9.2 Revised Total Coliform Rule (RTCR)

ABC/WPI Water Distribution Operator Class I Certification Exam Exam

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Exam Overview

1.1 Current Exam Facts 1.2 Certification, Eligibility & the WPI/ABC System 1.3 Study Plan & How to Use This Guide

2 Distribution Components — Pipes, Joints & Fittings

2.1 Mains & Service Lines 2.2 Pipe Materials (PVC, DI, CI, AC, HDPE, Copper, Steel) 2.3 Joints, Fittings & Thrust Restraint

3 Distribution Components — Valves, Hydrants, Storage & Wells

3.1 Valves (Gate, Butterfly, Check, PRV, Air Release, Blow-off) 3.2 Fire Hydrants 3.3 Storage Facilities (Ground, Elevated, Hydropneumatic) 3.4 Pumps & Pump Stations 3.5 Wells, Water Levels & Sanitary Condition

4 Meters, Backflow Devices, SCADA, Hydraulics & Demand

4.1 Meters & Metering (AMR/AMI) 4.2 Backflow Prevention Devices (Air Gap, RPZ, DCVA, PVB) 4.3 SCADA & Instrumentation 4.4 Distribution Hydraulics: Pressure, C-factor, Head Loss 4.5 System Demand, Water Production & Design Basics

5 Installation — Excavation, Bedding & Sewer Separation

5.1 Excavation Safety & Trenching (OSHA Subpart P) 5.2 Bedding, Backfill & Thrust Blocks 5.3 Separation from Sewer Mains

6 Installation — Pressure Testing & Disinfection

6.1 AWWA C600 Hydrostatic Pressure Testing 6.2 AWWA C651 Disinfection of New Mains 6.3 Service Line Installation, Tapping & Main Repairs

7 Operations & Maintenance

7.1 Valve Exercising & Hydrant Maintenance 7.2 Flushing & Unidirectional Flushing 7.3 Storage Facility Cleaning & Disinfection 7.4 Meter Reading & Underground Locating

8 Water Quality Monitoring & Lab Analysis

8.1 Disinfection Principles: Free vs Combined Chlorine, Breakpoint 8.2 Chemical Dosage & Feed Equipment 8.3 Sample Collection & Lab Analysis (Chlorine Residual, pH, Turbidity) 8.4 Lab Interpretation & Distribution Water Quality Problems

9 Regulations, Sampling & Public Notification

9.1 SDWA & Federal Drinking Water Regulations 9.2 Revised Total Coliform Rule (RTCR) 9.3 Lead & Copper Rule Revisions (LCRR) 9.4 Public Notification, CCR & Sampling Techniques

10 Safety, Security & Administrative Procedures

10.1 PPE, Safe Work Practices & Lockout/Tagout 10.2 Traffic Control (MUTCD) & Confined Space Entry 10.3 Underground Locating (811) & APWA Color Codes 10.4 Cross-Connection Control Program & Hazard Levels 10.5 System Maps, Schematics, Plans & Asset Management

11 Security, Records, Math Review & Final Readiness

11.1 Emergency Response, Facility Security & Water Loss Control 11.2 Recordkeeping, SOPs & Customer Inquiries 11.3 Operator Math: Flow, Pressure, Head & Pipe Volume 11.4 Operator Math: Chemical Feed & Chlorine Dose 11.5 Full-Length Practice & Test-Day Strategy

9.2 Revised Total Coliform Rule (RTCR)

Key Takeaways Explain This Topic AI

The Revised Total Coliform Rule (RTCR, effective 2016) treats total coliform as an indicator and responds to positive samples with repeat sampling and assessments rather than a fixed MCL.

A total coliform-positive (TC+) routine sample triggers 3 repeat samples within 24 hours, taken at the original tap and within 5 service connections upstream and downstream, plus increased routine monitoring next month.

Level 1 and Level 2 assessments find and fix sanitary defects; Level 1 is triggered by any TC+ or a monitoring/reporting failure, Level 2 by an E. coli MCL violation or repeated TC+.

