5.5 Raceways: RMC, IMC, EMT, FMC, LFMC, PVC and ENT

Alaska Journeyman Electrician Study Guide Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Alaska Certificates of Fitness, Law & Exam Logistics

1.1 The Alaska Certificate of Fitness System 1.2 Journeyman Eligibility: 8,000 Hours and How Alaska Counts Them 1.3 Trainee, Residential Wireman, Lineman, Provisional & Reciprocal Certificates 1.4 The Journeyman Examination: Format, Scheduling, Open-Book Rules & Retakes 1.5 Adopted Codes, Fees, Renewal, Inspection & Enforcement

2 Chapter 2: Using the 2020 NEC

2.1 Article 90: Purpose, Scope, Arrangement & Enforcement 2.2 Navigating the Code Book: Structure, Index & Tabbing Strategy 2.3 Article 100 Definitions You Must Know Cold 2.4 Electrical Theory for the Exam: Ohm's Law, Power & Three-Phase

3 Chapter 3: General Requirements — Article 110

3.1 Approval, Listing, Interrupting Rating & Terminations 3.2 Temperature Limitations of Terminations — 110.14(C) 3.3 Working Space, Access, Egress & Illumination — 110.26(A) through (D) 3.4 Dedicated Equipment Space, Guarding & Over-1000-Volt Installations

4 Chapter 4: Conductors and Ampacity — Article 310

4.1 Conductor Types, Insulation Markings & Table 310.16 4.2 Ambient Temperature Correction and Alaska's Cold 4.3 Adjustment for More Than Three Current-Carrying Conductors 4.4 Putting It Together: Full Conductor-Sizing Problems 4.5 Parallel Conductors, Dwelling Service Sizing & Conditions of Use

5 Chapter 5: Wiring Methods and Materials — NEC Chapter 3

5.1 Article 300 General Requirements and Underground Cover 5.2 Thermal Movement: Expansion Fittings and Table 352.44 5.3 Boxes and Enclosures: Box Fill and Pull Box Sizing 5.4 Cable Assemblies: NM, MC, AC, SE, UF and TC 5.5 Raceways: RMC, IMC, EMT, FMC, LFMC, PVC and ENT 5.6 Conduit Fill: Chapter 9 Tables and Annex C 5.7 Cable Trays, Wireways, Busways, Gutters and Surface Raceways

6 Chapter 6: Branch Circuits and Feeders

6.1 Branch-Circuit Ratings, Conductor Sizing & Multiwire Circuits 6.2 Required Outlets and Receptacle Spacing in Dwellings 6.3 GFCI Protection — Article 210.8 6.4 AFCI Protection and Receptacle Requirements 6.5 Feeders and Outside Branch Circuits — Articles 215 and 225 6.6 Grounded Conductor Identification, Switches & Panelboards

7 Chapter 7: Overcurrent Protection — Articles 240 and 242

7.1 Article 240 Fundamentals: Ratings, Locations & Conductor Protection 7.2 Feeder Tap Rules — 240.21(B) 7.3 Transformer Secondary Conductors — 240.21(C) 7.4 Fuses, Circuit Breakers, Series Ratings & Article 242 Surge Protection

8 Chapter 8: Services and Load Calculations

8.1 Service Conductors, Clearances and Service Equipment 8.2 Service Disconnects, the 2020 Rule Change, SPDs and Service GFPE 8.3 Article 220 Part II: General Lighting, Receptacles and Demand Factors 8.4 The Standard Dwelling Calculation — Article 220 Part III 8.5 Optional Dwelling and Multifamily Calculations 8.6 Commercial and Industrial Load Calculations 8.7 Neutral Load Calculations and Harmonics — 220.61

9 Chapter 9: Grounding and Bonding — Article 250

9.1 System Grounding, 250.24 and the Main Bonding Jumper 9.2 The Grounding Electrode System — 250.50 through 250.53 9.3 Grounding Electrode Conductor Sizing and Installation 9.4 Bonding: Services, Metal Piping, Structural Metal and Other Systems 9.5 Equipment Grounding Conductors: Types, Sizing and Continuity 9.6 Separately Derived Systems and Separate Buildings 9.7 Ground-Fault Protection of Equipment and Grounding of Specific Equipment

10 Chapter 10: Equipment for General Use — NEC Chapter 4

10.1 Flexible Cords, Cables and Fixture Wires 10.2 Switches, Receptacles and Industrial Control Panels 10.3 Luminaires, Lampholders and Recessed Installations 10.4 Appliances and Fixed Electric Space Heating 10.5 Deicing, Snow Melting, Pipeline and Vessel Heating 10.6 Motors Part I: Full-Load Current, Conductors and Overload Protection 10.7 Motors Part II: Short-Circuit Protection, Controllers, Disconnects and HVAC

11 Chapter 11: Transformers, Generators and Special Occupancies

11.1 Transformers — Article 450 11.2 Generators, Storage Batteries and Energy Storage Systems 11.3 Hazardous (Classified) Locations — Articles 500 through 506 11.4 Garages, Hangars, Fuel Dispensing, Bulk Storage and Spray Application 11.5 Health Care Facilities — Article 517 11.6 Agricultural Buildings, Manufactured Homes, RV Parks and Marinas 11.7 Assembly, Theaters, Carnivals, Temporary Installations and Pools

