8.4 Equipment Grounding Conductors (EGC) Sizing & Identification

Alabama Journeyman Electrician Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Licensing, Exam Strategy & General Electrical Theory

1.1 Alabama Electrical Licensing, AECB Regulations & Prov Exam Structure 1.2 Electrical Fundamentals, Ohm's Law, Joule's Law & Power Formulas 1.3 Circuit Analysis: Series, Parallel & Combination Circuits

2 Chapter 2: NEC General Requirements, Working Spaces & Trade Knowledge

2.1 NEC Structure, Article 90 & Mandatory Article 100 Definitions 2.2 Electrical Equipment Spaces, Working Clearances & Dedicated Spaces 2.3 Electrical Connections, Terminations & Temperature Ratings 2.4 Electrical Plans, Symbols, Test Instruments & Troubleshooting

3 Chapter 3: Branch Circuits & Receptacle Outlets

3.1 Branch Circuit Ratings, Multiwire Branch Circuits & Required Outlets 3.2 Receptacle Spacing & Placement Requirements 3.3 GFCI Protection Requirements 3.4 AFCI Protection Requirements & Tamper-Resistant Receptacles

4 Chapter 4: Feeders, Services & System Disconnects

4.1 Feeder Sizing, Demand Factors & Neutral Calculations 4.2 Service-Entrance Conductors & Service Disconnecting Means 4.3 Service Equipment Rating, Emergency Disconnects & Surge Protection

5 Chapter 5: Load Calculations

5.1 Standard Dwelling Unit Load Calculations 5.2 Optional Dwelling Unit Load Calculations 5.3 Commercial Load Calculations & Non-Dwelling Demands

6 Chapter 6: Conductors, Cables & Flexible Cords

6.1 Conductor Types, Insulation & Temperature Ratings 6.2 Conductor Ampacity Derating & Correction Factors 6.3 Nonmetallic-Sheathed Cable (Type NM) & Underground Feeder (Type UF) 6.4 Armored Cable (Type AC) & Metal-Clad Cable (Type MC) 6.5 Service-Entrance Cable (Types SE & USE), Other Cables & Flexible Cords

7 Chapter 7: Raceways, Conduit Fill & Enclosures

7.1 Conduit Systems: EMT, RMC, IMC, and PVC 7.2 Flexible Raceways: FMC, LFMC, and LFNC 7.3 Conduit Fill Calculations & Chapter 9 Tables 7.4 Outlet, Device & Junction Box Sizing 7.5 Wireways, Auxiliary Gutters, Surface Raceways & Cable Trays 7.6 Underground Raceways, ENT & Protection from Physical Damage

8 Chapter 8: Grounding & Bonding Systems

8.1 Grounding Electrode System & Grounding Electrodes 8.2 Grounding Electrode Conductor (GEC) Sizing & Installation 8.3 Main & System Bonding Jumpers 8.4 Equipment Grounding Conductors (EGC) Sizing & Identification

9 Chapter 9: Overcurrent Protection & Ground-Fault Protection

9.1 Standard Fuse & Circuit Breaker Ratings & Sizing 9.2 Small Conductor Rules & Overcurrent Exceptions 9.3 Tap Rules & Ground-Fault Protection of Equipment

10 Chapter 10: Motors, Motor Circuits & Transformers

10.1 Motor Conductor Sizing & Full-Load Current Tables 10.2 Motor Overload Protection 10.3 Motor Branch-Circuit Short-Circuit & Ground-Fault Protection 10.4 Transformer Sizing, Installation & Overcurrent Protection

11 Chapter 11: Special Occupancies, Hazardous Locations & Special Equipment

11.1 Hazardous (Classified) Locations: Class I, II, III 11.2 Healthcare Facilities & Patient Care Spaces 11.3 Swimming Pools, Spas & Hot Tubs 11.4 Agricultural Buildings, Mobile Homes, Marinas & RV Parks 11.5 Appliances, Electric Space Heating, Water Heaters & Special Equipment

12 Chapter 12: Lighting, Signs, Low Voltage, Communications & Safety

12.1 Luminaires, Lighting Outlets & Electric Signs 12.2 Fire Alarm Systems, Class 1, 2, 3 Circuits & Power-Limited Cables 12.3 Solar Photovoltaic (PV) & Energy Storage Systems 12.4 Electrical Safety, OSHA Regulations & NFPA 70E Fundamentals 12.5 Communications, CATV & Optical Fiber Systems (NEC Chapter 8) 12.6 OSHA Electrical Standards, Lockout/Tagout & Jobsite Safety

8.4 Equipment Grounding Conductors (EGC) Sizing & Identification

Key Takeaways Explain This Topic AI

An Equipment Grounding Conductor (EGC) connects non-current-carrying metal parts of equipment, raceways, and enclosures to the system grounded conductor at the service or source to ensure ground faults are cleared immediately.

