Study guide

1.3 Circuit Analysis: Series, Parallel & Combination Circuits

Alabama Journeyman Electrician Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Licensing, Exam Strategy & General Electrical Theory

1.1 Alabama Electrical Licensing, AECB Regulations & Prov Exam Structure 1.2 Electrical Fundamentals, Ohm's Law, Joule's Law & Power Formulas 1.3 Circuit Analysis: Series, Parallel & Combination Circuits

2 Chapter 2: NEC General Requirements, Working Spaces & Trade Knowledge

2.1 NEC Structure, Article 90 & Mandatory Article 100 Definitions 2.2 Electrical Equipment Spaces, Working Clearances & Dedicated Spaces 2.3 Electrical Connections, Terminations & Temperature Ratings 2.4 Electrical Plans, Symbols, Test Instruments & Troubleshooting

3 Chapter 3: Branch Circuits & Receptacle Outlets

3.1 Branch Circuit Ratings, Multiwire Branch Circuits & Required Outlets 3.2 Receptacle Spacing & Placement Requirements 3.3 GFCI Protection Requirements 3.4 AFCI Protection Requirements & Tamper-Resistant Receptacles

4 Chapter 4: Feeders, Services & System Disconnects

4.1 Feeder Sizing, Demand Factors & Neutral Calculations 4.2 Service-Entrance Conductors & Service Disconnecting Means 4.3 Service Equipment Rating, Emergency Disconnects & Surge Protection

5 Chapter 5: Load Calculations

5.1 Standard Dwelling Unit Load Calculations 5.2 Optional Dwelling Unit Load Calculations 5.3 Commercial Load Calculations & Non-Dwelling Demands

6 Chapter 6: Conductors, Cables & Flexible Cords

6.1 Conductor Types, Insulation & Temperature Ratings 6.2 Conductor Ampacity Derating & Correction Factors 6.3 Nonmetallic-Sheathed Cable (Type NM) & Underground Feeder (Type UF) 6.4 Armored Cable (Type AC) & Metal-Clad Cable (Type MC) 6.5 Service-Entrance Cable (Types SE & USE), Other Cables & Flexible Cords

7 Chapter 7: Raceways, Conduit Fill & Enclosures

7.1 Conduit Systems: EMT, RMC, IMC, and PVC 7.2 Flexible Raceways: FMC, LFMC, and LFNC 7.3 Conduit Fill Calculations & Chapter 9 Tables 7.4 Outlet, Device & Junction Box Sizing 7.5 Wireways, Auxiliary Gutters, Surface Raceways & Cable Trays 7.6 Underground Raceways, ENT & Protection from Physical Damage

8 Chapter 8: Grounding & Bonding Systems

8.1 Grounding Electrode System & Grounding Electrodes 8.2 Grounding Electrode Conductor (GEC) Sizing & Installation 8.3 Main & System Bonding Jumpers 8.4 Equipment Grounding Conductors (EGC) Sizing & Identification

9 Chapter 9: Overcurrent Protection & Ground-Fault Protection

9.1 Standard Fuse & Circuit Breaker Ratings & Sizing 9.2 Small Conductor Rules & Overcurrent Exceptions 9.3 Tap Rules & Ground-Fault Protection of Equipment

10 Chapter 10: Motors, Motor Circuits & Transformers

10.1 Motor Conductor Sizing & Full-Load Current Tables 10.2 Motor Overload Protection 10.3 Motor Branch-Circuit Short-Circuit & Ground-Fault Protection 10.4 Transformer Sizing, Installation & Overcurrent Protection

11 Chapter 11: Special Occupancies, Hazardous Locations & Special Equipment

11.1 Hazardous (Classified) Locations: Class I, II, III 11.2 Healthcare Facilities & Patient Care Spaces 11.3 Swimming Pools, Spas & Hot Tubs 11.4 Agricultural Buildings, Mobile Homes, Marinas & RV Parks 11.5 Appliances, Electric Space Heating, Water Heaters & Special Equipment

12 Chapter 12: Lighting, Signs, Low Voltage, Communications & Safety

12.1 Luminaires, Lighting Outlets & Electric Signs 12.2 Fire Alarm Systems, Class 1, 2, 3 Circuits & Power-Limited Cables 12.3 Solar Photovoltaic (PV) & Energy Storage Systems 12.4 Electrical Safety, OSHA Regulations & NFPA 70E Fundamentals 12.5 Communications, CATV & Optical Fiber Systems (NEC Chapter 8) 12.6 OSHA Electrical Standards, Lockout/Tagout & Jobsite Safety

1.3 Circuit Analysis: Series, Parallel & Combination Circuits

Key Takeaways Explain This Topic AI

In a series circuit, current remains constant throughout all components, while total circuit resistance equals the sum of individual resistances (R_total = R1 + R2 + R3) and total applied voltage equals the sum of individual voltage drops.

