Study guide
1.2 Electrical Fundamentals, Ohm's Law, Joule's Law & Power Formulas
Alabama Journeyman Electrician Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Licensing, Exam Strategy & General Electrical Theory
1.1 Alabama Electrical Licensing, AECB Regulations & Prov Exam Structure 1.2 Electrical Fundamentals, Ohm's Law, Joule's Law & Power Formulas 1.3 Circuit Analysis: Series, Parallel & Combination Circuits
2 Chapter 2: NEC General Requirements, Working Spaces & Trade Knowledge
2.1 NEC Structure, Article 90 & Mandatory Article 100 Definitions 2.2 Electrical Equipment Spaces, Working Clearances & Dedicated Spaces 2.3 Electrical Connections, Terminations & Temperature Ratings 2.4 Electrical Plans, Symbols, Test Instruments & Troubleshooting
3 Chapter 3: Branch Circuits & Receptacle Outlets
3.1 Branch Circuit Ratings, Multiwire Branch Circuits & Required Outlets 3.2 Receptacle Spacing & Placement Requirements 3.3 GFCI Protection Requirements 3.4 AFCI Protection Requirements & Tamper-Resistant Receptacles
4 Chapter 4: Feeders, Services & System Disconnects
4.1 Feeder Sizing, Demand Factors & Neutral Calculations 4.2 Service-Entrance Conductors & Service Disconnecting Means 4.3 Service Equipment Rating, Emergency Disconnects & Surge Protection
5 Chapter 5: Load Calculations
5.1 Standard Dwelling Unit Load Calculations 5.2 Optional Dwelling Unit Load Calculations 5.3 Commercial Load Calculations & Non-Dwelling Demands
6 Chapter 6: Conductors, Cables & Flexible Cords
6.1 Conductor Types, Insulation & Temperature Ratings 6.2 Conductor Ampacity Derating & Correction Factors 6.3 Nonmetallic-Sheathed Cable (Type NM) & Underground Feeder (Type UF) 6.4 Armored Cable (Type AC) & Metal-Clad Cable (Type MC) 6.5 Service-Entrance Cable (Types SE & USE), Other Cables & Flexible Cords
7 Chapter 7: Raceways, Conduit Fill & Enclosures
7.1 Conduit Systems: EMT, RMC, IMC, and PVC 7.2 Flexible Raceways: FMC, LFMC, and LFNC 7.3 Conduit Fill Calculations & Chapter 9 Tables 7.4 Outlet, Device & Junction Box Sizing 7.5 Wireways, Auxiliary Gutters, Surface Raceways & Cable Trays 7.6 Underground Raceways, ENT & Protection from Physical Damage
8 Chapter 8: Grounding & Bonding Systems
8.1 Grounding Electrode System & Grounding Electrodes 8.2 Grounding Electrode Conductor (GEC) Sizing & Installation 8.3 Main & System Bonding Jumpers 8.4 Equipment Grounding Conductors (EGC) Sizing & Identification
9 Chapter 9: Overcurrent Protection & Ground-Fault Protection
9.1 Standard Fuse & Circuit Breaker Ratings & Sizing 9.2 Small Conductor Rules & Overcurrent Exceptions 9.3 Tap Rules & Ground-Fault Protection of Equipment
10 Chapter 10: Motors, Motor Circuits & Transformers
10.1 Motor Conductor Sizing & Full-Load Current Tables 10.2 Motor Overload Protection 10.3 Motor Branch-Circuit Short-Circuit & Ground-Fault Protection 10.4 Transformer Sizing, Installation & Overcurrent Protection
11 Chapter 11: Special Occupancies, Hazardous Locations & Special Equipment
11.1 Hazardous (Classified) Locations: Class I, II, III 11.2 Healthcare Facilities & Patient Care Spaces 11.3 Swimming Pools, Spas & Hot Tubs 11.4 Agricultural Buildings, Mobile Homes, Marinas & RV Parks 11.5 Appliances, Electric Space Heating, Water Heaters & Special Equipment
12 Chapter 12: Lighting, Signs, Low Voltage, Communications & Safety
12.1 Luminaires, Lighting Outlets & Electric Signs 12.2 Fire Alarm Systems, Class 1, 2, 3 Circuits & Power-Limited Cables 12.3 Solar Photovoltaic (PV) & Energy Storage Systems 12.4 Electrical Safety, OSHA Regulations & NFPA 70E Fundamentals 12.5 Communications, CATV & Optical Fiber Systems (NEC Chapter 8) 12.6 OSHA Electrical Standards, Lockout/Tagout & Jobsite Safety
1.2 Electrical Fundamentals, Ohm's Law, Joule's Law & Power Formulas
Key Takeaways Explain This Topic AI
Ohm's Law governs the linear relationship between electromotive force (E in volts), current (I in amperes), and resistance (R in ohms) through the formulas E = I * R, I = E / R, and R = E / I.
Joule's Law (Watt's Law) quantifies electrical power (P in watts) as the rate of energy dissipation, expressed as P = E * I, P = I^2 * R, and P = E^2 / R.
Alternating current (AC) sinusoidal waveforms are quantified by their Root-Mean-Square (RMS) effective heating value, where V_RMS equals 0.707 multiplied by Peak Voltage (V_peak).
