11.2 Generators, Storage Batteries and Energy Storage Systems
Alaska Journeyman Electrician Study Guide Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Alaska Certificates of Fitness, Law & Exam Logistics
1.1 The Alaska Certificate of Fitness System 1.2 Journeyman Eligibility: 8,000 Hours and How Alaska Counts Them 1.3 Trainee, Residential Wireman, Lineman, Provisional & Reciprocal Certificates 1.4 The Journeyman Examination: Format, Scheduling, Open-Book Rules & Retakes 1.5 Adopted Codes, Fees, Renewal, Inspection & Enforcement
2 Chapter 2: Using the 2020 NEC
2.1 Article 90: Purpose, Scope, Arrangement & Enforcement 2.2 Navigating the Code Book: Structure, Index & Tabbing Strategy 2.3 Article 100 Definitions You Must Know Cold 2.4 Electrical Theory for the Exam: Ohm's Law, Power & Three-Phase
3 Chapter 3: General Requirements — Article 110
3.1 Approval, Listing, Interrupting Rating & Terminations 3.2 Temperature Limitations of Terminations — 110.14(C) 3.3 Working Space, Access, Egress & Illumination — 110.26(A) through (D) 3.4 Dedicated Equipment Space, Guarding & Over-1000-Volt Installations
4 Chapter 4: Conductors and Ampacity — Article 310
4.1 Conductor Types, Insulation Markings & Table 310.16 4.2 Ambient Temperature Correction and Alaska's Cold 4.3 Adjustment for More Than Three Current-Carrying Conductors 4.4 Putting It Together: Full Conductor-Sizing Problems 4.5 Parallel Conductors, Dwelling Service Sizing & Conditions of Use
5 Chapter 5: Wiring Methods and Materials — NEC Chapter 3
5.1 Article 300 General Requirements and Underground Cover 5.2 Thermal Movement: Expansion Fittings and Table 352.44 5.3 Boxes and Enclosures: Box Fill and Pull Box Sizing 5.4 Cable Assemblies: NM, MC, AC, SE, UF and TC 5.5 Raceways: RMC, IMC, EMT, FMC, LFMC, PVC and ENT 5.6 Conduit Fill: Chapter 9 Tables and Annex C 5.7 Cable Trays, Wireways, Busways, Gutters and Surface Raceways
6 Chapter 6: Branch Circuits and Feeders
6.1 Branch-Circuit Ratings, Conductor Sizing & Multiwire Circuits 6.2 Required Outlets and Receptacle Spacing in Dwellings 6.3 GFCI Protection — Article 210.8 6.4 AFCI Protection and Receptacle Requirements 6.5 Feeders and Outside Branch Circuits — Articles 215 and 225 6.6 Grounded Conductor Identification, Switches & Panelboards
7 Chapter 7: Overcurrent Protection — Articles 240 and 242
7.1 Article 240 Fundamentals: Ratings, Locations & Conductor Protection 7.2 Feeder Tap Rules — 240.21(B) 7.3 Transformer Secondary Conductors — 240.21(C) 7.4 Fuses, Circuit Breakers, Series Ratings & Article 242 Surge Protection
8 Chapter 8: Services and Load Calculations
8.1 Service Conductors, Clearances and Service Equipment 8.2 Service Disconnects, the 2020 Rule Change, SPDs and Service GFPE 8.3 Article 220 Part II: General Lighting, Receptacles and Demand Factors 8.4 The Standard Dwelling Calculation — Article 220 Part III 8.5 Optional Dwelling and Multifamily Calculations 8.6 Commercial and Industrial Load Calculations 8.7 Neutral Load Calculations and Harmonics — 220.61
9 Chapter 9: Grounding and Bonding — Article 250
9.1 System Grounding, 250.24 and the Main Bonding Jumper 9.2 The Grounding Electrode System — 250.50 through 250.53 9.3 Grounding Electrode Conductor Sizing and Installation 9.4 Bonding: Services, Metal Piping, Structural Metal and Other Systems 9.5 Equipment Grounding Conductors: Types, Sizing and Continuity 9.6 Separately Derived Systems and Separate Buildings 9.7 Ground-Fault Protection of Equipment and Grounding of Specific Equipment
10 Chapter 10: Equipment for General Use — NEC Chapter 4
10.1 Flexible Cords, Cables and Fixture Wires 10.2 Switches, Receptacles and Industrial Control Panels 10.3 Luminaires, Lampholders and Recessed Installations 10.4 Appliances and Fixed Electric Space Heating 10.5 Deicing, Snow Melting, Pipeline and Vessel Heating 10.6 Motors Part I: Full-Load Current, Conductors and Overload Protection 10.7 Motors Part II: Short-Circuit Protection, Controllers, Disconnects and HVAC
11 Chapter 11: Transformers, Generators and Special Occupancies
11.1 Transformers — Article 450 11.2 Generators, Storage Batteries and Energy Storage Systems 11.3 Hazardous (Classified) Locations — Articles 500 through 506 11.4 Garages, Hangars, Fuel Dispensing, Bulk Storage and Spray Application 11.5 Health Care Facilities — Article 517 11.6 Agricultural Buildings, Manufactured Homes, RV Parks and Marinas 11.7 Assembly, Theaters, Carnivals, Temporary Installations and Pools