In a parallel circuit, voltage across every branch is identical to the source voltage, total current equals the sum of all branch currents, and equivalent resistance is always less than the lowest individual branch resistance.

Kirchhoff's Voltage Law (KVL) dictates that the algebraic sum of voltages around any closed loop is zero, while Kirchhoff's Current Law (KCL) dictates that total current entering an electrical junction equals total current leaving it.

The National Electrical Code recommends in Informational Notes 210.19(A) and 215.2(A)(1) that conductor voltage drop should not exceed 3% on branch circuits or feeders, and no more than 5% overall from service disconnect to the farthest outlet.

Conductor voltage drop is calculated using VD = (2 * K * I * D) / CM for single-phase systems and VD = (1.732 * K * I * D) / CM for three-phase systems, where K equals 12.9 for copper and 21.2 for aluminum.

Last updated: September 2026

  • 1.3 Circuit Analysis: Series, Parallel & Combination Circuits
  • Fundamental Circuit Topologies and Series Configurations

Electrical systems route current through networks classified as series, parallel, or combination circuits. A series circuit provides a single continuous pathway for electron flow. Because charge cannot accumulate along an unbroken loop, current is constant across every component:

Current Law : I total = I 1 = I 2 = I 3 = ⋯ = I n I_{\text{total}} = I_1 = I_2 = I_3 = \dots = I_n I total ​ = I 1 ​ = I 2 ​ = I 3 ​ = ⋯ = I n ​

Total Resistance : Opposition to current flow is cumulative, meaning total resistance equals the sum of individual resistances: R total = R 1 + R 2 + R 3 + ⋯ + R n R_{\text{total}} = R_1 + R_2 + R_3 + \dots + R_n R total ​ = R 1 ​ + R 2 ​ + R 3 ​ + ⋯ + R n ​

Voltage Division : Applied voltage distributes across components proportionally to individual resistance: E total = E 1 + E 2 + E 3 + ⋯ + E n E_{\text{total}} = E_1 + E_2 + E_3 + \dots + E_n E total ​ = E 1 ​ + E 2 ​ + E 3 ​ + ⋯ + E n ​ E x = E total × ( R x R total ) E_x = E_{\text{total}} \times \left(\frac{R_x}{R_{\text{total}}}\right) E x ​ = E total ​ × ( R total ​ R x ​ ​ )

In field installations, loose terminations or corroded splices act as high-resistance series elements, causing unwanted voltage drop and dangerous localized thermal buildup.

Parallel Circuit Configurations and Branch Laws

A parallel circuit connects multiple devices across identical common nodes, providing separate conductive pathways for current:

Voltage Law : Because all branches connect across the same terminals, full source voltage appears across every branch: E total = E 1 = E 2 = E 3 = ⋯ = E n E_{\text{total}} = E_1 = E_2 = E_3 = \dots = E_n E total ​ = E 1 ​ = E 2 ​ = E 3 ​ = ⋯ = E n ​

Current Law : Total current equals the sum of individual branch currents: I total = I 1 + I 2 + I 3 + ⋯ + I n I_{\text{total}} = I_1 + I_2 + I_3 + \dots + I_n I total ​ = I 1 ​ + I 2 ​ + I 3 ​ + ⋯ + I n ​

Equivalent Resistance : Adding parallel branches creates additional paths, reducing overall opposition to current flow. Equivalent circuit resistance ( R eq R_{\text{eq}} R eq ​ ) is always less than the lowest branch resistance:

Reciprocal Formula : 1 R eq = 1 R 1 + 1 R 2 + ⋯ + 1 R n ⟹ R eq = 1 1 R 1 + 1 R 2 + ⋯ + 1 R n \frac{1}{R_{\text{eq}}} = \frac{1}{R_1} + \frac{1}{R_2} + \dots + \frac{1}{R_n} \implies R_{\text{eq}} = \frac{1}{\frac{1}{R_1} + \frac{1}{R_2} + \dots + \frac{1}{R_n}} R eq ​ 1 ​ = R 1 ​ 1 ​ + R 2 ​ 1 ​ + ⋯ + R n ​ 1 ​ ⟹ R eq ​ = R 1 ​ 1 ​ + R 2 ​ 1 ​ + ⋯ + R n ​ 1 ​ 1 ​

