11.4 Garages, Hangars, Fuel Dispensing, Bulk Storage and Spray Application
Alaska Journeyman Electrician Study Guide Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Alaska Certificates of Fitness, Law & Exam Logistics
1.1 The Alaska Certificate of Fitness System 1.2 Journeyman Eligibility: 8,000 Hours and How Alaska Counts Them 1.3 Trainee, Residential Wireman, Lineman, Provisional & Reciprocal Certificates 1.4 The Journeyman Examination: Format, Scheduling, Open-Book Rules & Retakes 1.5 Adopted Codes, Fees, Renewal, Inspection & Enforcement
2 Chapter 2: Using the 2020 NEC
2.1 Article 90: Purpose, Scope, Arrangement & Enforcement 2.2 Navigating the Code Book: Structure, Index & Tabbing Strategy 2.3 Article 100 Definitions You Must Know Cold 2.4 Electrical Theory for the Exam: Ohm's Law, Power & Three-Phase
3 Chapter 3: General Requirements — Article 110
3.1 Approval, Listing, Interrupting Rating & Terminations 3.2 Temperature Limitations of Terminations — 110.14(C) 3.3 Working Space, Access, Egress & Illumination — 110.26(A) through (D) 3.4 Dedicated Equipment Space, Guarding & Over-1000-Volt Installations
4 Chapter 4: Conductors and Ampacity — Article 310
4.1 Conductor Types, Insulation Markings & Table 310.16 4.2 Ambient Temperature Correction and Alaska's Cold 4.3 Adjustment for More Than Three Current-Carrying Conductors 4.4 Putting It Together: Full Conductor-Sizing Problems 4.5 Parallel Conductors, Dwelling Service Sizing & Conditions of Use
5 Chapter 5: Wiring Methods and Materials — NEC Chapter 3
5.1 Article 300 General Requirements and Underground Cover 5.2 Thermal Movement: Expansion Fittings and Table 352.44 5.3 Boxes and Enclosures: Box Fill and Pull Box Sizing 5.4 Cable Assemblies: NM, MC, AC, SE, UF and TC 5.5 Raceways: RMC, IMC, EMT, FMC, LFMC, PVC and ENT 5.6 Conduit Fill: Chapter 9 Tables and Annex C 5.7 Cable Trays, Wireways, Busways, Gutters and Surface Raceways
6 Chapter 6: Branch Circuits and Feeders
6.1 Branch-Circuit Ratings, Conductor Sizing & Multiwire Circuits 6.2 Required Outlets and Receptacle Spacing in Dwellings 6.3 GFCI Protection — Article 210.8 6.4 AFCI Protection and Receptacle Requirements 6.5 Feeders and Outside Branch Circuits — Articles 215 and 225 6.6 Grounded Conductor Identification, Switches & Panelboards
7 Chapter 7: Overcurrent Protection — Articles 240 and 242
7.1 Article 240 Fundamentals: Ratings, Locations & Conductor Protection 7.2 Feeder Tap Rules — 240.21(B) 7.3 Transformer Secondary Conductors — 240.21(C) 7.4 Fuses, Circuit Breakers, Series Ratings & Article 242 Surge Protection
8 Chapter 8: Services and Load Calculations
8.1 Service Conductors, Clearances and Service Equipment 8.2 Service Disconnects, the 2020 Rule Change, SPDs and Service GFPE 8.3 Article 220 Part II: General Lighting, Receptacles and Demand Factors 8.4 The Standard Dwelling Calculation — Article 220 Part III 8.5 Optional Dwelling and Multifamily Calculations 8.6 Commercial and Industrial Load Calculations 8.7 Neutral Load Calculations and Harmonics — 220.61
9 Chapter 9: Grounding and Bonding — Article 250
9.1 System Grounding, 250.24 and the Main Bonding Jumper 9.2 The Grounding Electrode System — 250.50 through 250.53 9.3 Grounding Electrode Conductor Sizing and Installation 9.4 Bonding: Services, Metal Piping, Structural Metal and Other Systems 9.5 Equipment Grounding Conductors: Types, Sizing and Continuity 9.6 Separately Derived Systems and Separate Buildings 9.7 Ground-Fault Protection of Equipment and Grounding of Specific Equipment
10 Chapter 10: Equipment for General Use — NEC Chapter 4
10.1 Flexible Cords, Cables and Fixture Wires 10.2 Switches, Receptacles and Industrial Control Panels 10.3 Luminaires, Lampholders and Recessed Installations 10.4 Appliances and Fixed Electric Space Heating 10.5 Deicing, Snow Melting, Pipeline and Vessel Heating 10.6 Motors Part I: Full-Load Current, Conductors and Overload Protection 10.7 Motors Part II: Short-Circuit Protection, Controllers, Disconnects and HVAC