An E. coli-positive result is an acute MCL violation requiring Tier 1 public notification within 24 hours and likely a boil-water advisory.

Last updated: August 2026

9.2 Revised Total Coliform Rule (RTCR)

Quick Answer: The Revised Total Coliform Rule (RTCR) , effective April 2016, replaced the 1989 Total Coliform Rule. It uses total coliform as an indicator of potential pathway contamination, not a direct health risk. Any total coliform-positive (TC+) routine sample triggers 3 repeat samples within 24 hours , taken at the original tap and within 5 service connections upstream and downstream . The rule shifts from a strict MCL to a find-and-fix approach: Level 1 and Level 2 assessments identify sanitary defects. An E. coli MCL violation is acute and requires Tier 1 public notification within 24 hours .

Why Coliform Instead of Pathogens

Pathogens like Giardia , Cryptosporidium , norovirus , and pathogenic E. coli are hard to grow in the lab, slow to detect, and present intermittently. Total coliform bacteria are easy to grow, survive longer in water, and die off faster than most pathogens — so their presence signals a sanitary defect that may also let pathogens in. The RTCR treats a coliform-positive as a trigger to investigate and fix , not as proof of disease.

Routine Sampling Schedule

Each system writes a sample siting plan approved by the state that identifies routine sample taps across the distribution system. Frequency depends on population and source type:

Large community systems typically sample monthly at multiple sites based on population.

Small groundwater systems serving ≤1,000 people may sample quarterly if sanitary surveys are clean.

Samples are collected from regular, representative distribution taps (not the treatment plant clearwell).

If a system fails to collect a routine sample, that itself is a monitoring violation.

TC+ Trigger: The 3-Repeat Rule

When a routine sample is total coliform-positive, the system must collect 3 repeat samples within 24 hours of being notified:

One at the original tap.

One within 5 service connections upstream.

One within 5 service connections downstream.

For groundwater systems, the rule also requires triggered source-water monitoring (a raw-water sample at each well in use) because a TC+ in distribution may indicate the source is compromised.

The system must also collect additional routine samples the following month — typically 3 times the normal monthly count — to confirm the system is back in control. This is called increased monitoring .

Assessments: Find and Fix

The RTCR replaces the old MCL (which counted the percentage of positive samples) with assessments that require the system to identify the sanitary defect and correct it.

Assessment Trigger Who Performs Scope

Level 1 Any TC+ routine, or a monitoring/reporting failure System operator Basic review of sampling, operations, and recent changes

Level 2 E. coli MCL violation; repeat Level 1 triggers; multiple TC+ in a 12-month period State or qualified party In-depth inspection of distribution, sources, treatment

Both assessments end with a corrective action — repair the break, flush the main, replace the tap, adjust chlorine — and a report to the state.

E. coli MCL = Acute Violation

The RTCR sets an E. coli MCL that is an acute violation. A system hits it when E. coli -positive results occur in any combination of routine or repeat samples (specific trigger patterns are defined in the rule). Because E. coli indicates fecal contamination, this is treated as an acute MCL violation requiring:

Tier 1 public notification within 24 hours (radio, TV, hand delivery, posting).

Consultation with the state.

Likely a boil-water advisory until the system is confirmed safe.

A Level 2 assessment.

A plain total coliform-positive (without E. coli) is not an acute violation — it triggers repeats and an assessment, but Tier 1 is not required.

Distribution Operator Role

For a Class I operator the RTCR is one of the most frequently tested rules because everything happens in distribution:

Pull routine samples on schedule from the approved siting plan.

Recognize a TC+ result and know to collect the 3 repeats within 24 hours in the right locations.

Maintain a chlorine residual (most systems) so the sampler can record a residual with each coliform sample.

Keep the sample siting plan current and rotate taps as required.

Exam Tip

Two numbers show up repeatedly on RTCR questions: 3 repeat samples and 24 hours . The 5-connections-upstream-and-downstream pattern is the spatial requirement. And remember: a TC+ alone is a Level 1 trigger; E. coli is the acute Tier 1 trigger.