5.3 Boxes and Enclosures: Box Fill and Pull Box Sizing
Alaska Journeyman Electrician Study Guide Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Alaska Certificates of Fitness, Law & Exam Logistics
1.1 The Alaska Certificate of Fitness System 1.2 Journeyman Eligibility: 8,000 Hours and How Alaska Counts Them 1.3 Trainee, Residential Wireman, Lineman, Provisional & Reciprocal Certificates 1.4 The Journeyman Examination: Format, Scheduling, Open-Book Rules & Retakes 1.5 Adopted Codes, Fees, Renewal, Inspection & Enforcement
2 Chapter 2: Using the 2020 NEC
2.1 Article 90: Purpose, Scope, Arrangement & Enforcement 2.2 Navigating the Code Book: Structure, Index & Tabbing Strategy 2.3 Article 100 Definitions You Must Know Cold 2.4 Electrical Theory for the Exam: Ohm's Law, Power & Three-Phase
3 Chapter 3: General Requirements — Article 110
3.1 Approval, Listing, Interrupting Rating & Terminations 3.2 Temperature Limitations of Terminations — 110.14(C) 3.3 Working Space, Access, Egress & Illumination — 110.26(A) through (D) 3.4 Dedicated Equipment Space, Guarding & Over-1000-Volt Installations
4 Chapter 4: Conductors and Ampacity — Article 310
4.1 Conductor Types, Insulation Markings & Table 310.16 4.2 Ambient Temperature Correction and Alaska's Cold 4.3 Adjustment for More Than Three Current-Carrying Conductors 4.4 Putting It Together: Full Conductor-Sizing Problems 4.5 Parallel Conductors, Dwelling Service Sizing & Conditions of Use
5 Chapter 5: Wiring Methods and Materials — NEC Chapter 3
5.1 Article 300 General Requirements and Underground Cover 5.2 Thermal Movement: Expansion Fittings and Table 352.44 5.3 Boxes and Enclosures: Box Fill and Pull Box Sizing 5.4 Cable Assemblies: NM, MC, AC, SE, UF and TC 5.5 Raceways: RMC, IMC, EMT, FMC, LFMC, PVC and ENT 5.6 Conduit Fill: Chapter 9 Tables and Annex C 5.7 Cable Trays, Wireways, Busways, Gutters and Surface Raceways
6 Chapter 6: Branch Circuits and Feeders
6.1 Branch-Circuit Ratings, Conductor Sizing & Multiwire Circuits 6.2 Required Outlets and Receptacle Spacing in Dwellings 6.3 GFCI Protection — Article 210.8 6.4 AFCI Protection and Receptacle Requirements 6.5 Feeders and Outside Branch Circuits — Articles 215 and 225 6.6 Grounded Conductor Identification, Switches & Panelboards
7 Chapter 7: Overcurrent Protection — Articles 240 and 242
7.1 Article 240 Fundamentals: Ratings, Locations & Conductor Protection 7.2 Feeder Tap Rules — 240.21(B) 7.3 Transformer Secondary Conductors — 240.21(C) 7.4 Fuses, Circuit Breakers, Series Ratings & Article 242 Surge Protection
8 Chapter 8: Services and Load Calculations
8.1 Service Conductors, Clearances and Service Equipment 8.2 Service Disconnects, the 2020 Rule Change, SPDs and Service GFPE 8.3 Article 220 Part II: General Lighting, Receptacles and Demand Factors 8.4 The Standard Dwelling Calculation — Article 220 Part III 8.5 Optional Dwelling and Multifamily Calculations 8.6 Commercial and Industrial Load Calculations 8.7 Neutral Load Calculations and Harmonics — 220.61
9 Chapter 9: Grounding and Bonding — Article 250
9.1 System Grounding, 250.24 and the Main Bonding Jumper 9.2 The Grounding Electrode System — 250.50 through 250.53 9.3 Grounding Electrode Conductor Sizing and Installation 9.4 Bonding: Services, Metal Piping, Structural Metal and Other Systems 9.5 Equipment Grounding Conductors: Types, Sizing and Continuity 9.6 Separately Derived Systems and Separate Buildings 9.7 Ground-Fault Protection of Equipment and Grounding of Specific Equipment
10 Chapter 10: Equipment for General Use — NEC Chapter 4
10.1 Flexible Cords, Cables and Fixture Wires 10.2 Switches, Receptacles and Industrial Control Panels 10.3 Luminaires, Lampholders and Recessed Installations 10.4 Appliances and Fixed Electric Space Heating 10.5 Deicing, Snow Melting, Pipeline and Vessel Heating 10.6 Motors Part I: Full-Load Current, Conductors and Overload Protection 10.7 Motors Part II: Short-Circuit Protection, Controllers, Disconnects and HVAC
11 Chapter 11: Transformers, Generators and Special Occupancies
11.1 Transformers — Article 450 11.2 Generators, Storage Batteries and Energy Storage Systems 11.3 Hazardous (Classified) Locations — Articles 500 through 506 11.4 Garages, Hangars, Fuel Dispensing, Bulk Storage and Spray Application 11.5 Health Care Facilities — Article 517 11.6 Agricultural Buildings, Manufactured Homes, RV Parks and Marinas 11.7 Assembly, Theaters, Carnivals, Temporary Installations and Pools
12 Chapter 12: Special Equipment, Special Conditions and Exam Strategy
12.1 Signs, Cranes, Elevators, Electric Vehicle Charging and Welders 12.2 Solar Photovoltaic, Interconnection and Stand-Alone Systems 12.3 Wind Electric Systems and Fire Pumps 12.4 Emergency, Legally Required Standby, Optional Standby and COPS 12.5 Class 1, 2 and 3 Circuits, Fire Alarm, Optical Fiber and Communications 12.6 Cold-Climate Practice in Alaska: Code Basis and Engineering Judgment 12.7 Exam-Day Strategy: Navigation, Calculation Workflow and Time Management
5.3 Boxes and Enclosures: Box Fill and Pull Box Sizing
Key Takeaways Explain This Topic AI
Table 314.16(B) assigns free space per conductor: 2.00 cubic inches for 14 AWG, 2.25 for 12 AWG, 2.50 for 10 AWG, 3.00 for 8 AWG, and 5.00 for 6 AWG.
