2.4 Electrical Theory for the Exam: Ohm's Law, Power & Three-Phase

Alaska Journeyman Electrician Study Guide Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Alaska Certificates of Fitness, Law & Exam Logistics

1.1 The Alaska Certificate of Fitness System 1.2 Journeyman Eligibility: 8,000 Hours and How Alaska Counts Them 1.3 Trainee, Residential Wireman, Lineman, Provisional & Reciprocal Certificates 1.4 The Journeyman Examination: Format, Scheduling, Open-Book Rules & Retakes 1.5 Adopted Codes, Fees, Renewal, Inspection & Enforcement

2 Chapter 2: Using the 2020 NEC

2.1 Article 90: Purpose, Scope, Arrangement & Enforcement 2.2 Navigating the Code Book: Structure, Index & Tabbing Strategy 2.3 Article 100 Definitions You Must Know Cold 2.4 Electrical Theory for the Exam: Ohm's Law, Power & Three-Phase

3 Chapter 3: General Requirements — Article 110

3.1 Approval, Listing, Interrupting Rating & Terminations 3.2 Temperature Limitations of Terminations — 110.14(C) 3.3 Working Space, Access, Egress & Illumination — 110.26(A) through (D) 3.4 Dedicated Equipment Space, Guarding & Over-1000-Volt Installations

4 Chapter 4: Conductors and Ampacity — Article 310

4.1 Conductor Types, Insulation Markings & Table 310.16 4.2 Ambient Temperature Correction and Alaska's Cold 4.3 Adjustment for More Than Three Current-Carrying Conductors 4.4 Putting It Together: Full Conductor-Sizing Problems 4.5 Parallel Conductors, Dwelling Service Sizing & Conditions of Use

5 Chapter 5: Wiring Methods and Materials — NEC Chapter 3

5.1 Article 300 General Requirements and Underground Cover 5.2 Thermal Movement: Expansion Fittings and Table 352.44 5.3 Boxes and Enclosures: Box Fill and Pull Box Sizing 5.4 Cable Assemblies: NM, MC, AC, SE, UF and TC 5.5 Raceways: RMC, IMC, EMT, FMC, LFMC, PVC and ENT 5.6 Conduit Fill: Chapter 9 Tables and Annex C 5.7 Cable Trays, Wireways, Busways, Gutters and Surface Raceways

6 Chapter 6: Branch Circuits and Feeders

6.1 Branch-Circuit Ratings, Conductor Sizing & Multiwire Circuits 6.2 Required Outlets and Receptacle Spacing in Dwellings 6.3 GFCI Protection — Article 210.8 6.4 AFCI Protection and Receptacle Requirements 6.5 Feeders and Outside Branch Circuits — Articles 215 and 225 6.6 Grounded Conductor Identification, Switches & Panelboards

7 Chapter 7: Overcurrent Protection — Articles 240 and 242

7.1 Article 240 Fundamentals: Ratings, Locations & Conductor Protection 7.2 Feeder Tap Rules — 240.21(B) 7.3 Transformer Secondary Conductors — 240.21(C) 7.4 Fuses, Circuit Breakers, Series Ratings & Article 242 Surge Protection

8 Chapter 8: Services and Load Calculations

8.1 Service Conductors, Clearances and Service Equipment 8.2 Service Disconnects, the 2020 Rule Change, SPDs and Service GFPE 8.3 Article 220 Part II: General Lighting, Receptacles and Demand Factors 8.4 The Standard Dwelling Calculation — Article 220 Part III 8.5 Optional Dwelling and Multifamily Calculations 8.6 Commercial and Industrial Load Calculations 8.7 Neutral Load Calculations and Harmonics — 220.61

9 Chapter 9: Grounding and Bonding — Article 250

9.1 System Grounding, 250.24 and the Main Bonding Jumper 9.2 The Grounding Electrode System — 250.50 through 250.53 9.3 Grounding Electrode Conductor Sizing and Installation 9.4 Bonding: Services, Metal Piping, Structural Metal and Other Systems 9.5 Equipment Grounding Conductors: Types, Sizing and Continuity 9.6 Separately Derived Systems and Separate Buildings 9.7 Ground-Fault Protection of Equipment and Grounding of Specific Equipment

