------------------------+
  • Technical Comparison: HGI vs. GGI

Design Feature Hydromechanical Grease Interceptor (HGI) Gravity Grease Interceptor (GGI)

Installation Location Indoors: Under-sink, floor-mounted, or floor-recessed Outdoors: Underground concrete or fiberglass vault

Operating Capacity Flow-rate rated: 20 to 100 gpm Volume rated: 750 to 2,000+ gallons

Hydraulic Retention Short (1 to 3 minutes); relies on internal baffles & air Long ( minimum 30 minutes hydraulic retention time)

Separation Method Flow control device with air intake vent; micro-bubbles Gravity differential (FOG specific gravity ~0.90 vs water 1.00)

Cleaning Frequency Daily, weekly, or bi-weekly by kitchen staff Every 30 to 90 days by licensed liquid waste pump hauler

Application Scope Small restaurants, deli counters, coffee shops High-volume restaurants, cafeterias, full-service kitchens

3. The 25% Rule for Interceptor Maintenance

The 25% Rule is the universal regulatory standard enforced by municipal FOG inspectors to determine when an interceptor must be pumped and cleaned. Combined FOG & Sludge Depth (inches) ≥ 0.25 × Total Liquid Depth (inches) \text{Combined FOG \& Sludge Depth (inches)} \ge 0.25 \times \text{Total Liquid Depth (inches)} Combined FOG & Sludge Depth (inches) ≥ 0.25 × Total Liquid Depth (inches) +-------------------------------------------------------------------------+

  • | THE 25% RULE EXPLAINED |
  • +-------------------------------------------------------------------------+
  • | When the combined thickness of the TOP FLOATING GREASE LAYER plus the |
  • | BOTTOM SETTLED SLUDGE LAYER occupies 25% or more of the tank's total |
  • | operating liquid depth, the interceptor MUST be completely evacuated. |
  • | |
  • | Why? When solids exceed 25%, the effective clear water volume is |
  • | compromised. Retention time drops below 30 minutes, velocity increases, |
  • | and grease short-circuits directly out the discharge tee into the |
  • | municipal collection system. |
  • +-------------------------------------------------------------------------+
  • Measurement Procedure with a Core Sampler (Sludge Judge)

Lower a clear acrylic core sampler ("Sludge Judge") through the inspection port to the bottom of the interceptor.

Allow the internal check valve to seat and withdraw the column.

Measure three specific vertical dimensions:

Total Operating Liquid Depth ( D t o t a l D_{total} D t o t a l ​ ): Distance from bottom of tank to liquid surface.

Top Grease Layer Thickness ( T g r e a s e T_{grease} T g re a se ​ ): Depth of floating congealed grease cap.

Bottom Sludge Layer Thickness ( T s l u d g e T_{sludge} T s l u d g e ​ ): Depth of settled food solids and grit.

Worked Step-by-Step Problem: 25% Rule Compliance

Problem: A FOG inspector tests an outdoor 1,500-gallon gravity grease interceptor using a Sludge Judge. The total liquid depth is 48 inches 48\text{ inches} 48 inches . The top floating grease layer measures 7.5 inches 7.5\text{ inches} 7.5 inches and the bottom sludge layer measures 6.0 inches 6.0\text{ inches} 6.0 inches . Determine: (a) the total solids percentage, and (b) whether the facility is in violation of the 25% Rule.

Step 1: Calculate Total Combined Solids Thickness T s o l i d s = T g r e a s e + T s l u d g e = 7.5 in + 6.0 in = 13.5 inches T_{solids} = T_{grease} + T_{sludge} = 7.5\text{ in} + 6.0\text{ in} = 13.5\text{ inches} T so l i d s ​ = T g re a se ​ + T s l u d g e ​ = 7.5 in + 6.0 in = 13.5 inches

Step 2: Calculate Allowable Maximum 25% Thickness Allowable Limit = 0.25 × D t o t a l = 0.25 × 48 in = 12.0 inches \text{Allowable Limit} = 0.25 \times D_{total} = 0.25 \times 48\text{ in} = 12.0\text{ inches} Allowable Limit = 0.25 × D t o t a l ​ = 0.25 × 48 in = 12.0 inches

Step 3: Calculate Actual Solids Percentage Solids Percentage = ( 13.5 in 48.0 in ) × 100 = 28.125 % \text{Solids Percentage} = \left( \frac{13.5\text{ in}}{48.0\text{ in}} \right) \times 100 = 28.125\% Solids Percentage = ( 48.0 in 13.5 in ​ ) × 100 = 28.125%

Compliance Finding: The interceptor is operating at 28.1 % 28.1\% 28.1% solids, exceeding the 25.0 % 25.0\% 25.0% legal threshold ( 13.5 in > 12.0 in 13.5\text{ in} > 12.0\text{ in} 13.5 in > 12.0 in ). The inspector issues a Notice of Violation (NOV) requiring a complete pump-out within 48 hours.

4. Municipal FOG Program Administration & Kitchen BMPs

An effective municipal FOG program combines regulatory enforcement with commercial and residential education. FOG CONTROL PROGRAM PILLARS

  • |
  • +--------------------------+--------------------------+
  • | | |
  • v v v
  • [Sewer Use Ordinance] [FSE Facility Inspections] [Hauler Manifest Tracking]
  • Legal authority - Unannounced inspections - Cradle-to-grave tracking
  • 100 mg/L FOG limit - Check interceptor baffles - Verify pump-out logs
  • Interceptor mandate - Inspect sink strainers - 3-year record retention
  • Fines & surcharge fees - Enforce 25% rule - Certified disposal sites
  • Best Management Practices (BMPs) for Kitchens

Dry Wiping / Scraping: Scrape food residues and wipe greasy cookware with paper towels directly into trash bins before dishwashing.

Drain Screens: Install removable mesh screens ( ≤ 1 / 8 inch \le 1/8\text{ inch} ≤ 1/8 inch mesh) in all sink drains, floor drains, and mop basins.

Yellow Grease Recycling: Collect spent deep-fryer oil in dedicated outdoor rendering barrels for biodiesel recycling; never pour fryer oil into sinks or floor drains.

Temperature & Additive Restrictions: Prohibit hot water flushing ( > 140 ∘ F >140^\circ\text{F} > 14 0 ∘ F ) intended to melt grease past interceptors. Strictly ban chemical, enzymatic, or biological grease emulsifiers/degreasers , as they merely liquefy grease temporarily, causing it to re-congeal downstream in municipal collection mains.

Residential Outreach: Distribute "Cease the Grease" educational materials, promote residential used cooking oil drop-off centers, and provide free reusable grease collection scrapers and cans.