3.3 Working Space, Access, Egress & Illumination — 110.26(A) through (D)
Alaska Journeyman Electrician Study Guide Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Alaska Certificates of Fitness, Law & Exam Logistics
1.1 The Alaska Certificate of Fitness System 1.2 Journeyman Eligibility: 8,000 Hours and How Alaska Counts Them 1.3 Trainee, Residential Wireman, Lineman, Provisional & Reciprocal Certificates 1.4 The Journeyman Examination: Format, Scheduling, Open-Book Rules & Retakes 1.5 Adopted Codes, Fees, Renewal, Inspection & Enforcement
2 Chapter 2: Using the 2020 NEC
2.1 Article 90: Purpose, Scope, Arrangement & Enforcement 2.2 Navigating the Code Book: Structure, Index & Tabbing Strategy 2.3 Article 100 Definitions You Must Know Cold 2.4 Electrical Theory for the Exam: Ohm's Law, Power & Three-Phase
3 Chapter 3: General Requirements — Article 110
3.1 Approval, Listing, Interrupting Rating & Terminations 3.2 Temperature Limitations of Terminations — 110.14(C) 3.3 Working Space, Access, Egress & Illumination — 110.26(A) through (D) 3.4 Dedicated Equipment Space, Guarding & Over-1000-Volt Installations
4 Chapter 4: Conductors and Ampacity — Article 310
4.1 Conductor Types, Insulation Markings & Table 310.16 4.2 Ambient Temperature Correction and Alaska's Cold 4.3 Adjustment for More Than Three Current-Carrying Conductors 4.4 Putting It Together: Full Conductor-Sizing Problems 4.5 Parallel Conductors, Dwelling Service Sizing & Conditions of Use
5 Chapter 5: Wiring Methods and Materials — NEC Chapter 3
5.1 Article 300 General Requirements and Underground Cover 5.2 Thermal Movement: Expansion Fittings and Table 352.44 5.3 Boxes and Enclosures: Box Fill and Pull Box Sizing 5.4 Cable Assemblies: NM, MC, AC, SE, UF and TC 5.5 Raceways: RMC, IMC, EMT, FMC, LFMC, PVC and ENT 5.6 Conduit Fill: Chapter 9 Tables and Annex C 5.7 Cable Trays, Wireways, Busways, Gutters and Surface Raceways
6 Chapter 6: Branch Circuits and Feeders
6.1 Branch-Circuit Ratings, Conductor Sizing & Multiwire Circuits 6.2 Required Outlets and Receptacle Spacing in Dwellings 6.3 GFCI Protection — Article 210.8 6.4 AFCI Protection and Receptacle Requirements 6.5 Feeders and Outside Branch Circuits — Articles 215 and 225 6.6 Grounded Conductor Identification, Switches & Panelboards
7 Chapter 7: Overcurrent Protection — Articles 240 and 242
7.1 Article 240 Fundamentals: Ratings, Locations & Conductor Protection 7.2 Feeder Tap Rules — 240.21(B) 7.3 Transformer Secondary Conductors — 240.21(C) 7.4 Fuses, Circuit Breakers, Series Ratings & Article 242 Surge Protection
8 Chapter 8: Services and Load Calculations
8.1 Service Conductors, Clearances and Service Equipment 8.2 Service Disconnects, the 2020 Rule Change, SPDs and Service GFPE 8.3 Article 220 Part II: General Lighting, Receptacles and Demand Factors 8.4 The Standard Dwelling Calculation — Article 220 Part III 8.5 Optional Dwelling and Multifamily Calculations 8.6 Commercial and Industrial Load Calculations 8.7 Neutral Load Calculations and Harmonics — 220.61
9 Chapter 9: Grounding and Bonding — Article 250
9.1 System Grounding, 250.24 and the Main Bonding Jumper 9.2 The Grounding Electrode System — 250.50 through 250.53 9.3 Grounding Electrode Conductor Sizing and Installation 9.4 Bonding: Services, Metal Piping, Structural Metal and Other Systems 9.5 Equipment Grounding Conductors: Types, Sizing and Continuity 9.6 Separately Derived Systems and Separate Buildings 9.7 Ground-Fault Protection of Equipment and Grounding of Specific Equipment
10 Chapter 10: Equipment for General Use — NEC Chapter 4
10.1 Flexible Cords, Cables and Fixture Wires 10.2 Switches, Receptacles and Industrial Control Panels 10.3 Luminaires, Lampholders and Recessed Installations 10.4 Appliances and Fixed Electric Space Heating 10.5 Deicing, Snow Melting, Pipeline and Vessel Heating 10.6 Motors Part I: Full-Load Current, Conductors and Overload Protection 10.7 Motors Part II: Short-Circuit Protection, Controllers, Disconnects and HVAC