Product-Over-Sum Formula (two branches): R eq = R 1 × R 2 R 1 + R 2 R_{\text{eq}} = \frac{R_1 \times R_2}{R_1 + R_2} R eq ​ = R 1 ​ + R 2 ​ R 1 ​ × R 2 ​ ​

Equal Resistance Formula (for n n n identical resistors R R R ): R eq = R n R_{\text{eq}} = \frac{R}{n} R eq ​ = n R ​

Kirchhoff's Laws in Electrical Circuit Analysis

Complex networks follow Gustav Kirchhoff's two governing theorems:

Kirchhoff's Current Law (KCL / Node Rule) : The algebraic sum of currents entering and exiting an electrical node equals zero ( ∑ I in = ∑ I out \sum I_{\text{in}} = \sum I_{\text{out}} ∑ I in ​ = ∑ I out ​ ). Current entering a junction must balance across departing conductor paths.

Kirchhoff's Voltage Law (KVL / Loop Rule) : The algebraic sum of voltages around any closed conductive loop equals zero ( ∑ E source − ∑ V drops = 0 \sum E_{\text{source}} - \sum V_{\text{drops}} = 0 ∑ E source ​ − ∑ V drops ​ = 0 ). KVL is applied in field diagnostics to verify loop drops and ground-fault paths.

Combination (Series-Parallel) Network Reduction Technique

Combination circuits require systematic five-step reduction:

Identify Isolated Clusters : Locate purely parallel or series resistor groups furthest from the supply.

Calculate Equivalent Values : Resolve isolated clusters into single equivalent resistances.

Simplify Schematic : Repeat reductions until collapsing into a single equivalent resistance ( R total R_{\text{total}} R total ​ ).

Determine Source Current : Calculate source current using Ohm's Law ( I total = E source / R total I_{\text{total}} = E_{\text{source}} / R_{\text{total}} I total ​ = E source ​ / R total ​ ).

Expand Backward : Trace backward through the circuit to solve individual component voltage drops and branch currents.

Conductor Resistance and Circular Mil Area

Every electrical conductor possesses internal resistance that creates voltage drop over distance. Resistance depends on material resistivity, length, and cross-sectional area: R = K × L CM R = \frac{K \times L}{\text{CM}} R = CM K × L ​

K K K : Specific resistivity in ohms per circular mil-foot at 75 ∘ C 75^\circ\text{C} 7 5 ∘ C :

  • Copper: K = 12.9 Ω ⋅ cmil/ft K = 12.9\,\Omega\cdot\text{cmil/ft} K = 12.9 Ω ⋅ cmil/ft
  • Aluminum: K = 21.2 Ω ⋅ cmil/ft K = 21.2\,\Omega\cdot\text{cmil/ft} K = 21.2 Ω ⋅ cmil/ft

L L L : One-way length of the conductor run in feet.

CM \text{CM} CM : Conductor cross-sectional area in circular mils ( 1 mil = 0.001 inch 1\text{ mil} = 0.001\text{ inch} 1 mil = 0.001 inch ; CM = d 2 \text{CM} = d^2 CM = d 2 ). Exact areas are listed in NEC Chapter 9, Table 8.

NEC Voltage Drop Standards and Formulas

Excessive voltage drop causes motor overheating, relay chatter, and lumen loss. NEC Informational Notes 210.19(A) Note 4 and 215.2(A)(1) Note 2 recommend sizing conductors so voltage drop does not exceed:

3% on branch circuits (or feeders) at the farthest connected outlet.

5% total overall voltage drop combining feeder and branch conductors to the final load.

Standard Journeyman calculation formulas:

Single-Phase Circuits : V D = 2 × K × I × D CM VD = \frac{2 \times K \times I \times D}{\text{CM}} V D = CM 2 × K × I × D ​

Three-Phase Balanced Circuits : V D = 3 × K × I × D CM = 1.732 × K × I × D CM VD = \frac{\sqrt{3} \times K \times I \times D}{\text{CM}} = \frac{1.732 \times K \times I \times D}{\text{CM}} V D = CM 3 ​ × K × I × D ​ = CM 1.732 × K × I × D ​

Minimum Conductor Sizing for Maximum Allowable Voltage Drop :