Box fill counts one volume per conductor entering and terminating or passing through, one volume total for all internal cable clamps, two volumes per yoke or strap for each device, and one volume total for all equipment grounding conductors.
A conductor that both originates and terminates within the box, such as a pigtail, is not counted at all.
NEC 314.28(A)(1) requires straight pulls to have a length not less than eight times the trade size of the largest raceway; 314.28(A)(2) requires angle and U pulls to be six times the largest raceway plus the sum of the other raceway diameters in the same row.
NEC 314.29 requires boxes and conduit bodies to be installed so that the wiring inside is accessible without removing any part of the building or, in underground installations, without excavating.
Last updated: August 2026
Why Box Fill Exists
Conductors crammed into a box are hard to fold without damaging insulation, they trap heat, and they push against devices when the cover goes on. 314.16 sets a maximum number of conductors based on the free volume the box provides.
314.16(A) Box Volume Calculations. The volume of a wiring enclosure is the total volume of its assembled sections and any listed extension rings, plaster rings, domed covers, and mud rings marked with their volume. Standard box volumes are listed in Table 314.16(A) for metal boxes; nonmetallic boxes must be durably and legibly marked with their volume by the manufacturer.
Table 314.16(B) — Volume Required per Conductor
- Conductor size Free space required
- 18 AWG 1.50 cubic inches
- 16 AWG 1.75 cubic inches
- 14 AWG 2.00 cubic inches
- 12 AWG 2.25 cubic inches
- 10 AWG 2.50 cubic inches
- 8 AWG 3.00 cubic inches
- 6 AWG 5.00 cubic inches
- The Five Counting Rules
(1) Conductor fill — 314.16(B)(1). Each conductor that originates outside the box and terminates or is spliced within the box counts as one . Each conductor that passes through the box without splice or termination counts as one . A conductor that originates and terminates within the box — a pigtail or jumper — is not counted .
(2) Clamp fill — 314.16(B)(2). Where one or more internal cable clamps are present, a single volume allowance based on the largest conductor in the box shall be made. Cable connectors with their clamping mechanism outside the box do not count. Note this is one allowance total, not one per clamp.
(3) Support fittings fill — 314.16(B)(3). Where one or more luminaire studs or hickeys are present, a single volume allowance for each type shall be made, based on the largest conductor present.
(4) Device or equipment fill — 314.16(B)(4). For each yoke or strap containing one or more devices or equipment, a double volume allowance based on the largest conductor connected to that yoke shall be made. A device that is too large for a single gang box, occupying two gang positions, requires double volume for each gang it occupies.
(5) Equipment grounding conductor fill — 314.16(B)(5). Where one or more equipment grounding conductors enter the box, a single volume allowance based on the largest equipment grounding conductor present shall be made. Where an additional set of isolated equipment grounding conductors is present per 250.146(D), an additional one-quarter volume allowance based on the largest isolated EGC shall be made.
Worked Example 1 — Switch Box
A device box contains two 14/2 NM cables with ground, internal cable clamps, and one single-pole switch. What minimum box volume is required? Insulated conductors: 2 cables x 2 conductors = 4 x 2.00 = 8.00 cu in
- Equipment grounding conductors: all count as ONE x 2.00 = 2.00 cu in
- Internal clamps: ONE allowance, largest conductor x 2.00 = 2.00 cu in
- Device yoke (switch): TWO allowances 2 x 2.00 = 4.00 cu in
- ----------------
- Total required 16.00 cu in
16.00 cubic inches. A standard 3 x 2 x 3.5-inch device box is 18.0 cubic inches, so it is acceptable; a 3 x 2 x 2.5-inch box at 12.5 cubic inches is not.