12 Chapter 12: Special Equipment, Special Conditions and Exam Strategy

12.1 Signs, Cranes, Elevators, Electric Vehicle Charging and Welders 12.2 Solar Photovoltaic, Interconnection and Stand-Alone Systems 12.3 Wind Electric Systems and Fire Pumps 12.4 Emergency, Legally Required Standby, Optional Standby and COPS 12.5 Class 1, 2 and 3 Circuits, Fire Alarm, Optical Fiber and Communications 12.6 Cold-Climate Practice in Alaska: Code Basis and Engineering Judgment 12.7 Exam-Day Strategy: Navigation, Calculation Workflow and Time Management

5.5 Raceways: RMC, IMC, EMT, FMC, LFMC, PVC and ENT

Key Takeaways Explain This Topic AI

NEC 344.30 requires rigid metal conduit to be secured within 3 feet of each box and supported per Table 344.30(B)(2), from 10 feet for trade size 1/2 and 3/4 up to 20 feet for trade size 3 and larger.

NEC 358.30 requires EMT to be securely fastened within 3 feet of each box and supported at intervals not exceeding 10 feet.

NEC 352.30 requires PVC conduit to be supported within 3 feet of each box and at the much closer intervals of Table 352.30(B), from 3 feet for trade sizes 1/2 through 1 up to 8 feet for trade size 6.

NEC 352.10(F) permits PVC conduit for exposed work where identified for the purpose, and Schedule 80 PVC is identified for use where subject to physical damage.

NEC 348.20 and 350.20 limit FMC and LFMC smaller than trade size 1/2 to specified applications, and 250.118 permits FMC and LFMC as an equipment grounding conductor only in limited lengths with listed fittings and overcurrent protection of 20 amperes or less.

Last updated: August 2026

The Common Rules

Every raceway article in Chapter 3 shares a structure: .10 Uses Permitted , .12 Uses Not Permitted , .20 Size , .22 Number of Conductors , .24 Bends — How Made , .26 Bends — Number in One Run , .28 Reaming and Threading , .30 Securing and Supporting , .42 Couplings and Connectors , .46 Bushings .

Two rules are nearly universal:

Bends — number in one run: there shall not be more than the equivalent of four quarter bends (360 degrees total) between pull points such as conduit bodies and boxes. This applies to RMC, IMC, EMT, FMC, LFMC, PVC, RTRC, and ENT.

Bushings: where a raceway terminates at a box, fitting, or enclosure, a bushing shall be provided to protect the conductors from abrasion unless the design of the box, fitting, or enclosure provides equivalent protection.

Rigid Metal Conduit — Article 344

RMC is the heaviest and most damage-resistant raceway, permitted under all atmospheric conditions and occupancies per 344.10(A). Galvanized steel RMC may be installed in concrete, in direct contact with earth, and in severe corrosive influences where protected by corrosion protection and judged suitable for the condition. Aluminum RMC in concrete or earth requires approved supplementary corrosion protection.

344.24 Bends — How Made. Bends shall be made so that the conduit is not damaged and the internal diameter is not effectively reduced. The radius of the curve of any field bend shall not be less than shown in Table 2, Chapter 9 .

344.30(A) Securely Fastened. RMC shall be secured within 3 feet (900 mm) of each outlet box, junction box, device box, cabinet, conduit body, or other conduit termination.

344.30(B)(2) Supports. Per Table 344.30(B)(2):

  • Trade size Maximum distance between supports
  • 1/2 – 3/4 10 ft
  • 1 12 ft
  • 1-1/4 – 1-1/2 14 ft
  • 2 – 2-1/2 16 ft
  • 3 and larger 20 ft

An exception permits straight runs of RMC made up with threaded couplings to be supported per this table, and the 3-foot rule may be increased to 5 feet where structural members do not readily permit fastening within 3 feet.

Intermediate Metal Conduit (Article 342) has the same uses and support rules as RMC but a thinner wall and lighter weight, with the same outside diameter and thread specification.

Electrical Metallic Tubing — Article 358

EMT is unthreaded thinwall tubing, lighter and cheaper than RMC, and by far the most common commercial raceway.

358.10 Uses Permitted. Exposed and concealed work; in concrete, in direct contact with earth, or in areas subject to severe corrosive influences where protected by corrosion protection and judged suitable ; in wet locations where all supports, bolts, straps, and screws are protected against corrosion.

358.12 Uses Not Permitted. Where subject to severe physical damage ; for the support of luminaires or other equipment except conduit bodies no larger than the largest trade size of the tubing; where practicable, dissimilar metals in contact.

358.30(A) Securely Fastened. EMT shall be securely fastened in place at least every 10 feet (3 m) and within 3 feet (900 mm) of each outlet box, junction box, device box, cabinet, conduit body, or other tubing termination. An exception permits unbroken lengths of unthreaded EMT to be fastened within 5 feet of termination where structural members do not readily permit 3 feet.

