6.2 Required Outlets and Receptacle Spacing in Dwellings
Alaska Journeyman Electrician Study Guide Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Alaska Certificates of Fitness, Law & Exam Logistics
1.1 The Alaska Certificate of Fitness System 1.2 Journeyman Eligibility: 8,000 Hours and How Alaska Counts Them 1.3 Trainee, Residential Wireman, Lineman, Provisional & Reciprocal Certificates 1.4 The Journeyman Examination: Format, Scheduling, Open-Book Rules & Retakes 1.5 Adopted Codes, Fees, Renewal, Inspection & Enforcement
2 Chapter 2: Using the 2020 NEC
2.1 Article 90: Purpose, Scope, Arrangement & Enforcement 2.2 Navigating the Code Book: Structure, Index & Tabbing Strategy 2.3 Article 100 Definitions You Must Know Cold 2.4 Electrical Theory for the Exam: Ohm's Law, Power & Three-Phase
3 Chapter 3: General Requirements — Article 110
3.1 Approval, Listing, Interrupting Rating & Terminations 3.2 Temperature Limitations of Terminations — 110.14(C) 3.3 Working Space, Access, Egress & Illumination — 110.26(A) through (D) 3.4 Dedicated Equipment Space, Guarding & Over-1000-Volt Installations
4 Chapter 4: Conductors and Ampacity — Article 310
4.1 Conductor Types, Insulation Markings & Table 310.16 4.2 Ambient Temperature Correction and Alaska's Cold 4.3 Adjustment for More Than Three Current-Carrying Conductors 4.4 Putting It Together: Full Conductor-Sizing Problems 4.5 Parallel Conductors, Dwelling Service Sizing & Conditions of Use
5 Chapter 5: Wiring Methods and Materials — NEC Chapter 3
5.1 Article 300 General Requirements and Underground Cover 5.2 Thermal Movement: Expansion Fittings and Table 352.44 5.3 Boxes and Enclosures: Box Fill and Pull Box Sizing 5.4 Cable Assemblies: NM, MC, AC, SE, UF and TC 5.5 Raceways: RMC, IMC, EMT, FMC, LFMC, PVC and ENT 5.6 Conduit Fill: Chapter 9 Tables and Annex C 5.7 Cable Trays, Wireways, Busways, Gutters and Surface Raceways
6 Chapter 6: Branch Circuits and Feeders
6.1 Branch-Circuit Ratings, Conductor Sizing & Multiwire Circuits 6.2 Required Outlets and Receptacle Spacing in Dwellings 6.3 GFCI Protection — Article 210.8 6.4 AFCI Protection and Receptacle Requirements 6.5 Feeders and Outside Branch Circuits — Articles 215 and 225 6.6 Grounded Conductor Identification, Switches & Panelboards
7 Chapter 7: Overcurrent Protection — Articles 240 and 242
7.1 Article 240 Fundamentals: Ratings, Locations & Conductor Protection 7.2 Feeder Tap Rules — 240.21(B) 7.3 Transformer Secondary Conductors — 240.21(C) 7.4 Fuses, Circuit Breakers, Series Ratings & Article 242 Surge Protection
8 Chapter 8: Services and Load Calculations
8.1 Service Conductors, Clearances and Service Equipment 8.2 Service Disconnects, the 2020 Rule Change, SPDs and Service GFPE 8.3 Article 220 Part II: General Lighting, Receptacles and Demand Factors 8.4 The Standard Dwelling Calculation — Article 220 Part III 8.5 Optional Dwelling and Multifamily Calculations 8.6 Commercial and Industrial Load Calculations 8.7 Neutral Load Calculations and Harmonics — 220.61
9 Chapter 9: Grounding and Bonding — Article 250
9.1 System Grounding, 250.24 and the Main Bonding Jumper 9.2 The Grounding Electrode System — 250.50 through 250.53 9.3 Grounding Electrode Conductor Sizing and Installation 9.4 Bonding: Services, Metal Piping, Structural Metal and Other Systems 9.5 Equipment Grounding Conductors: Types, Sizing and Continuity 9.6 Separately Derived Systems and Separate Buildings 9.7 Ground-Fault Protection of Equipment and Grounding of Specific Equipment
10 Chapter 10: Equipment for General Use — NEC Chapter 4
10.1 Flexible Cords, Cables and Fixture Wires 10.2 Switches, Receptacles and Industrial Control Panels 10.3 Luminaires, Lampholders and Recessed Installations 10.4 Appliances and Fixed Electric Space Heating 10.5 Deicing, Snow Melting, Pipeline and Vessel Heating 10.6 Motors Part I: Full-Load Current, Conductors and Overload Protection 10.7 Motors Part II: Short-Circuit Protection, Controllers, Disconnects and HVAC
11 Chapter 11: Transformers, Generators and Special Occupancies
11.1 Transformers — Article 450 11.2 Generators, Storage Batteries and Energy Storage Systems 11.3 Hazardous (Classified) Locations — Articles 500 through 506 11.4 Garages, Hangars, Fuel Dispensing, Bulk Storage and Spray Application 11.5 Health Care Facilities — Article 517 11.6 Agricultural Buildings, Manufactured Homes, RV Parks and Marinas 11.7 Assembly, Theaters, Carnivals, Temporary Installations and Pools
12 Chapter 12: Special Equipment, Special Conditions and Exam Strategy
12.1 Signs, Cranes, Elevators, Electric Vehicle Charging and Welders 12.2 Solar Photovoltaic, Interconnection and Stand-Alone Systems 12.3 Wind Electric Systems and Fire Pumps 12.4 Emergency, Legally Required Standby, Optional Standby and COPS 12.5 Class 1, 2 and 3 Circuits, Fire Alarm, Optical Fiber and Communications 12.6 Cold-Climate Practice in Alaska: Code Basis and Engineering Judgment 12.7 Exam-Day Strategy: Navigation, Calculation Workflow and Time Management
6.2 Required Outlets and Receptacle Spacing in Dwellings
Key Takeaways Explain This Topic AI
NEC 210.52(A)(1) requires receptacles in dwelling habitable rooms so that no point measured horizontally along the floor line of any wall space is more than 6 feet from a receptacle outlet.