10 Chapter 10: Equipment for General Use — NEC Chapter 4

10.1 Flexible Cords, Cables and Fixture Wires 10.2 Switches, Receptacles and Industrial Control Panels 10.3 Luminaires, Lampholders and Recessed Installations 10.4 Appliances and Fixed Electric Space Heating 10.5 Deicing, Snow Melting, Pipeline and Vessel Heating 10.6 Motors Part I: Full-Load Current, Conductors and Overload Protection 10.7 Motors Part II: Short-Circuit Protection, Controllers, Disconnects and HVAC

11 Chapter 11: Transformers, Generators and Special Occupancies

11.1 Transformers — Article 450 11.2 Generators, Storage Batteries and Energy Storage Systems 11.3 Hazardous (Classified) Locations — Articles 500 through 506 11.4 Garages, Hangars, Fuel Dispensing, Bulk Storage and Spray Application 11.5 Health Care Facilities — Article 517 11.6 Agricultural Buildings, Manufactured Homes, RV Parks and Marinas 11.7 Assembly, Theaters, Carnivals, Temporary Installations and Pools

12 Chapter 12: Special Equipment, Special Conditions and Exam Strategy

12.1 Signs, Cranes, Elevators, Electric Vehicle Charging and Welders 12.2 Solar Photovoltaic, Interconnection and Stand-Alone Systems 12.3 Wind Electric Systems and Fire Pumps 12.4 Emergency, Legally Required Standby, Optional Standby and COPS 12.5 Class 1, 2 and 3 Circuits, Fire Alarm, Optical Fiber and Communications 12.6 Cold-Climate Practice in Alaska: Code Basis and Engineering Judgment 12.7 Exam-Day Strategy: Navigation, Calculation Workflow and Time Management

2.4 Electrical Theory for the Exam: Ohm's Law, Power & Three-Phase

Key Takeaways Explain This Topic AI

Ohm's law and the power formulas cover most single-phase theory items: E = I x R and P = E x I, with P = I squared x R for conductor heating.

Single-phase apparent power is VA = E x I; three-phase apparent power is VA = 1.732 x E-line x I-line, so a three-phase line current is kVA x 1000 divided by (1.732 x line voltage).

Power factor is real power divided by apparent power, so line current rises as power factor falls for the same kilowatt load.

In a balanced wye system, line voltage equals 1.732 times phase voltage while line current equals phase current; in a delta system, line current equals 1.732 times phase current while line voltage equals phase voltage.

The single-phase voltage-drop formula is VD = 2 x K x I x L divided by CM; the three-phase version substitutes 1.732 for the 2, using K of about 12.9 for copper and 21.2 for aluminum.

Last updated: August 2026

The Formulas Worth Owning

The NEC contains rules, not physics. Theory questions and the arithmetic inside code questions come from a short list of relationships. Write these on the inside cover of your working notes and drill until they are automatic.

Ohm's Law and Power

  • Quantity Formula
  • Voltage E = I x R
  • Current I = E / R
  • Resistance R = E / I
  • Power (resistive) P = E x I
  • Power from current and resistance P = I squared x R
  • Power from voltage and resistance P = E squared / R

P = I squared x R is the one that explains the Code. Conductor heating rises with the square of current, which is why ampacity tables exist, why bundling forces adjustment, and why a 20 percent overload is far worse than it sounds.

  • Single-Phase Current I = VA / E (apparent power)
  • I = (kW x 1000) / (E x PF) (real power with power factor)

A 9.6 kW, 240 V single-phase resistance heater at unity power factor draws 9600 / 240 = 40 A .

  • Three-Phase Current I(line) = VA / (1.732 x E-line)
  • I(line) = (kW x 1000) / (1.732 x E-line x PF)

The 1.732 is the square root of 3. A 30 kW, 480 V three-phase heater at unity power factor draws 30,000 / (1.732 x 480) = 30,000 / 831.4 = 36.1 A .

A 75 kVA, 208 V three-phase transformer secondary delivers 75,000 / (1.732 x 208) = 75,000 / 360.3 = 208.2 A . That number is worth remembering as a sanity check: a 75 kVA 208Y/120 V transformer is roughly a 200 A secondary.