11 Chapter 11: Transformers, Generators and Special Occupancies
11.1 Transformers — Article 450 11.2 Generators, Storage Batteries and Energy Storage Systems 11.3 Hazardous (Classified) Locations — Articles 500 through 506 11.4 Garages, Hangars, Fuel Dispensing, Bulk Storage and Spray Application 11.5 Health Care Facilities — Article 517 11.6 Agricultural Buildings, Manufactured Homes, RV Parks and Marinas 11.7 Assembly, Theaters, Carnivals, Temporary Installations and Pools
12 Chapter 12: Special Equipment, Special Conditions and Exam Strategy
12.1 Signs, Cranes, Elevators, Electric Vehicle Charging and Welders 12.2 Solar Photovoltaic, Interconnection and Stand-Alone Systems 12.3 Wind Electric Systems and Fire Pumps 12.4 Emergency, Legally Required Standby, Optional Standby and COPS 12.5 Class 1, 2 and 3 Circuits, Fire Alarm, Optical Fiber and Communications 12.6 Cold-Climate Practice in Alaska: Code Basis and Engineering Judgment 12.7 Exam-Day Strategy: Navigation, Calculation Workflow and Time Management
11.4 Garages, Hangars, Fuel Dispensing, Bulk Storage and Spray Application
Key Takeaways Explain This Topic AI
In a major repair garage without adequate ventilation, Table 511.3(C) classifies the area from the floor up to 18 inches above the floor as Class I, Division 2.
NEC 511.12 requires GFCI protection for all 125-volt, single-phase, 15- and 20-ampere receptacles installed in areas where electrical diagnostic equipment, hand tools, or portable lighting are to be used in repair garages.
NEC 513.3 classifies the area within 5 feet horizontally of aircraft power plants or fuel tanks as Class I, Division 2 or Zone 2, and any pit or depression below the level of the hangar floor as Class I, Division 1.
Table 514.3(B)(1) classifies the space within 18 inches of grade extending 20 feet horizontally from a motor fuel dispenser as Class I, Division 2, and the dispenser interior as Class I, Division 1.
NEC 514.11 requires an emergency shutoff device or electrical disconnect for motor fuel dispensing that disconnects all conductors including the grounded conductor, located more than 20 feet but less than 100 feet from the dispensers.
Last updated: August 2026
Article 511 — Commercial Garages, Repair and Storage
511.1 Scope. Article 511 applies to locations used for service and repair operations in connection with self-propelled vehicles in which volatile flammable liquids or flammable gases are used for fuel or power.
511.2 distinguishes a major repair garage — where major repairs such as engine overhauls, painting, body and fender work, and repairs that require draining of the fuel tank are performed — from a minor repair garage , where lubrication, inspection, and minor routine maintenance are performed.
511.3 Area Classification. Where flammable liquids having a flash point below 38 degrees C (100 degrees F), such as gasoline, are used, the classification is determined by Table 511.3(C) for major repair garages and Table 511.3(D) for minor repair garages.
For a major repair garage where ventilation is not provided :
- Space Classification
- Entire area within the garage from the floor up to 18 inches (450 mm) above the floor Class I, Division 2
Any pit or depression below floor level Class I, Division 1 up to the floor level, or Division 2 with adequate ventilation
Where ventilation is provided — mechanical ventilation providing a minimum of 4 air changes per hour or 1 cubic foot per minute per square foot of floor area, with exhaust taken from a point within 18 inches of the floor — the floor-to-18-inch area is unclassified .
511.3(A) Parking Garages. Parking garages used for parking or storage shall be unclassified .