Single-Phase: CM = 2 × K × I × D V D allowed \text{CM} = \frac{2 \times K \times I \times D}{VD_{\text{allowed}}} CM = V D allowed ​ 2 × K × I × D ​

Three-Phase: CM = 1.732 × K × I × D V D allowed \text{CM} = \frac{1.732 \times K \times I \times D}{VD_{\text{allowed}}} CM = V D allowed ​ 1.732 × K × I × D ​

  • Step-by-Step Worked Calculations
  • Worked Calculation 1: Combination Circuit Reduction

A 120-volt source supplies a circuit containing a 10 Ω 10\,\Omega 10 Ω series resistor ( R 1 R_1 R 1 ​ ) connected in series with a parallel pair consisting of R 2 = 30 Ω R_2 = 30\,\Omega R 2 ​ = 30 Ω and R 3 = 60 Ω R_3 = 60\,\Omega R 3 ​ = 60 Ω .

Equivalent parallel resistance : R 23 = 30 × 60 30 + 60 = 1800 90 = 20 Ω R_{23} = \frac{30 \times 60}{30 + 60} = \frac{1800}{90} = 20\,\Omega R 23 ​ = 30 + 60 30 × 60 ​ = 90 1800 ​ = 20 Ω

Total circuit resistance : R total = R 1 + R 23 = 10 + 20 = 30 Ω R_{\text{total}} = R_1 + R_{23} = 10 + 20 = 30\,\Omega R total ​ = R 1 ​ + R 23 ​ = 10 + 20 = 30 Ω

Total circuit current : I total = 120 V 30 Ω = 4.0 Amperes I_{\text{total}} = \frac{120\text{ V}}{30\,\Omega} = 4.0\text{ Amperes} I total ​ = 30 Ω 120 V ​ = 4.0 Amperes

Component voltage drops : E 1 = 4.0 A × 10 Ω = 40 Volts E_1 = 4.0\text{ A} \times 10\,\Omega = 40\text{ Volts} E 1 ​ = 4.0 A × 10 Ω = 40 Volts E 23 = 120 V − 40 V = 80 Volts E_{23} = 120\text{ V} - 40\text{ V} = 80\text{ Volts} E 23 ​ = 120 V − 40 V = 80 Volts

Branch currents : I 2 = 80 V 30 Ω = 2.67 A ; I 3 = 80 V 60 Ω = 1.33 A I_2 = \frac{80\text{ V}}{30\,\Omega} = 2.67\text{ A}; \quad I_3 = \frac{80\text{ V}}{60\,\Omega} = 1.33\text{ A} I 2 ​ = 30 Ω 80 V ​ = 2.67 A ; I 3 ​ = 60 Ω 80 V ​ = 1.33 A Verifying KCL : 2.67 A + 1.33 A = 4.0 Amperes 2.67\text{ A} + 1.33\text{ A} = 4.0\text{ Amperes} 2.67 A + 1.33 A = 4.0 Amperes .

Worked Calculation 2: Feeder Sizing for Voltage Drop Compliance

A 240-volt single-phase feeder supplies a continuous 45-ampere load over 200 feet using copper conductors ( K = 12.9 K = 12.9 K = 12.9 ). Limit voltage drop to 3%.

Allowable voltage drop : V D allowed = 240 V × 0.03 = 7.2 Volts VD_{\text{allowed}} = 240\text{ V} \times 0.03 = 7.2\text{ Volts} V D allowed ​ = 240 V × 0.03 = 7.2 Volts

Required circular mils : CM = 2 × 12.9 × 45 × 200 7.2 = 232 , 200 7.2 = 32 , 250 cmil \text{CM} = \frac{2 \times 12.9 \times 45 \times 200}{7.2} = \frac{232,200}{7.2} = 32,250\text{ cmil} CM = 7.2 2 × 12.9 × 45 × 200 ​ = 7.2 232 , 200 ​ = 32 , 250 cmil

NEC Chapter 9, Table 8 Evaluation :

#6 AWG copper = 26 , 240 cmil 26,240\text{ cmil} 26 , 240 cmil ( V D = 8.85 V VD = 8.85\text{V} V D = 8.85 V or 3.69 % 3.69\% 3.69% , exceeds limit)

#4 AWG copper = 41 , 740 cmil 41,740\text{ cmil} 41 , 740 cmil ( V D = 5.56 V VD = 5.56\text{V} V D = 5.56 V or 2.32 % 2.32\% 2.32% , compliant)

Conclusion : Install #4 AWG copper conductors to meet the 3% threshold.