Power Factor PF = P (watts) / S (volt-amperes)

Power factor is the ratio of real power doing work to apparent power the system must carry. Purely resistive loads — heaters, incandescent lamps — run at unity. Motors and transformers run lagging because magnetizing current does no work.

The practical consequence is that current increases as power factor falls . A 20 kW three-phase 480 V load at unity PF draws 24.1 A. The same 20 kW at 0.80 PF draws 20,000 / (1.732 x 480 x 0.80) = 30.1 A — the conductors, raceway, and overcurrent device must all be sized for the larger figure.

The power triangle relates the three: apparent power S in kVA is the hypotenuse, real power P in kW is the horizontal leg, and reactive power Q in kVAR is the vertical leg, with S squared = P squared + Q squared.

Wye and Delta Relationships

These two sets of relationships are frequently reversed in distractor answers:

  • System Voltage Current
  • Wye (star) E-line = 1.732 x E-phase I-line = I-phase
  • Delta E-line = E-phase I-line = 1.732 x I-phase

A 208Y/120 V system is a wye: 120 V phase-to-neutral, 120 x 1.732 = 208 V phase-to-phase. A 480Y/277 V system is the same relationship scaled: 277 x 1.732 = 480 V.

The high-leg delta. A 240/120 V three-phase four-wire delta has a centre tap on one winding, giving 120 V to neutral on two phases and 208 V to neutral on the third — the "high leg" or "wild leg." 110.15 requires the high leg to be durably and permanently marked by an orange outer finish or other effective means at each point where a connection is made if the grounded conductor is present, and 408.3(E)(1) requires it to be phase B in switchboards and panelboards. Never land a 120 V load on the high leg.

Voltage Drop

Voltage drop is a performance issue, not a mandatory rule for most conductors. The 3 percent branch-circuit and 5 percent total figures live in Informational Notes to 210.19(A) and 215.2(A), which 90.5(C) makes non-enforceable. Some specific rules do mandate voltage-drop limits — 647.4(D) for sensitive electronic equipment, 695.7 for fire pumps, and Article 690 for PV — but for ordinary branch circuits and feeders the 3/5 figures are recommendations.

  • The Circular-Mil Formulas Single-phase: VD = (2 x K x I x L) / CM
  • Three-phase: VD = (1.732 x K x I x L) / CM

Solve for wire size:

  • Single-phase: CM = (2 x K x I x L) / VD
  • Three-phase: CM = (1.732 x K x I x L) / VD

Where K is the resistivity constant — approximately 12.9 for copper and 21.2 for aluminum — I is load current in amperes, L is the one-way length in feet, CM is the conductor's circular-mil area from Chapter 9, Table 8 , and VD is the voltage drop in volts. The 2 in the single-phase formula accounts for the out-and-back path, which is why L is one-way.

Useful circular-mil values from Table 8: 14 AWG = 4,110; 12 AWG = 6,530; 10 AWG = 10,380; 8 AWG = 16,510; 6 AWG = 26,240; 4 AWG = 41,740; 3 AWG = 52,620; 2 AWG = 66,360; 1 AWG = 83,690; 1/0 = 105,600.

Worked Example 1 — Find the Drop

A 240 V single-phase circuit carries 30 A to a load 150 feet away on 10 AWG copper. VD = (2 x 12.9 x 30 x 150) / 10,380

  • = 116,100 / 10,380
  • = 11.19 V

That is 11.19 / 240 = 4.7 percent — beyond the 3 percent recommendation, so upsize if performance matters.

Worked Example 2 — Find the Wire Size

A 480 V three-phase load draws 50 A over 400 feet, and you want to hold the drop to 3 percent (0.03 x 480 = 14.4 V) using copper. CM = (1.732 x 12.9 x 50 x 400) / 14.4

  • = 446,856 / 14.4
  • = 31,032 circular mils

From Table 8, 6 AWG is 26,240 CM — too small. 4 AWG at 41,740 CM is the smallest conductor that satisfies the target. Always verify separately that the chosen conductor also meets its ampacity requirement; voltage drop can only drive you larger, never smaller.