NEC 210.52(A)(2) defines wall space as any space 2 feet or more in width, the space occupied by fixed panels in walls excluding sliding panels, and the space afforded by fixed room dividers such as railings and counters.
NEC 210.11(C) requires at least two 20-ampere small-appliance branch circuits, one 20-ampere laundry circuit, one 20-ampere bathroom circuit, and one 20-ampere garage circuit in dwelling units.
NEC 210.52(C)(1) requires a receptacle at each kitchen counter wall space 12 inches or wider, positioned so no point along the wall line is more than 24 inches measured horizontally from a receptacle outlet.
NEC 210.52(D) requires at least one receptacle within 36 inches of the outside edge of each bathroom basin, and 210.52(E) requires accessible outdoor receptacles at the front and back of one- and two-family dwellings not more than 6.5 feet above grade.
Last updated: August 2026
The Purpose of Part III
Article 210 Part III specifies where receptacles must exist , independent of load. The goal is to make extension cords unnecessary. These rules are minimums; nothing prevents adding more.
The 6-Foot Rule — 210.52(A)
210.52(A)(1) Spacing. Receptacles shall be installed such that no point measured horizontally along the floor line of any wall space is more than 1.8 m (6 ft) from a receptacle outlet .
The practical translation: a receptacle within 6 feet of each end of a wall , and no more than 12 feet apart thereafter, because the 6-foot reach works in both directions.
210.52(A)(2) Wall Space. As used in this section, a wall space shall include the following:
Any space 2 feet (600 mm) or more in width , including space measured around corners, and unbroken along the floor line by doorways, fireplaces, and similar openings;
The space occupied by fixed panels in walls , excluding sliding panels;
The space afforded by fixed room dividers such as freestanding bar-type counters or railings.
A wall segment less than 2 feet wide is not a wall space and needs no receptacle.
210.52(A)(3) Floor Receptacles. Receptacle outlets in or on floors shall not be counted as part of the required number unless located within 18 inches (450 mm) of the wall.
210.52(A)(4) Countertop and Similar Work Surface Receptacle Outlets. Receptacles installed for countertop and similar work surfaces as specified in 210.52(C) shall not be considered as the receptacle outlets required by 210.52(A)(1).
Counting Example
How many receptacles are required along an unbroken 14-foot living-room wall?
A receptacle at the 6-foot mark covers 0 through 12 feet. The point at 14 feet is then 2 feet beyond coverage. One receptacle cannot be both within 6 feet of the 0-foot end and within 6 feet of the 14-foot end, because that would require it to be at or below 6 feet and at or above 8 feet simultaneously. Two receptacles are required.
For a 24-foot wall: receptacles at 6 and 18 feet cover it — two are enough, since 6 + 12 = 18 and 18 + 6 = 24.
Required Dwelling Branch Circuits — 210.11(C)
Circuit Section Rating Notes
Small appliance 210.11(C)(1) Two or more 20 A Serve all receptacles in kitchen, pantry, breakfast room, dining room, or similar area
Laundry 210.11(C)(2) One 20 A Supplies laundry receptacle outlets required by 210.52(F); no other outlets
Bathroom 210.11(C)(3) One 20 A Supplies bathroom receptacle outlets; no other outlets, with an exception permitting a single bathroom's other equipment
Garage 210.11(C)(4) One 120 V, 20 A Supplies receptacle outlets required by 210.52(G)(1) in attached garages and detached garages with electric power
210.52(B)(1) requires the two or more small-appliance branch circuits to serve all receptacle outlets covered by 210.52(A) and (C)(1) in the kitchen, pantry, breakfast room, dining room, or similar area, plus the refrigeration equipment receptacle.
210.52(B)(2) states these circuits shall have no other outlets — with exceptions for a receptacle installed solely for the electric supply to and support of an electric clock, and for receptacles supplying gas-fired ranges, ovens, or counter-mounted cooking units.
