Study guide
7.6 Refrigerants, Cooling Towers, and Specialized HVAC Technologies (Absorption, VRF, Chilled Beams)
AEE Certified Energy Manager CEM
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Energy and Sustainability Policies, Codes, and Standards
1.1 Federal and State Energy Policies, Decarbonization Targets, and ESG Reporting 1.2 Building Energy Codes: ASHRAE Standard 90.1, IECC, and Compliance Paths 1.3 Energy Management Systems: ISO 50001, ENERGY STAR Benchmarking, and Portfolio Manager
2 Chapter 2: Energy Rates, Tariffs, and Supply Options
2.1 Utility Rate Structures: Volumetric vs. Demand Charges, Time-of-Use (TOU), and Real-Time Pricing 2.2 Demand Charges, Ratchets, Peak Shaving, and Power Factor Penalties 2.3 Energy Procurement, Deregulated Markets, Supply Contracts, and Green Tariffs 2.4 Demand-Side Management, Load Curtailment, and Transportation Energy Efficiency
3 Chapter 3: Energy Audits and Instrumentation
3.1 Energy Audit Methodologies: ASHRAE Level I, II, and III Audit Scopes 3.2 Audit Instrumentation, Data Loggers, Metering Accuracy, and Safety (PPE) 3.3 Baseline Energy Data, Utility Bill Disaggregation, and ECM Identification 3.4 Energy Modeling, Simulation, Digital Tools, and Performance Indicators
4 Chapter 4: Energy Accounting and Economics
4.1 Energy & Power Units (kWh, kW, Therms, MMBtu, Joules) and Conversion Calculations 4.2 Financial Metrics: Simple Payback Period, Return on Investment (ROI), and LCCA 4.3 Time Value of Money: Net Present Value (NPV), Internal Rate of Return (IRR), and Escalation 4.4 Advanced Financial Evaluation: Annual Worth, SIR, Depreciation, and Interest Formulas
5 Chapter 5: Electrical Power Systems and Motors
5.1 Electrical Fundamentals: Single/Three-Phase Power, Apparent/Real/Reactive Power, and Power Factor 5.2 Electric Motors: Efficiency Classes, Loading Calculations, NEMA Premium, and Losses 5.3 Variable Frequency Drives (VFDs), Affinity Laws, and Electrical Harmonics
6 Chapter 6: Lighting Systems
6.1 Lighting Fundamentals: Photometric Quantities (Lumens, Lux, Foot-Candles, CRI, CCT) and Efficacy 6.2 Lighting Technologies & Retrofits: LED Systems, Fluorescent/HID Replacement, and LPD 6.3 Lighting Controls: Occupancy/Vacancy Sensors, Daylight Harvesting, Dimming, and Task Tuning
7 Chapter 7: HVAC Systems and Building Envelope
7.1 HVAC Fundamentals & Psychrometrics: Dry-Bulb, Wet-Bulb, Dew Point, Relative Humidity, and Enthalpy 7.2 Cooling and Heating Equipment: Chillers (COP, kW/ton, EER, SEER), Heat Pumps, and Boilers 7.3 Air and Water Distribution: AHUs, VAV vs. CAV, Pumping Systems, Fans, and Economizers 7.4 Building Envelope: Heat Transfer (U-factor, R-value, SHGC), Infiltration, and Thermal Insulation 7.5 Building Envelope Calculations: Degree-Days, Solar Heat Gain, and Passive Design 7.6 Refrigerants, Cooling Towers, and Specialized HVAC Technologies (Absorption, VRF, Chilled Beams)
8 Chapter 8: Building Automation, Controls, and Artificial Intelligence Systems
8.1 Building Automation Systems (BAS) Architecture, BACnet, Modbus, and DDC Loops 8.2 Energy Control Strategies: Temperature/Pressure Resets, Night Setback, and Deadbands 8.3 Fault Detection & Diagnostics (FDD), Energy Analytics, and AI Optimization 8.4 IoT, Cloud-Based BAS, Expert Systems, and Cyber-Security
9 Chapter 9: Energy Storage Systems
9.1 Battery Energy Storage Systems (BESS): Technologies, Capacity, Efficiency, and Safety 9.2 Thermal Energy Storage (TES): Chilled Water, Ice Storage, and Phase Change Materials 9.3 Storage Dispatch Strategies, Tariff Integration, Peak Shaving, and Microgrid Integration