511.7 Wiring and Equipment Installed Above Class I Locations. (A) Wiring in spaces above Class I locations shall be in metal raceways, PVC, RTRC, electrical nonmetallic tubing, flexible metal conduit, liquidtight flexible conduit, or Types MC, MI, or PLTC cable. (B) Equipment less than 12 feet above the floor level that may produce arcs, sparks, or particles of hot metal shall be of the totally enclosed type or constructed so as to prevent the escape of sparks or hot metal particles. Equipment such as lamps and lampholders installed above lanes through which vehicles are commonly driven or that may be exposed to physical damage shall be located not less than 3.7 m (12 ft) above floor level , unless of the totally enclosed type or otherwise protected.
511.12 Ground-Fault Circuit-Interrupter Protection for Personnel. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in areas where electrical diagnostic equipment, electrical hand tools, or portable lighting equipment are to be used shall have GFCI protection for personnel .
511.16 Grounding and Bonding. All metal raceways, the metal armor or metallic sheath on cables, and all non-current-carrying metal parts of fixed and portable electrical equipment shall be bonded in accordance with 501.30(A) in Class I locations.
Article 513 — Aircraft Hangars
513.3 Classification of Locations.
(A) Below Floor Level. Any pit or depression below the level of the hangar floor shall be classified as a Class I, Division 1 or Zone 1 location that extends up to said floor level.
(B) Areas Not Cut Off or Ventilated. The entire area of the hangar, including any adjacent and communicating area not suitably cut off from the hangar, shall be classified as a Class I, Division 2 or Zone 2 location up to a level 18 inches (450 mm) above the floor.
(C) Vicinity of Aircraft. The area within 1.5 m (5 ft) horizontally from aircraft power plants or aircraft fuel tanks shall be classified as a Class I, Division 2 or Zone 2 location that extends upward from the floor to a level 1.5 m (5 ft) above the upper surface of wings and of engine enclosures .
(D) Areas Suitably Cut Off and Ventilated. Adjacent areas in which flammable liquids or vapors are not likely to be released, such as stock rooms and electrical control rooms, shall be unclassified where adequately ventilated and effectively cut off by walls or partitions.
513.7 Wiring and Equipment Not Installed in Class I Locations. (E) Lampholders of metal-shell, fiber-lined types shall not be used for fixed incandescent lighting. (F) Portable lighting equipment used inside aircraft or within a Class I location shall be identified for the location .
513.12 Ground-Fault Circuit-Interrupter Protection for Personnel. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in areas where electrical diagnostic equipment, electrical hand tools, or portable lighting equipment are to be used shall have GFCI protection.
513.16 Grounding and Bonding applies 501.30(A) within Class I locations.
Article 514 — Motor Fuel Dispensing Facilities
514.3 Classification of Locations. Classified locations are as specified in Table 514.3(B)(1) for dispensing devices, and Table 514.3(B)(2) for compressed natural gas, liquefied natural gas, and liquefied petroleum gas dispensing.
Selected values from Table 514.3(B)(1) for a dispenser other than an overhead type:
Location Extent Classification
Under the dispenser — the pit or space below the dispenser Any pit, box, or space below grade, any part within the Division 1 or 2 area Class I, Division 1
Dispenser enclosure Entire interior of the dispenser enclosure and 18 inches horizontally in all directions extending to grade Class I, Division 1
Outdoor dispenser Up to 18 inches (450 mm) above grade level within 20 feet (6.0 m) horizontally of any edge of the enclosure Class I, Division 2
Remote pump, outdoor Any pit, box, or space below grade level, any part within the Division 1 or 2 area Class I, Division 1
- Remote pump, outdoor Within 3 feet of any edge of pump, extending in all directions Class I, Division 2
- Vent — discharging upward Sphere of 3 feet radius from the open end Class I, Division 1
- Vent — discharging upward Sphere from 3 feet to 5 feet radius from the open end Class I, Division 2
514.8 Underground Wiring. Underground wiring shall be installed in threaded rigid metal conduit or threaded steel intermediate metal conduit . Any portion of electrical wiring that is below the surface of a Class I, Division 1 or Division 2 location shall be considered to be within a Class I, Division 1 location that shall extend at least to the point of emergence above grade.