Worked Example 2 — Junction Box with Mixed Sizes
A 4 x 4 x 1.5-inch square box (21.0 cubic inches) contains: three 12/2 NM cables with ground, one 10/2 NM cable with ground, internal clamps, and no devices. Does it comply? 12 AWG insulated: 3 cables x 2 = 6 x 2.25 = 13.50 cu in
- 10 AWG insulated: 1 cable x 2 = 2 x 2.50 = 5.00 cu in
- EGCs: one allowance at the LARGEST EGC (10 AWG) = 2.50 cu in
- Clamps: one allowance at the LARGEST conductor (10 AWG) = 2.50 cu in
- ---------------
- Total required 23.50 cu in
23.50 cubic inches required against 21.0 available — it does not comply. Two points to notice: the equipment grounding conductors get one allowance total, sized on the largest of them, and the clamp allowance is also sized on the largest conductor in the box , not on the conductor the clamp happens to grip.
Worked Example 3 — A Pigtail Does Not Count
Add a 12 AWG pigtail from the neutral splice to a receptacle inside the box in Example 2.
No change. 314.16(B)(1) excludes conductors that both originate and terminate within the box. Pigtails are free.
Conduit Bodies — 314.16(C)
Conduit bodies enclosing 6 AWG or smaller conductors, other than short-radius bodies, shall have a cross-sectional area not less than twice the cross-sectional area of the largest conduit or tubing to which they are attached. The maximum number of conductors is the same as permitted for the entering raceway.
Conduit bodies shall not contain splices, taps, or devices unless they are durably and legibly marked by the manufacturer with their volume , are supported in a rigid and secure manner, and the conductor fill does not exceed that volume.
Short-radius conduit bodies — capped elbows, service-entrance elbows — shall not contain conductors larger than that for which the body is designed, and shall not contain splices, taps, or devices .
Pull and Junction Boxes — 314.28
These rules apply to boxes and conduit bodies containing conductors 4 AWG or larger that are required to be insulated.
314.28(A)(1) Straight Pulls. The length of the box or conduit body shall not be less than eight times the metric designator (trade size) of the largest raceway .
Example: a straight pull with a 3-inch raceway requires a box at least 8 x 3 = 24 inches long.
314.28(A)(2) Angle or U Pulls, or Splices. Where splices or where angle or U pulls are made, the distance between each raceway entry inside the box and the opposite wall shall not be less than six times the trade size of the largest raceway in a row . That distance shall be increased for additional entries by the sum of the diameters of all other raceway entries in the same row on the same wall .
Where a raceway enters the wall of a box opposite a removable cover , the distance from that wall to the cover shall not be less than the outside diameter of the largest raceway plus 6 times its trade size ... in the 2020 text, the rule is that the distance shall not be less than the trade size of the largest raceway multiplied by six, plus the sum of the diameters of the other raceways.
U pull rule: the distance between raceway entries enclosing the same conductor shall not be less than six times the trade size of the larger raceway .
Worked Example 4 — Angle Pull
A junction box has three raceways entering the left wall: one 3-inch and two 2-inch. Conductors turn 90 degrees and exit the top wall. What minimum horizontal dimension is required? 6 x largest raceway trade size = 6 x 3 = 18 in
- Plus sum of other raceway diameters in the same row = 2 + 2 = 4 in
- Minimum dimension = 18 + 4 = 22 inches
314.28(A)(3) allows smaller dimensions where the box or conduit body is permanently marked with the maximum number and maximum size of conductors and the marking is based on calculations by a qualified person under engineering supervision.
314.28(B) Conductors in Pull or Junction Boxes. In boxes where the dimension of one side exceeds 6 feet (1.8 m) , all conductors shall be cabled or racked up in an approved manner.
314.28(C) Covers. All pull boxes, junction boxes, and conduit bodies shall be provided with a cover compatible with the box or conduit body construction and suitable for the conditions of use. Metal covers shall comply with the grounding requirements of 250.110.
Accessibility and Support
314.29 Boxes, Conduit Bodies, and Handhole Enclosures to Be Accessible. Boxes, conduit bodies, and handhole enclosures shall be installed so that the wiring contained in them can be rendered accessible without removing any part of the building or structure , or in underground circuits, without excavating sidewalks, paving, earth, or other substance that is to be used to establish the finished grade.
314.23 covers supports: boxes shall be rigidly and securely fastened to the surface, or supported from structural members, or in specified cases supported by the entering raceways. A conduit body may be supported by threaded conduit entries where the entries are made up wrenchtight and the conduit is supported within 3 feet on two or more sides.
314.20 requires boxes in walls or ceilings of noncombustible material to be installed so that the front edge is set back not more than 1/4 inch (6 mm) from the finished surface; in walls of combustible material the box must be flush with or project from the finished surface.
314.21 requires plaster, drywall, or plasterboard surfaces broken or incomplete around boxes to be repaired so there are no gaps or open spaces greater than 1/8 inch (3 mm) at the edge of the box.