10 Chapter 10: Boiler and Steam Systems
10.1 Boiler Fundamentals & Efficiency: Combustion Efficiency, Excess Air, and Stack Losses 10.2 Steam Distribution & Traps: Steam Trap Types, Failure Modes, Testing, and Insulation 10.3 Condensate Recovery, Boiler Blowdown Control, and Waste Heat Recovery
11 Chapter 11: Distributed Generation and Renewable Energy Systems
11.1 Solar Photovoltaic (PV) and Wind Energy Systems: Design, Inverters, and Capacity Factor 11.2 Combined Heat and Power (CHP) / Cogeneration: Thermal Efficiency and System Sizing 11.3 Grid Interconnection, Net Metering, Islanding, and Microgrid Resilience 11.4 Biomass, Geothermal, Hydropower, Solar Thermal, and Waste-to-Energy Systems
12 Chapter 12: Industrial Systems
12.1 Compressed Air Systems: Efficiency, Pressure Drop, Leak Management, and Receiver Storage 12.2 Industrial Process Heating, Cooling Towers, and Industrial Refrigeration 12.3 Production-Normalized Energy Metrics, Pumping System Optimization, and Process Integration
13 Chapter 13: Operations, Maintenance, and Commissioning
13.1 Preventive, Predictive, and Reliability-Centered Maintenance Strategies 13.2 Building Commissioning: Existing Building Commissioning (EBCx) & Retro-Commissioning (RCx) 13.3 Savings Persistence, Continuous Commissioning, Sensor Calibration, and Alarms 13.4 Quantifying O&M Losses: Compressed Air Leaks, Steam Traps, Boiler Scale, and Group Relamping 13.5 CMMS, Water Treatment, and Human Behavior in Energy Management
14 Chapter 14: Energy Savings Performance Contracting and Measurement & Verification
14.1 Energy Savings Performance Contracting (ESPC), ESCO Roles, and Financing Models 14.2 Measurement and Verification (M&V): IPMVP Options A, B, C, and D 14.3 Baselines, Weather Normalization, Non-Routine Adjustments, and M&V Reporting
7.6 Refrigerants, Cooling Towers, and Specialized HVAC Technologies (Absorption, VRF, Chilled Beams)
Key Takeaways Explain This Topic AI
Refrigerant selection now balances performance, GWP, and ASHRAE 34 flammability/toxicity class under the AIM Act HFC phase-down (~85% by 2036).
Cooling tower performance is governed by range (hot-in minus cold-out) and approach (cold-out minus wet-bulb); optimizing the chiller-tower trade-off is a classic CEM analysis.
Absorption chillers are heat-driven, with single-effect COP ~0.6–0.8 and double-effect ~1.0–1.2; they are most economical when waste heat or surplus steam is available.
VRF and chilled-beam systems offer high part-load and radiant efficiency but require careful design of refrigerant charge and condensation control.
Last updated: July 2026
Refrigerants, Cooling Towers, and Specialized HVAC Technologies
Beyond the core vapor-compression chiller and air-distribution systems, the CEM exam tests several specialized HVAC technologies that drive both energy use and regulatory compliance. This section covers refrigerant regulations and selection, cooling-tower performance, absorption chillers, variable refrigerant flow (VRF) systems, and chilled beams—technologies that appear throughout the HVAC Systems and Building Envelope domain.
Refrigerants and Global Warming Potential (GWP)
A refrigerant is the working fluid in a vapor-compression cycle, absorbing heat at the evaporator and rejecting it at the condenser. Historically, CFCs and HCFCs (e.g., R-22) were phased out under the Montreal Protocol for ozone depletion. Today's fleet relies heavily on HFCs, which are ozone-safe but have high Global Warming Potential (GWP). GWP measures how much heat a greenhouse gas traps relative to CO2 over 100 years; CO2 has a GWP of 1.