210.52(B)(3) requires at least two of the small-appliance branch circuits to serve the kitchen countertop receptacles required by 210.52(C).
Countertops and Work Surfaces — 210.52(C)
(C)(1) Wall Spaces. A receptacle outlet shall be installed at each wall countertop and work surface that is 12 inches (300 mm) or wider . Receptacle outlets shall be installed so that no point along the wall line is more than 24 inches (600 mm) measured horizontally from a receptacle outlet in that space.
The 24-inch figure is the reach in each direction, so the practical maximum spacing between countertop receptacles is 48 inches . Any countertop 12 inches or wider needs at least one.
(C)(2) Island Countertop Spaces and (C)(3) Peninsular Countertop Spaces. At least one receptacle outlet shall be installed at each island and each peninsular countertop space with a long dimension of 24 inches or greater and a short dimension of 12 inches or greater . Peninsular countertop length is measured from the connecting edge.
(C)(4) Separate Spaces. Countertop spaces separated by rangetops, refrigerators, or sinks shall be considered as separate countertop spaces in applying the requirements. A sink or range that breaks the counter starts a new counting run.
(C)(5) Receptacle Outlet Location. Receptacles shall be located not more than 20 inches (500 mm) above the countertop or work surface . Receptacles shall not be installed in a face-up position in or on countertop surfaces or work surfaces unless listed for that application. Specific allowances exist for installations below a countertop where the counter is a construction for the physically impaired or where an island or peninsular countertop has no means of mounting above.
Other Required Receptacle Locations
210.52(D) Bathrooms. At least one receptacle outlet shall be installed in bathrooms within 36 inches (900 mm) of the outside edge of each basin . The receptacle outlet shall be located on a wall or partition adjacent to the basin or basin countertop, located on the countertop, or installed on the side or face of the basin cabinet not more than 12 inches (300 mm) below the countertop . Receptacles shall not be installed in a face-up position unless listed.
210.52(E) Outdoor Outlets. For a one-family dwelling and each unit of a two-family dwelling that is at grade level, at least one receptacle outlet readily accessible from grade and not more than 6.5 feet (2.0 m) above grade shall be installed at the front and back of the dwelling. (E)(2) requires balconies, decks, and porches accessible from inside the dwelling unit to have at least one receptacle outlet within the perimeter, not more than 6.5 feet above the surface. (E)(3) requires each dwelling unit of a multifamily dwelling at grade level with individual exterior entrance/egress to have at least one outdoor receptacle.
210.52(F) Laundry Areas. At least one receptacle outlet shall be installed in areas designated for the installation of laundry equipment.
210.52(G) Basements, Garages, and Accessory Buildings. For a one-family dwelling: (1) at least one receptacle outlet shall be installed in each vehicle bay of a garage, not more than 5.5 feet (1.7 m) above the floor ; (2) at least one in each separate unfinished portion of a basement; (3) at least one in each accessory building with electric power.
210.52(H) Hallways. In dwelling units, hallways of 10 feet (3.0 m) or more in length shall have at least one receptacle outlet. The hall length is measured along the centerline of the hall without passing through a doorway.
210.52(I) Foyers. Foyers that are not part of a hallway and have an area greater than 60 square feet (5.6 m squared) shall have a receptacle located in each wall space 3 feet or more in width that is unbroken by doorways, floor-to-ceiling windows, and similar openings.
Lighting Outlets — 210.70
210.70(A)(1) Habitable Rooms. At least one wall switch-controlled lighting outlet shall be installed in every habitable room, kitchen, and bathroom. Exception No. 1 permits a switch-controlled receptacle in place of a lighting outlet in other than kitchens and bathrooms.
210.70(A)(2) Additional Locations. At least one wall switch-controlled lighting outlet is required in hallways, stairways, attached garages, and detached garages with electric power; at outdoor entrances or exits with grade-level access; and where a stairway between floor levels has six risers or more , a wall switch at each floor level and landing level that includes an entryway to control the stairway lighting outlet.
210.70(A)(3) Storage or Equipment Spaces. At least one lighting outlet containing a switch, or controlled by a wall switch, shall be installed in attics, underfloor spaces, utility rooms, and basements where these spaces are used for storage or contain equipment requiring servicing , with the lighting outlet located at or near the equipment.
210.70(C) All Occupancies. At least one lighting outlet containing a switch or controlled by a wall switch shall be installed in attics or underfloor spaces used for storage or containing equipment requiring servicing.
Arctic Entries and Alaska Practice
Alaska dwellings very often have an arctic entry — an unheated or semi-heated vestibule between the outdoors and the living space. Nothing in Article 210 creates a special category for it, so the correct analysis is by function. If it is a habitable room, the 210.52(A) 6-foot rule applies; if it functions as a hallway 10 feet or more in length, 210.52(H) applies; if it is a storage or utility space, 210.70(A)(3) governs the lighting outlet. If a receptacle in that space qualifies as an indoor damp or wet location it falls under 210.8(A)(11) for GFCI protection, covered in the next section.