Study guide

2.3 Article 100 Definitions You Must Know Cold

Alaska Journeyman Electrician Study Guide Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Alaska Certificates of Fitness, Law & Exam Logistics

1.1 The Alaska Certificate of Fitness System 1.2 Journeyman Eligibility: 8,000 Hours and How Alaska Counts Them 1.3 Trainee, Residential Wireman, Lineman, Provisional & Reciprocal Certificates 1.4 The Journeyman Examination: Format, Scheduling, Open-Book Rules & Retakes 1.5 Adopted Codes, Fees, Renewal, Inspection & Enforcement

2 Chapter 2: Using the 2020 NEC

2.1 Article 90: Purpose, Scope, Arrangement & Enforcement 2.2 Navigating the Code Book: Structure, Index & Tabbing Strategy 2.3 Article 100 Definitions You Must Know Cold 2.4 Electrical Theory for the Exam: Ohm's Law, Power & Three-Phase

3 Chapter 3: General Requirements — Article 110

3.1 Approval, Listing, Interrupting Rating & Terminations 3.2 Temperature Limitations of Terminations — 110.14(C) 3.3 Working Space, Access, Egress & Illumination — 110.26(A) through (D) 3.4 Dedicated Equipment Space, Guarding & Over-1000-Volt Installations

4 Chapter 4: Conductors and Ampacity — Article 310

4.1 Conductor Types, Insulation Markings & Table 310.16 4.2 Ambient Temperature Correction and Alaska's Cold 4.3 Adjustment for More Than Three Current-Carrying Conductors 4.4 Putting It Together: Full Conductor-Sizing Problems 4.5 Parallel Conductors, Dwelling Service Sizing & Conditions of Use

5 Chapter 5: Wiring Methods and Materials — NEC Chapter 3

5.1 Article 300 General Requirements and Underground Cover 5.2 Thermal Movement: Expansion Fittings and Table 352.44 5.3 Boxes and Enclosures: Box Fill and Pull Box Sizing 5.4 Cable Assemblies: NM, MC, AC, SE, UF and TC 5.5 Raceways: RMC, IMC, EMT, FMC, LFMC, PVC and ENT 5.6 Conduit Fill: Chapter 9 Tables and Annex C 5.7 Cable Trays, Wireways, Busways, Gutters and Surface Raceways

6 Chapter 6: Branch Circuits and Feeders

6.1 Branch-Circuit Ratings, Conductor Sizing & Multiwire Circuits 6.2 Required Outlets and Receptacle Spacing in Dwellings 6.3 GFCI Protection — Article 210.8 6.4 AFCI Protection and Receptacle Requirements 6.5 Feeders and Outside Branch Circuits — Articles 215 and 225 6.6 Grounded Conductor Identification, Switches & Panelboards

7 Chapter 7: Overcurrent Protection — Articles 240 and 242

7.1 Article 240 Fundamentals: Ratings, Locations & Conductor Protection 7.2 Feeder Tap Rules — 240.21(B) 7.3 Transformer Secondary Conductors — 240.21(C) 7.4 Fuses, Circuit Breakers, Series Ratings & Article 242 Surge Protection

8 Chapter 8: Services and Load Calculations

8.1 Service Conductors, Clearances and Service Equipment 8.2 Service Disconnects, the 2020 Rule Change, SPDs and Service GFPE 8.3 Article 220 Part II: General Lighting, Receptacles and Demand Factors 8.4 The Standard Dwelling Calculation — Article 220 Part III 8.5 Optional Dwelling and Multifamily Calculations 8.6 Commercial and Industrial Load Calculations 8.7 Neutral Load Calculations and Harmonics — 220.61

9 Chapter 9: Grounding and Bonding — Article 250

9.1 System Grounding, 250.24 and the Main Bonding Jumper 9.2 The Grounding Electrode System — 250.50 through 250.53 9.3 Grounding Electrode Conductor Sizing and Installation 9.4 Bonding: Services, Metal Piping, Structural Metal and Other Systems 9.5 Equipment Grounding Conductors: Types, Sizing and Continuity 9.6 Separately Derived Systems and Separate Buildings 9.7 Ground-Fault Protection of Equipment and Grounding of Specific Equipment