11 Chapter 11: Transformers, Generators and Special Occupancies
11.1 Transformers — Article 450 11.2 Generators, Storage Batteries and Energy Storage Systems 11.3 Hazardous (Classified) Locations — Articles 500 through 506 11.4 Garages, Hangars, Fuel Dispensing, Bulk Storage and Spray Application 11.5 Health Care Facilities — Article 517 11.6 Agricultural Buildings, Manufactured Homes, RV Parks and Marinas 11.7 Assembly, Theaters, Carnivals, Temporary Installations and Pools
12 Chapter 12: Special Equipment, Special Conditions and Exam Strategy
12.1 Signs, Cranes, Elevators, Electric Vehicle Charging and Welders 12.2 Solar Photovoltaic, Interconnection and Stand-Alone Systems 12.3 Wind Electric Systems and Fire Pumps 12.4 Emergency, Legally Required Standby, Optional Standby and COPS 12.5 Class 1, 2 and 3 Circuits, Fire Alarm, Optical Fiber and Communications 12.6 Cold-Climate Practice in Alaska: Code Basis and Engineering Judgment 12.7 Exam-Day Strategy: Navigation, Calculation Workflow and Time Management
3.3 Working Space, Access, Egress & Illumination — 110.26(A) through (D)
Key Takeaways Explain This Topic AI
Table 110.26(A)(1) sets minimum working space depth by nominal voltage to ground and by Condition 1, 2, or 3, ranging from 3 feet to 4 feet at 0 to 150 volts and from 3 feet to 4 feet at 151 to 600 volts depending on condition.
NEC 110.26(A)(2) requires working space width of 30 inches or the width of the equipment, whichever is greater, and the space must permit at least a 90-degree opening of equipment doors.
NEC 110.26(A)(3) requires working space height of 6.5 feet or the height of the equipment, whichever is greater.
NEC 110.26(C)(2) requires at least one entrance of sufficient area for equipment rated 1200 amperes or more and over 6 feet wide, and 110.26(C)(3) requires personnel doors within 25 feet of the working space for equipment rated 800 amperes or more to open in the direction of egress with listed panic hardware.
NEC 110.26(D) requires illumination for working spaces about service equipment, switchboards, switchgear, panelboards, and motor control centers in other than dwelling units, and prohibits control of that lighting by automatic means only.
Last updated: August 2026
The Purpose Statement
110.26 opens by stating that access and working space shall be provided and maintained about all electrical equipment to permit ready and safe operation and maintenance. The word maintained is deliberate — a compliant installation that later becomes a storage area is a violation.
110.26(A) applies where equipment is likely to require examination, adjustment, servicing, or maintenance while energized . A junction box does not require working space; a panelboard does.
Depth — Table 110.26(A)(1) and the Three Conditions
Depth is measured from the exposed live parts , or from the enclosure front or opening if the live parts are enclosed. The required depth depends on the nominal voltage to ground and on what is on the opposite side of the working space:
Condition What is on the other side
Condition 1 Exposed live parts on one side and no live or grounded parts on the other side; or exposed live parts on both sides effectively guarded by suitable wood or other insulating material
Condition 2 Exposed live parts on one side and grounded parts on the other side. Concrete, brick, or tile walls are considered grounded.
Condition 3 Exposed live parts on both sides of the working space, not guarded
- Nominal voltage to ground Condition 1 Condition 2 Condition 3
- 0–150 V 3 ft 3 ft 3 ft
- 151–600 V 3 ft 3.5 ft 4 ft
- 601–1000 V 3 ft 4 ft 5 ft
The critical detail is the Condition 2 definition : concrete, brick, or tile walls are considered grounded . A 480Y/277 V panelboard across a corridor from a concrete wall is Condition 2 at 151–600 V, requiring 3.5 feet , not 3 feet. Change the wall to painted gypsum board over wood studs and it becomes Condition 1 at 3 feet. Put a second energized panel opposite and it becomes Condition 3 at 4 feet.