Exception No. 1: Type MI cable shall be permitted where it is installed in accordance with Article 332.
Exception No. 2: Rigid nonmetallic conduit shall be permitted where buried under not less than 600 mm (2 ft) of cover. Where rigid nonmetallic conduit is used, threaded rigid metal conduit or threaded steel intermediate metal conduit shall be used for the last 600 mm (2 ft) of the underground run to emergence or to the point of connection to the aboveground raceway , and an equipment grounding conductor shall be included to provide electrical continuity of the raceway system and for grounding of non-current-carrying metal parts.
514.9 Sealing. (A) A listed seal shall be provided in each conduit run entering or leaving a dispenser or any cavity or enclosure in direct communication therewith. The sealing fitting shall be the first fitting after the conduit emerges from the earth or concrete . (B) Additional seals shall be provided in accordance with 501.15, and 501.15(B)(2) shall apply to horizontal as well as vertical boundaries of the defined Class I locations.
514.11 Circuit Disconnects.
(A) General. Each circuit leading to or through dispensing equipment, including equipment for remote pumping systems, shall be provided with a clearly identified and readily accessible switch or other acceptable means, located remote from the dispensing devices, to disconnect simultaneously from the source of supply all conductors of the circuits, including the grounded conductor, if any .
(B) Attended Self-Service Motor Fuel Dispensing Facilities. Emergency controls as specified in 514.11(A) shall be installed at a location acceptable to the authority having jurisdiction, but controls shall not be more than 30 m (100 ft) from dispensers .
(C) Unattended Self-Service Motor Fuel Dispensing Facilities. Emergency controls as specified in 514.11(A) shall be installed at a location acceptable to the authority having jurisdiction, but the controls shall be more than 6 m (20 ft) but less than 30 m (100 ft) from the dispensers . Additional emergency controls shall be installed on each group of dispensers or the outdoor equipment used to control the dispensers.
The requirement that the disconnect open the grounded conductor as well is unusual in the Code and is a reliable exam item. It exists because leaving a neutral connected to a damaged dispenser can maintain an ignition source.
514.13 Maintenance and Service of Dispensing Equipment. Each dispensing device shall be provided with a means to remove all external voltage sources, including feedback, during periods of maintenance and service of the dispensing equipment.
514.16 Grounding and Bonding applies 501.30(A) in Class I locations.
Article 515 — Bulk Storage Plants
515.1 Scope. Article 515 covers a property or portion of a property where flammable liquids are received by tank vessel, pipelines, tank car, or tank vehicle and are stored or blended in bulk for the purpose of distributing such liquids by tank vessel, pipeline, tank car, tank vehicle, portable tank, or container.
515.3 and Table 515.3 classify the locations, including tank vehicle and tank car loading and unloading areas, the interior of tanks, and pits and sumps.
515.8 Underground Wiring parallels 514.8: threaded RMC or threaded steel IMC, with an exception for rigid nonmetallic conduit buried under not less than 2 feet of cover with the last 2 feet in threaded metal conduit and an equipment grounding conductor included.
515.16 Grounding and Bonding. All metal raceways, cable armor, and non-current-carrying metal parts shall be bonded per 501.30(A) in Class I locations.
Article 516 — Spray Application, Dipping, Coating, and Printing Processes Using Flammable or Combustible Materials
516.4 and Table 516.4 classify spray areas. In an open spray area the space within 5 feet (1.5 m) in all directions from the spray area is Class I or Class II, Division 1, and beyond that, extending 5 feet horizontally and upward to a height of 3 feet above the floor, is Division 2, subject to the specific configuration.
516.7 Wiring and Equipment Not Within Classified Locations. (A) Wiring above classified locations shall be in metal raceways, PVC, RTRC, or Type MI, MC, or TC cable. (B) Equipment that may produce arcs, sparks, or particles of hot metal, located above the classified location or above a location where readily ignitible residues may be deposited, shall be of the totally enclosed type or be so constructed as to prevent escape of sparks or hot metal particles.
516.10 Special Equipment covers spray application equipment, electrostatic equipment, and powder coating, with detailed requirements including minimum clearances between goods being coated and electrodes, and interlocks that de-energize the high-voltage supply when ventilation fails.