10 Chapter 10: Equipment for General Use — NEC Chapter 4

10.1 Flexible Cords, Cables and Fixture Wires 10.2 Switches, Receptacles and Industrial Control Panels 10.3 Luminaires, Lampholders and Recessed Installations 10.4 Appliances and Fixed Electric Space Heating 10.5 Deicing, Snow Melting, Pipeline and Vessel Heating 10.6 Motors Part I: Full-Load Current, Conductors and Overload Protection 10.7 Motors Part II: Short-Circuit Protection, Controllers, Disconnects and HVAC

11 Chapter 11: Transformers, Generators and Special Occupancies

11.1 Transformers — Article 450 11.2 Generators, Storage Batteries and Energy Storage Systems 11.3 Hazardous (Classified) Locations — Articles 500 through 506 11.4 Garages, Hangars, Fuel Dispensing, Bulk Storage and Spray Application 11.5 Health Care Facilities — Article 517 11.6 Agricultural Buildings, Manufactured Homes, RV Parks and Marinas 11.7 Assembly, Theaters, Carnivals, Temporary Installations and Pools

12 Chapter 12: Special Equipment, Special Conditions and Exam Strategy

12.1 Signs, Cranes, Elevators, Electric Vehicle Charging and Welders 12.2 Solar Photovoltaic, Interconnection and Stand-Alone Systems 12.3 Wind Electric Systems and Fire Pumps 12.4 Emergency, Legally Required Standby, Optional Standby and COPS 12.5 Class 1, 2 and 3 Circuits, Fire Alarm, Optical Fiber and Communications 12.6 Cold-Climate Practice in Alaska: Code Basis and Engineering Judgment 12.7 Exam-Day Strategy: Navigation, Calculation Workflow and Time Management

2.3 Article 100 Definitions You Must Know Cold

Key Takeaways Explain This Topic AI

Article 100 definitions govern wherever the defined term appears in the Code, unless a specific article supplies its own modified definition for its scope.

Accessible (equipment) means admitting close approach and not guarded by locked doors, elevation, or other effective means; Readily Accessible adds that reaching it must not require ladders, climbing over obstacles, or removing barriers.

Ampacity is the maximum current a conductor can carry continuously under the conditions of use without exceeding its temperature rating.

A Feeder runs between the service equipment or other supply source and the final branch-circuit overcurrent device; the Branch Circuit runs from that final overcurrent device to the outlets.

The 2020 NEC added the defined terms Reconditioned and Retrofit Kit, and revised the definitions of Bonding Jumper, Supply-Side Bonding Jumper, and Overcurrent.

Last updated: August 2026

Why Definitions Decide Questions

NEC terms are legal terms. "Accessible" in the Code does not mean what it means in ordinary speech, and a question that turns on the difference between accessible and readily accessible has one right answer regardless of trade habit. Article 100 definitions apply wherever the term appears throughout the Code; where an individual article needs a narrower meaning for its own scope, it supplies its own definition in its .2 section.

Accessibility — Three Distinct Terms

Term Definition (paraphrased from Article 100) Typical application

Accessible (as applied to wiring methods) Capable of being removed or exposed without damaging the building structure or finish, or not permanently closed in by the structure or finish Junction box above a lay-in ceiling; splices must remain accessible per 314.29

Accessible (as applied to equipment) Admitting close approach; not guarded by locked doors, elevation, or other effective means Equipment reachable with a ladder

Readily Accessible Capable of being reached quickly for operation, renewal, or inspection without requiring those to whom ready access is requisite to take actions such as to use tools (other than keys), to climb over or under, to remove obstacles, or to resort to portable ladders Service disconnect (230.70), overcurrent devices (240.24)

The 2020 definition of Readily Accessible contains a parenthetical that matters: tools other than keys . A locked door alone does not defeat ready accessibility where the lock is under the control of the people who need access — an informational note addresses locks under controlled or supervised industrial conditions. But an eight-foot mounting height requiring a portable ladder does defeat it.

Circuit Vocabulary

Branch Circuit. The circuit conductors between the final overcurrent device protecting the circuit and the outlet(s).

Appliance branch circuit — supplies outlets to which appliances are connected, with no permanently connected luminaires that are not part of an appliance.