Common high-GWP HFCs include R-410A (GWP ≈ 2,088) and R-134a (GWP ≈ 1,430). Under the Kigali Amendment to the Montreal Protocol and the U.S. AIM (American Innovation and Manufacturing) Act, HFCs are being phased down roughly 85% by 2036. The industry is transitioning to low-GWP hydrofluoroolefins (HFOs) and HFC/HFO blends, including:
R-1234ze(E) — GWP ≈ 1, used in centrifugal chillers and as a foam-blowing agent.
R-1233zd(E) — GWP ≈ 1, a low-pressure refrigerant for centrifugal chillers.
R-32 — GWP ≈ 675, a lower-GWP HFC used in residential and light-commercial split systems.
ASHRAE Standard 34 classifies refrigerants by toxicity (A = lower, B = higher) and flammability (1 = no flame propagation, 2L = lower flammability, 2 = flammable, 3 = higher flammability). Most modern low-GWP refrigerants carry a 2L flammability classification, requiring equipment and installation adjustments. Refrigerant leak detection is also an energy issue—leaks degrade chiller capacity and efficiency over time.
Cooling Towers
A cooling tower rejects condenser heat from a water-cooled chiller through evaporative cooling. A portion of the recirculating condenser water is evaporated, carrying away latent heat; the rest is cooled and returned to the chiller. Two performance metrics dominate:
Range = hot water temperature in − cold water temperature out (the degrees the tower cools the water).
Approach = cold water temperature out − ambient wet-bulb temperature (how close the tower gets to the theoretical limit).
The wet-bulb temperature sets the floor for the cold-water temperature; a tighter (smaller) approach requires more tower fan energy and/or a larger tower. Energy managers optimize the trade-off between chiller kW/ton (improved by colder condenser water) and tower fan kW (increased by a tighter approach). Cycling tower fans or using two-speed/VFD fans allows the tower to match part-load conditions efficiently.
Water management is equally important. Cycles of concentration compare the dissolved solids in the recirculating water to the makeup water; higher cycles reduce water consumption but increase scaling/fouling risk. Drift eliminators reduce water (and chemical) loss. Unmanaged towers risk Legionella growth and scale formation on condenser tubes, both of which raise condensing pressure and chiller energy use.
Absorption Chillers
An absorption chiller uses a heat source (steam, hot water, direct gas firing, or waste heat) instead of a mechanical compressor to drive the refrigeration cycle. The working pair is typically lithium bromide (LiBr) and water, where LiBr is the absorbent and water is the refrigerant; ammonia-water is used for low-temperature industrial applications.
Because the cycle is heat-driven, the COP (defined as cooling output ÷ heat input, not electricity) is far lower than a vapor-compression chiller:
Single-effect (low-grade steam or hot water): COP ≈ 0.6–0.8.
Double-effect (higher-pressure steam or direct-fired): COP ≈ 1.0–1.2.
Direct gas-fired : COP ≈ 1.2.
An absorption chiller makes economic sense when free or low-cost heat is available—engine jacket/exhaust heat from a CHP system, process waste heat, solar thermal, or surplus steam. They consume very little electricity (mainly small solution pumps), shifting load from peak electrical demand to thermal input.
Variable Refrigerant Flow (VRF) Systems
VRF systems use an inverter-driven outdoor unit connected to multiple indoor fan-coil units via refrigerant piping, modulating the refrigerant flow to each zone. Key advantages include simultaneous heating and cooling (with heat-recovery VRF, one zone can be heated while another is cooled by transferring heat between them), high part-load efficiency from inverter compressors, and long refrigerant runs that reduce ductwork. They are common in hotels, multifamily, and office buildings. The CEM should weigh their high installed cost and refrigerant charge against their efficiency and zoning flexibility.
Chilled Beams
Chilled beams are radiant terminal devices that cool primarily by absorbing heat from the room rather than by blowing cold air. Passive chilled beams rely on natural convection; active chilled beams mix primary ventilation air with induced room air for higher capacity. They use warmer chilled water (typically 55–58°F) to avoid condensation, which raises chiller efficiency. Their low fan energy and quiet operation make them attractive for perimeter zones, but condensation management and fresh-air delivery (a separate dedicated outdoor air system is required) must be designed correctly.