NEC 250.118 recognizes specific types of EGCs, including copper/aluminum wire, rigid metal conduit (RMC), intermediate metal conduit (IMC), electrical metallic tubing (EMT), and listed cable armor.

NEC 250.119 mandates that EGCs be bare, covered with green insulation, or covered with green insulation having one or more yellow stripes; conductors 4 AWG and larger are permitted to be permanently re-identified at terminations with green tape.

EGCs are sized under NEC Table 250.122 based solely on the rating or setting of the automatic overcurrent protective device (fuse or circuit breaker) protecting the circuit.

Under NEC 250.122(B), whenever ungrounded circuit conductors are increased in size for voltage drop or temperature correction, wire-type EGCs must be proportionally increased in circular mil area.

Last updated: September 2026

  • 8.4 Equipment Grounding Conductors (EGC) Sizing & Identification
  • 1. Function and Purpose of EGCs (NEC Article 100 & 250.4(A)(3))

NEC Article 100 defines the Equipment Grounding Conductor (EGC) as the conductive path(s) that provides a ground-fault current path and connects normally non-current-carrying metal parts of equipment together and to the system grounded conductor or to the grounding electrode conductor, or both.

Under normal conditions, an EGC carries zero current. Its sole function is to return fault current back to the system neutral, permitting high currents to trip breakers in fractions of a second.

2. Approved Types of Equipment Grounding Conductors (NEC 250.118)

NEC 250.118 recognizes 14 distinct materials and wiring methods as approved Equipment Grounding Conductors:

Wire Conductors : Copper, aluminum, or copper-clad aluminum; solid or stranded; insulated, covered, or bare.

Rigid Metal Conduit (RMC) & Intermediate Metal Conduit (IMC) : Heavy-wall threaded steel conduits provide approved ground paths without an internal wire.

Electrical Metallic Tubing (EMT) : Fully approved as an equipment grounding conductor by itself, provided couplings and connectors are made up wrench-tight.

Flexible Metal Conduit (FMC) : Permitted as an EGC only where listed, installed with listed grounding fittings, protected by an OCPD rated 20 amperes or less , length not exceeding 6 feet (1.8 m) , and where flexibility is not required.

Liquidtight Flexible Metal Conduit (LFMC) : Permitted as an EGC only where listed with listed grounding fittings, length not exceeding 6 feet , and OCPD ratings not exceeding 20 amperes for 3/8-in and 1/2-in sizes, or 60 amperes for 3/4-in through 1-1/4-in sizes (where flexibility is not required).

Cable Armor : Armor of Type AC cable; listed Type MC cable with interlocked armor and internal bare aluminum grounding tape in continuous contact with armor, or smooth/corrugated metallic sheaths.

3. Conductor Identification and Re-Identification Rules (NEC 250.119)

NEC 250.119 establishes strict color-coding rules for wire-type Equipment Grounding Conductors:

Permitted Finishes : Bare, continuous green outer insulation, or green insulation with one or more continuous yellow stripes.

Conductors 6 AWG and Smaller : Must have factory-extruded continuous green outer finish or green with yellow stripes along their entire length (or be bare). Re-identifying conductors 6 AWG or smaller with green tape is strictly prohibited.

Conductors 4 AWG and Larger (NEC 250.119(A)) : Conductors 4 AWG and larger are permitted to be permanently re-identified as an EGC at each termination and accessible point using green tape, green paint, or green adhesive labels.

4. Sizing EGCs Using NEC Table 250.122

Unlike the GEC (sized from Table 250.66 by conductor size), the Equipment Grounding Conductor is sized strictly by the rating or setting of the automatic overcurrent protective device ahead of the equipment.