General-purpose branch circuit — supplies two or more receptacles or outlets for lighting and appliances.

Individual branch circuit — supplies only one utilization equipment.

Multiwire branch circuit — two or more ungrounded conductors with a voltage between them, and a grounded conductor with equal voltage between it and each ungrounded conductor, that is connected to the neutral or grounded conductor of the system.

Feeder. All circuit conductors between the service equipment, the source of a separately derived system, or other power-supply source and the final branch-circuit overcurrent device .

Outlet. A point on the wiring system at which current is taken to supply utilization equipment. Note that an outlet is not the same thing as a receptacle — a hardwired luminaire is at an outlet.

Receptacle. A contact device installed at the outlet for the connection of an attachment plug or for the direct connection of electrical utilization equipment designed to mate with the corresponding contact device. A single receptacle is a single contact device with no other contact device on the same yoke or strap; a multiple receptacle has two or more.

Device. A unit of an electrical system, other than a conductor, that carries or controls electric energy as its principal function.

Ampacity and Related Terms

Ampacity. The maximum current, in amperes, that a conductor can carry continuously under the conditions of use without exceeding its temperature rating.

Continuous Load. A load where the maximum current is expected to continue for three hours or more . This drives the 125 percent rule in 210.19(A), 210.20(A), 215.2(A) and 215.3.

Overcurrent. Any current in excess of the rated current of equipment or the ampacity of a conductor — it may result from overload, short circuit, or ground fault.

Overload. Operation of equipment in excess of normal full-load rating, or of a conductor in excess of rated ampacity, which, when it persists for a sufficient time, would cause damage or dangerous overheating. A fault such as a short circuit or ground fault is not an overload.

Grounding and Bonding Vocabulary

These six terms are frequently swapped in distractor options:

  • Term Meaning
  • Grounded Conductor A system or circuit conductor that is intentionally grounded — usually the neutral
  • Grounding Electrode A conducting object through which a direct connection to earth is established

Grounding Electrode Conductor (GEC) A conductor used to connect the system grounded conductor or the equipment to a grounding electrode or to a point on the grounding electrode system

Equipment Grounding Conductor (EGC) The conductive path installed to connect normally non-current-carrying metal parts of equipment together and to the system grounded conductor or the GEC, or both

Bonding Jumper, Main (MBJ) The connection between the grounded circuit conductor and the equipment grounding conductor at the service

Bonding Jumper, System (SBJ) The connection between the grounded circuit conductor and the supply-side bonding jumper, the equipment grounding conductor, or both, at a separately derived system

Two more from the same family: an Equipment Bonding Jumper is the connection between two or more portions of the equipment grounding conductor, and a Supply-Side Bonding Jumper is a conductor installed on the supply side of a service, or within a service equipment enclosure, or for a separately derived system, that ensures the required electrical conductivity between metal parts required to be electrically connected.

Service Vocabulary

Service. The conductors and equipment connecting the serving utility to the wiring system of the premises served.

Service Point. The point of connection between the facilities of the serving utility and the premises wiring. Everything on the utility side is outside the NEC per 90.2(B)(5).

Service Conductors. The conductors from the service point to the service disconnecting means.

Service Equipment. The necessary equipment, usually one or more circuit breakers or switches and fuses and their accessories, connected to the load end of service conductors and intended to constitute the main control and cutoff of the supply.

Separately Derived System. An electrical source, other than a service, having no direct connection to circuit conductors of any other source other than through grounding and bonding connections. A transformer secondary and most generators qualify; a transfer switch that keeps the neutral solidly connected does not.

New and Revised in the 2020 Edition

Reconditioned. Electromechanical systems, equipment, apparatus, or components that are restored to operating conditions — the 2020 Code added this term and used it in many articles to restrict reconditioning of specific equipment.

Retrofit Kit. A general term for a complete subassembly of parts and devices for field conversion of utilization equipment.

Overcurrent Protective Device, Branch-Circuit and Supplementary — the definitions were relocated to Article 100 in 2020.

Qualified Person

One who has skills and knowledge related to the construction and operation of the electrical equipment and installations and has received safety training to recognize and avoid the hazards involved. Both halves are required — experience alone does not make a person qualified under the Code definition.