12 Chapter 12: Special Equipment, Special Conditions and Exam Strategy
12.1 Signs, Cranes, Elevators, Electric Vehicle Charging and Welders 12.2 Solar Photovoltaic, Interconnection and Stand-Alone Systems 12.3 Wind Electric Systems and Fire Pumps 12.4 Emergency, Legally Required Standby, Optional Standby and COPS 12.5 Class 1, 2 and 3 Circuits, Fire Alarm, Optical Fiber and Communications 12.6 Cold-Climate Practice in Alaska: Code Basis and Engineering Judgment 12.7 Exam-Day Strategy: Navigation, Calculation Workflow and Time Management
11.2 Generators, Storage Batteries and Energy Storage Systems
Key Takeaways Explain This Topic AI
NEC 445.13(A) requires conductors from the generator terminals to the first overcurrent device to have an ampacity of not less than 115 percent of the nameplate current rating of the generator.
NEC 445.18 requires generators to have one or more disconnecting means that simultaneously open all associated ungrounded conductors and are lockable in the open position, with specified provisions for shutdown.
NEC 445.20 requires ground-fault circuit-interrupter protection for 125-volt, 15- and 20-ampere receptacles on 15-kilowatt or smaller portable generators under the conditions stated in that section.
NEC 480.7 requires a disconnecting means for ungrounded conductors derived from a stationary battery system over 60 volts DC, and 480.10 sets the requirements for battery locations including ventilation and working space.
Article 706 governs energy storage systems, requiring listed systems, a disconnecting means, and compliance with the manufacturer's operating and maintenance instructions.
Last updated: August 2026
Article 445 — Generators
445.10 Location. Generators shall be of a type suitable for the locations in which they are installed. They shall also meet the requirements for motors in 430.14. Generators installed in hazardous (classified) locations as described in Articles 500 through 503, or in other locations that are attributable to hazardous (classified) conditions of operation and maintenance, shall comply with the applicable provisions of those articles.
445.11 Marking. Each generator shall be provided with a nameplate giving the manufacturer's name, rated frequency, number of phases if AC, rating in kilowatts or kilovolt-amperes, normal volts and amperes corresponding to the rating, rated revolutions per minute, insulation system class and rated ambient temperature or rated temperature rise, time rating, power factor, subtransient and transient impedances, and, for stationary generators, whether the neutral is bonded to the generator frame. Generators arranged to operate in parallel shall be marked accordingly. A generator with a factory-installed overcurrent device shall be marked with the maximum load current for which the device is set.
445.12 Overcurrent Protection. Constant-voltage generators, except AC generator exciters, shall be protected from overload by inherent design, circuit breakers, fuses, protective relays, or other identified overcurrent protective means suitable for the conditions of use.
445.13(A) Ampacity of Conductors. The ampacity of the conductors from the generator terminals to the first distribution device containing overcurrent protection shall not be less than 115 percent of the nameplate current rating of the generator . It shall be permitted to size the neutral conductors in accordance with 220.61. Conductors that must carry ground-fault currents shall not be smaller than required by 250.30.
Exception: Where the design and operation of the generator prevent overloading, the ampacity of the conductors shall not be less than 100 percent of the nameplate current rating of the generator.
445.13(B) Overcurrent Protection Provided. Where the generator set is equipped with a listed overcurrent protective device or a combination of a current transformer and overcurrent relay, conductors shall be permitted to be tapped from the load side of the protected terminals in accordance with 240.21(B).
445.18 Disconnecting Means and Shutdown of Prime Mover.
(A) Disconnecting Means. Generators, other than cord-and-plug-connected portable generators, shall have one or more disconnecting means. Each disconnecting means shall simultaneously open all associated ungrounded conductors . Each disconnecting means shall be lockable in the open position in accordance with 110.25.