NEC Table 250.122: Minimum Size Equipment Grounding Conductors

Rating of Overcurrent Device Ahead of Equipment (Amperes) Minimum Size Copper EGC (AWG or kcmil) Minimum Size Aluminum / Copper-Clad EGC (AWG or kcmil)

  • 15 A 14 AWG 12 AWG
  • 20 A 12 AWG 10 AWG
  • 30 A 10 AWG 8 AWG
  • 40 A / 60 A 10 AWG 8 AWG
  • 100 A 8 AWG 6 AWG
  • 200 A 6 AWG 4 AWG
  • 400 A 3 AWG 1 AWG
  • 600 A 1 AWG 2/0 AWG
  • 800 A 1/0 AWG 3/0 AWG
  • 5. Proportional Up-Sizing for Voltage Drop (NEC 250.122(B))

Under NEC 250.122(B) , where phase conductors are enlarged for voltage drop, wire-type EGCs must be proportionally increased in circular mils.

The Proportional Formula Required EGC Circular Mils = Actual (New) Phase Circular Mils Original Minimum Phase Circular Mils × Table 250.122 Minimum EGC Circular Mils \text{Required EGC Circular Mils} = \frac{\text{Actual (New) Phase Circular Mils}}{\text{Original Minimum Phase Circular Mils}} \times \text{Table 250.122 Minimum EGC Circular Mils} Required EGC Circular Mils = Original Minimum Phase Circular Mils Actual (New) Phase Circular Mils ​ × Table 250.122 Minimum EGC Circular Mils

Relevant Conductor Circular Mils (NEC Chapter 9, Table 8)

14 AWG = 4,110 cmils 4{,}110\text{ cmils} 4 , 110 cmils ; 12 AWG = 6,530 cmils 6{,}530\text{ cmils} 6 , 530 cmils ; 10 AWG = 10,380 cmils 10{,}380\text{ cmils} 10 , 380 cmils ; 8 AWG = 16,510 cmils 16{,}510\text{ cmils} 16 , 510 cmils ; 6 AWG = 26,240 cmils 26{,}240\text{ cmils} 26 , 240 cmils ; 4 AWG = 41,740 cmils 41{,}740\text{ cmils} 41 , 740 cmils

Worked Example 1: Voltage Drop Calculation

A 30A branch circuit protected by a 30A breaker supplies equipment 350 feet away. The minimum phase conductor is 10 AWG copper ( 10,380 cmils 10{,}380\text{ cmils} 10 , 380 cmils ), and Table 250.122 requires a 10 AWG copper EGC ( 10,380 cmils 10{,}380\text{ cmils} 10 , 380 cmils ). To limit voltage drop to under 3%, phase conductors are up-sized to 4 AWG copper ( 41,740 cmils 41{,}740\text{ cmils} 41 , 740 cmils ).

Calculate expansion ratio : Ratio = 41,740 cmils 10,380 cmils ≈ 4.0212 \text{Ratio} = \frac{41{,}740\text{ cmils}}{10{,}380\text{ cmils}} \approx 4.0212 Ratio = 10 , 380 cmils 41 , 740 cmils ​ ≈ 4.0212

Calculate required EGC area : New EGC Area = 4.0212 × 10,380 cmils = 41,740 cmils \text{New EGC Area} = 4.0212 \times 10{,}380\text{ cmils} = 41{,}740\text{ cmils} New EGC Area = 4.0212 × 10 , 380 cmils = 41 , 740 cmils

Select conductor from Table 8 :

A 6 AWG conductor is only 26,240 cmils 26{,}240\text{ cmils} 26 , 240 cmils . A 4 AWG copper conductor ( 41,740 cmils 41{,}740\text{ cmils} 41 , 740 cmils ) must be installed as the equipment grounding conductor.

6. Sizing EGCs in Multiple Parallel Raceways (NEC 250.122(F))

Under NEC 250.122(F)(1) , where circuit conductors are installed in parallel in multiple raceways or cables, the wire-type equipment grounding conductor installed in each raceway must be sized based on the full rating of the overcurrent protective device protecting the entire circuit .

Worked Example 2: Parallel Feeder Raceways

An 800-ampere feeder protected by an 800A breaker is installed in two parallel IMC raceways with 500 kcmil copper conductors.

Dividing EGC size among raceways is prohibited.

Per Table 250.122, an 800A overcurrent device requires a 1/0 AWG copper (or 3/0 AWG aluminum) equipment grounding conductor.

A full-size 1/0 AWG copper EGC must be installed in each parallel raceway to carry fault current safely.