358.42 Couplings and Connectors must be made up tight; where buried in masonry or concrete or installed in wet locations, they must be concretetight or raintight respectively.

PVC Conduit — Article 352

352.10 Uses Permitted includes concealed work in walls, floors, and ceilings; corrosive influences; cinder fill; wet locations; dry and damp locations; and 352.10(F) Exposed — PVC conduit is permitted for exposed work where not subject to physical damage if identified for such use . Schedule 80 PVC is identified for use where subject to physical damage , which is the practical reason it appears on exposed exterior risers and in parking structures.

352.12 Uses Not Permitted. In hazardous locations except as permitted; for the support of luminaires or other equipment; where subject to ambient temperatures exceeding those for which the conduit is listed; for conductors whose insulation temperature limitations would exceed those for which the conduit is listed; in theaters and similar areas except as provided; where exposed to physical damage unless identified for such use; and where subject to ambient temperature exceeding 50 degrees C (122 degrees F) unless listed otherwise.

352.30(B) Supports. PVC requires much closer support than metal raceways because it sags:

  • Trade size Maximum spacing between supports
  • 1/2 – 1 3 ft
  • 1-1/4 – 2 5 ft
  • 2-1/2 – 3 6 ft
  • 3-1/2 – 5 7 ft
  • 6 8 ft

PVC must also be secured within 3 feet of each box, cabinet, or other termination, and 352.30(A) requires supports to allow for movement resulting from thermal expansion or contraction — the tie-in to 352.44 covered in section 5.2.

352.44 Expansion Fittings and 352.48 Joints (all joints made by an approved method) complete the article. Electrical Nonmetallic Tubing (Article 362) is the corrugated, flexible nonmetallic cousin, limited to buildings not exceeding three floors above grade and prohibited in hazardous locations, for support of luminaires, and where ambient exceeds 50 degrees C.

Flexible Metal Conduit — Article 348

348.10 Uses Permitted. FMC is permitted in exposed and concealed locations.

348.12 Uses Not Permitted. In wet locations; in hoistways other than as permitted in 620.21(A)(1); in storage battery rooms; in hazardous locations except as permitted; where exposed to materials having a deteriorating effect; underground or embedded in poured concrete or aggregate; where subject to physical damage.

348.20(A) Minimum Size. FMC less than trade size 1/2 shall not be used except as permitted for enclosing motor leads, in lengths not exceeding 6 feet as part of a listed assembly or for tap connections to luminaires, in manufactured wiring systems, or in hoistways.

348.30(A) Securely Fastened. FMC shall be secured at intervals not exceeding 4.5 feet and within 12 inches of each box or fitting. Exceptions allow lengths not exceeding 3 feet at terminals where flexibility is necessary, 6 feet from a luminaire terminal connection for tap connections in accessible ceilings, and 6 feet from the last point where securely fastened for connections within an accessible ceiling.

348.60 Grounding and Bonding. Where used to connect equipment where flexibility is necessary after installation, an equipment grounding conductor shall be installed. Where flexibility is not required, FMC may qualify as an equipment grounding conductor under the conditions of 250.118(5) .

FMC as an Equipment Grounding Conductor — 250.118(5)

FMC may serve as the equipment grounding conductor only where all of the following are met:

The conduit is terminated in listed fittings ;

The circuit conductors contained in the conduit are protected by overcurrent devices rated at 20 amperes or less ;

The combined length of flexible metal conduit and flexible metallic tubing and liquidtight flexible metal conduit in the same ground return path does not exceed 6 feet ;

Where used to connect equipment where flexibility is required after installation , an equipment grounding conductor shall be installed .

Liquidtight Flexible Metal Conduit (Article 350) has parallel rules. 250.118(6) permits LFMC as an EGC in trade sizes 3/8 through 1/2 with a 20 A overcurrent device, and trade sizes 3/4 through 1-1/4 with a 60 A device, subject to the same 6-foot combined length and listed-fitting conditions. LFMC is permitted in wet locations where listed and marked for the purpose, which FMC is not.

Liquidtight Flexible Nonmetallic Conduit (Article 356) contains no metallic path at all and always requires a wire-type EGC.

Physical Damage and Cold-Weather Selection

On Alaska exteriors the raceway choice is usually driven by two constraints that pull in opposite directions: PVC is immune to corrosion but moves a great deal thermally and becomes progressively less impact resistant as temperature falls , while galvanized steel RMC barely moves thermally and takes impact well but must be protected against corrosion in aggressive soils .

The Code hooks are 352.12 (PVC not permitted where subject to physical damage unless identified for such use), 352.10(F) with Schedule 80 for damage-prone exposed locations, 344.10(B) for RMC corrosion protection in concrete and earth, and 300.6 for the general protection-against-corrosion requirement. Where a manufacturer publishes a minimum installation or handling temperature for a conduit or fitting, 110.3(B) makes that limit enforceable — that is the correct Code basis for cold-weather material limits, rather than any Alaska amendment, because Alaska adopts the NEC without technical amendments.