(B) Shutdown of Prime Mover. Generators shall have provisions to shut down the prime mover. The means of shutdown shall comply with all of the following: (1) be equipped with provisions to disable all prime mover start control circuits to render the prime mover incapable of starting; and (2) initiate a shutdown mechanism that requires a mechanical reset. The provisions to shut down the prime mover shall be permitted to satisfy the requirements of 445.18(A) where it is capable of being locked in the open position in accordance with 110.25.
(C) Generators with Greater Than 15 kW Rating. For generators with greater than 15 kW rating, a remote emergency stop switch shall be provided to shut down the prime mover. The remote emergency stop switch shall be located outside the equipment room or generator enclosure and shall also meet the requirements of 445.18(B)(1).
(D) Emergency Shutdown of Prime Mover in Other Than One- and Two-Family Dwellings. Where a generator is installed in a parallel configuration with other generators or other power production sources, in other than one- and two-family dwellings, the disconnecting means shall be provided with a means to disable all prime mover start control circuits.
445.19 Generators Supplying Multiple Loads. A single generator supplying more than one load, or multiple generators operating in parallel, shall be permitted to supply the following: (1) an emergency system; (2) a legally required standby system; (3) an optional standby system; (4) a parallel power production system; or (5) an interconnected electric power production source. Where the generator or generators supply more than one class of load, other articles of the Code shall apply.
445.20 Ground-Fault Circuit-Interrupter Protection for Receptacles on 15-Kilowatt or Smaller Portable Generators. All 125-volt, single-phase, 15- and 20-ampere receptacle outlets that are a part of a 15-kilowatt or smaller portable generator shall have ground-fault circuit-interrupter protection for personnel integral to the generator or receptacle, in accordance with the conditions of the section. Listed cord sets or devices incorporating listed GFCI protection identified for portable use shall be permitted.
445.11 requires stationary generators to be marked as to whether the neutral is bonded to the generator frame . That marking answers the separately-derived-system question from section 9.6: a generator whose neutral is bonded at the frame and whose transfer switch does not switch the neutral will create a parallel neutral path unless the bond is removed.
Interconnection and Transfer Equipment
702.5 Capacity and Rating (Optional Standby Systems). Optional standby system equipment shall be suitable for the maximum available fault current at its terminals. The calculated load shall be in accordance with Article 220 or by another approved method.
702.6 Transfer Equipment. Transfer equipment shall be required for all standby systems subject to the provisions of Article 702 and for which an electric utility supply is either the normal or standby source. Transfer equipment shall be suitable for the intended use, designed and installed so as to prevent the inadvertent interconnection of all sources of supply in any operation of the transfer equipment , and shall be listed and marked for emergency, legally required, or optional standby use as applicable.
702.7 Signals and 702.12 Outdoor Generator Sets complete the general requirements. 702.12(A) provides that where an outdoor housed generator set is equipped with a readily accessible disconnecting means located within sight of the building or structure supplied, an additional disconnecting means shall not be required where ungrounded conductors serve or pass through the building or structure.
Article 480 — Stationary Standby Batteries
480.4 Battery and Cell Terminations. (A) Corrosion prevention — antioxidant material shall be permitted to be used on battery terminals. (B) Intercell and intertier conductors and connections shall be sized to carry the maximum anticipated current.
480.5 Wiring and Equipment Supplied from Batteries. Wiring and equipment supplied from storage batteries shall be subject to the requirements of the Code applying to wiring and equipment operating at the same voltage.
480.6 Overcurrent Protection for Prime Movers. Overcurrent protection shall not be required for conductors from a battery with a voltage of 60 volts DC or less if the battery provides power for starting, ignition, or control of prime movers.
480.7 Disconnecting Means.
(A) Disconnecting Means. A disconnecting means shall be provided for all ungrounded conductors derived from a stationary battery system over 60 volts DC . A disconnecting means shall be readily accessible and located within sight of the battery system .
(B) Remote Actuation. Where a disconnecting means located remote from the battery system is provided, a means shall be provided at the battery system to remotely actuate the disconnecting means.
(C) Notification. The disconnecting means shall be legibly marked in the field with nominal battery voltage , available fault current derived from the stationary battery system , an arc-flash label applied in accordance with acceptable industry practice, and the date the calculation was performed .