Remember that the table is indexed on voltage to ground , not phase-to-phase voltage. A 480Y/277 V system is 277 V to ground and therefore sits in the 151–600 V row. A 480 V corner-grounded or ungrounded delta is 480 V to ground and also sits in that row. A 208Y/120 V panel is 120 V to ground and falls in the 0–150 V row, where all three conditions require 3 feet.
110.26(A)(1)(a) Dead-Front Assemblies. Working space is not required in the back or sides of assemblies such as dead-front switchboards or motor control centers where all connections and renewable or adjustable parts are accessible from locations other than the back or sides. Where rear access is required to work on de-energized parts on the back of enclosed equipment, a minimum horizontal working space of 30 inches shall be provided.
110.26(A)(1)(b) Low Voltage. By special permission, smaller spaces are permitted where all uninsulated parts operate at not greater than 30 V RMS, 42 V peak, or 60 V DC.
Width and Height
110.26(A)(2) Width. The width of the working space shall be the width of the equipment or 30 inches, whichever is greater . In all cases the working space shall permit at least a 90-degree opening of equipment doors or hinged panels. The space may be measured from left to right, from right to left, or be centered on the equipment — it does not need to be centered.
A 20-inch-wide panelboard requires 30 inches of clear width. A 42-inch-wide switchboard requires 42 inches.
110.26(A)(3) Height. The work space shall be clear and extend from the grade, floor, or platform to a height of 6.5 feet (2.0 m) or the height of the equipment, whichever is greater. Within the height and width of the working space, other equipment located above or below the electrical equipment shall be permitted to extend not more than 6 inches beyond the front of the equipment.
110.26(A)(4) Limited Access. Where equipment is installed in a space with limited access — above a suspended ceiling or in a crawl space — additional rules apply, including a minimum 22-inch-wide horizontal opening path and a 30-inch by 30-inch working space at the equipment where the equipment is installed with the face parallel to the access opening.
Clear Spaces, Grade Level and Headroom
110.26(B) Clear Spaces. Working space required by this section shall not be used for storage . When normally enclosed live parts are exposed for inspection or servicing, the working space, if in a passageway or general open space, shall be suitably guarded.
110.26(E)(2) Outdoor. Outdoor electrical equipment shall be installed in identified enclosures and protected from vehicular traffic, and the working space shall be adequate to permit safe operation and maintenance.
110.26(F) Locked Electrical Equipment Rooms or Enclosures. Rooms or enclosures containing exposed live parts or exposed conductors operating at over 1000 V shall be kept locked unless under the observation of a qualified person at all times. Electrical equipment rooms controlled by a lock are considered accessible to qualified persons.
Entrance and Egress — 110.26(C)
This subsection produces very consistent exam questions, and the two thresholds are different numbers. Learn them separately.
110.26(C)(1) Minimum Required. At least one entrance of sufficient area shall be provided to give access to and egress from the working space.
110.26(C)(2) Large Equipment. For equipment rated 1200 A or more and over 6 feet (1.8 m) wide containing overcurrent devices, switching devices, or control devices, there shall be one entrance to and egress from the required working space not less than 24 inches wide and 6.5 feet high at each end . There are two exceptions: where the location permits a continuous and unobstructed way of egress travel, one means is permitted; and where the required working space depth is doubled , only one entrance is required, and it must be located so that the edge of the entrance nearest the equipment is the minimum clear distance away.
110.26(C)(3) Personnel Doors. Where equipment rated 800 A or more that contains overcurrent devices, switching devices, or control devices is installed and there is a personnel door intended for entrance to and egress from the working space less than 25 feet (7.6 m) from the nearest edge of the working space, the door shall open in the direction of egress and be equipped with listed panic hardware or listed fire exit hardware .
So: 1200 A and over 6 ft wide triggers the two-entrance rule; 800 A within 25 ft triggers the panic-hardware rule. Mixing these two thresholds is the most common error on this topic.
Illumination — 110.26(D)
Illumination shall be provided for all working spaces about service equipment, switchboards, switchgear, panelboards, and motor control centers installed indoors , and shall not be controlled by automatic means only . In electrical equipment rooms, additional lighting outlets shall not be required where the working space is illuminated by an adjacent light source.
The phrase "not controlled by automatic means only" is the tested point: an occupancy sensor may be present, but there must be a manual override or a manually operable switch. Nobody should be plunged into darkness with a panel cover off.