(D) Emergency Shutdown. In one- and two-family dwellings, a disconnecting means or its remote control for a stationary battery system exceeding 60 volts shall be located at a readily accessible location outside the building for emergency shutdown.
480.9 Battery Support Systems. (A) Racks shall be substantial and treated to be resistant to deteriorating action by the electrolyte. (B) Trays shall be treated to be resistant to deteriorating action by the electrolyte.
480.10 Battery Locations.
(A) Ventilation. Provisions appropriate to the battery technology shall be made for sufficient diffusion and ventilation of gases from the battery to prevent the accumulation of an explosive mixture.
(B) Live Parts. Guarding of live parts shall comply with 110.27.
(C) Working Space. Working space about the battery systems shall comply with 110.26 . Working clearance shall be measured from the edge of the battery rack.
(D) Top Terminal Batteries. Where top terminal batteries are installed on tiered racks or on stacked modules, working space shall be provided in accordance with the battery manufacturer's instructions.
(E) Egress. A personnel door intended for entrance to and egress from rooms designated as a battery room shall open in the direction of egress and shall be equipped with listed panic hardware .
480.12 Battery Interconnections. Flexible cables, as identified in Article 400, in sizes 2/0 AWG and larger shall be permitted within the battery enclosure from battery terminals to a nearby junction box where they shall be connected to an approved wiring method.
Article 706 — Energy Storage Systems
706.1 Scope. Article 706 applies to all permanently installed energy storage systems (ESS) operating at over 50 volts AC or 60 volts DC that may be stand-alone or interactive with other electric power production sources.
706.5 Listing. Energy storage systems shall be listed . Where an energy storage system is composed of a combination of listed components, the completed installation shall be approved .
706.7 Maintenance. Energy storage systems shall be maintained in proper and safe operating condition . Documentation of the maintenance shall be maintained.
706.15 Disconnecting Means. A disconnecting means shall be provided for all ungrounded conductors derived from an ESS. A disconnecting means shall be readily accessible and located within sight of the ESS. Where the disconnecting means is remote from the ESS, a directory showing the location of each disconnect shall be installed at the ESS location, and remote actuation shall be provided.
706.15(C) Notification. The disconnecting means shall be legibly marked in the field with the nominal ESS voltage , available fault current , an arc-flash label, and the date the calculation was performed .
706.15(E) Disconnection of Series Battery Circuits. Battery circuits subject to field servicing, where more than 240 volts DC are present, shall have provisions to disconnect the series-connected strings into segments not exceeding 240 volts DC for maintenance by qualified persons.
706.20 General (Installation). ESS shall be installed in accordance with the manufacturer's instructions and the listing.
706.21 Directory. A permanent plaque or directory shall be installed at each service equipment location or at an approved readily visible location, denoting the location of each power source disconnecting means for the building or structure.
706.30 Circuit Sizing and Current. Requirements for calculating maximum current and sizing conductors and overcurrent protection for ESS circuits.
Cold-Climate Considerations
These are engineering and manufacturer-listing matters, not separate Code rules, but they determine whether an Alaska installation works.
Lithium-ion charging below freezing. Lithium-ion chemistries, including lithium iron phosphate, generally cannot accept charge current at cell temperatures below 0 degrees C (32 degrees F) without plating metallic lithium on the anode, which permanently reduces capacity and can create an internal short. Manufacturers address this with battery management systems that block charging below a temperature threshold, and often with integral heaters. The Code hook is 706.5 (the ESS must be listed) and 110.3(B) (installed per the instructions), including any minimum ambient temperature stated in the listing. Discharging at low temperature is generally permitted at reduced capacity; charging is the limited operation.
Lead-acid capacity loss. Flooded and valve-regulated lead-acid batteries lose usable capacity as temperature drops — roughly a quarter of rated capacity at minus 18 degrees C. A discharged lead-acid battery can also freeze, because its electrolyte approaches the freezing point of water as specific gravity falls. Sizing must account for the design low temperature.
Ventilation still applies. 480.10(A) requires ventilation appropriate to the battery technology to prevent accumulation of an explosive mixture. Enclosing a vented lead-acid bank in a sealed insulated box to keep it warm creates a hydrogen accumulation hazard. Heat the space, do not seal the battery.
Generator installation. Diesel gensets in Alaska require block heaters, battery warmers, and fuel treated or heated against gelling. None of that is NEC content, but the electrical consequence is real: the block heater and battery charger are loads that must be included in the service calculation, and a block heater receptacle outdoors requires GFCI protection under 210.8.