The AC power triangle interrelates apparent power (kVA), true power (kW), and reactive power (kVAR), defining power factor (PF) as the ratio of true power to apparent power (kW / kVA).
Three-phase true power is calculated using the formula P = 1.732 * V_line * I_line * PF, while mechanical motor output converts at exactly 746 watts per horsepower.
Last updated: September 2026
- 1.2 Electrical Fundamentals, Ohm's Law, Joule's Law & Power Formulas
- Core Electrical Quantities and Physical Definitions
Every electrical system operates on fundamental physical principles governing charge, force, and energy. Four primary quantities form the foundation of electrical trade analysis:
Electromotive Force ( E E E or V V V ) : Measured in volts ( V \text{V} V ), electromotive force is the electrical potential difference driving electrons through a conductor ( 1 V = 1 J/C 1\text{ V} = 1\text{ J/C} 1 V = 1 J/C ).
Electric Current ( I I I ) : Measured in amperes ( A \text{A} A ), current represents the rate of charge displacement. One ampere equals one coulomb flowing per second ( 1 A = 1 C/s = 6.242 × 10 18 electrons/second 1\text{ A} = 1\text{ C/s} = 6.242 \times 10^{18}\text{ electrons/second} 1 A = 1 C/s = 6.242 × 1 0 18 electrons/second ).
Electrical Resistance ( R R R ) : Measured in ohms ( Ω \Omega Ω ), resistance is the opposition offered by a material to electron flow, converting electrical energy into heat.
Electrical Power ( P P P ) : Measured in watts ( W \text{W} W ), power represents the rate of performing work ( 1 W = 1 J/s = 1 V × 1 A 1\text{ W} = 1\text{ J/s} = 1\text{ V} \times 1\text{ A} 1 W = 1 J/s = 1 V × 1 A ).
Ohm's Law and Algebraic Derivations
Formulated by Georg Simon Ohm, Ohm's Law establishes that current through a linear conductor is directly proportional to applied voltage and inversely proportional to circuit resistance: E = I × R E = I \times R E = I × R I = E R I = \frac{E}{R} I = R E R = E I R = \frac{E}{I} R = I E
Joule's Law and Power Equations
James Prescott Joule demonstrated that heat generation is proportional to resistance and the square of the current. Combining Ohm's Law with Joule's findings yields the primary power expressions: P = E × I P = E \times I P = E × I P = I 2 × R P = I^2 \times R P = I 2 × R P = E 2 R P = \frac{E^2}{R} P = R E 2
Solving for voltage and current from power and resistance: E = P × R E = \sqrt{P \times R} E = P × R I = P R I = \sqrt{\frac{P}{R}} I = R P
- Known Values Voltage ( E E E ) Current ( I I I ) Resistance ( R R R ) Power ( P P P )
- I , R I, R I , R E = I × R E = I \times R E = I × R — — P = I 2 × R P = I^2 \times R P = I 2 × R
- E , I E, I E , I — — R = E I R = \frac{E}{I} R = I E P = E × I P = E \times I P = E × I
- E , R E, R E , R — I = E R I = \frac{E}{R} I = R E — P = E 2 R P = \frac{E^2}{R} P = R E 2
- P , E P, E P , E — I = P E I = \frac{P}{E} I = E P R = E 2 P R = \frac{E^2}{P} R = P E 2 —
- P , I P, I P , I E = P I E = \frac{P}{I} E = I P — R = P I 2 R = \frac{P}{I^2} R = I 2 P —
- P , R P, R P , R E = P × R E = \sqrt{P \times R} E = P × R I = P R I = \sqrt{\frac{P}{R}} I = R P — —
- Alternating Current Fundamentals: Peak and RMS Values
Direct current maintains unidirectional flow, whereas alternating current periodically reverses direction following a sinusoidal waveform. In North American systems, generation operates at 60 Hertz ( 60 Hz 60\text{ Hz} 60 Hz ), yielding a cycle duration of 16.67 milliseconds 16.67\text{ milliseconds} 16.67 milliseconds .
Peak Voltage ( V peak V_{\text{peak}} V peak ) : Maximum instantaneous amplitude reached during the sinusoidal crest.
Peak-to-Peak Voltage ( V p-p V_{\text{p-p}} V p-p ) : Total voltage span between positive and negative alternating peaks ( V p-p = 2 × V peak V_{\text{p-p}} = 2 \times V_{\text{peak}} V p-p = 2 × V peak ).
Root-Mean-Square Voltage ( V RMS V_{\text{RMS}} V RMS ) : Because AC voltage varies continuously, peak values do not represent working thermal capacity. The RMS value provides the equivalent heating value of a DC system across an identical resistive load: V RMS = V peak 2 = 0.7071 × V peak V_{\text{RMS}} = \frac{V_{\text{peak}}}{\sqrt{2}} = 0.7071 \times V_{\text{peak}} V RMS = 2 V peak = 0.7071 × V peak V peak = 2 × V RMS = 1.4142 × V RMS V_{\text{peak}} = \sqrt{2} \times V_{\text{RMS}} = 1.4142 \times V_{\text{RMS}} V peak = 2 × V RMS = 1.4142 × V RMS
A nominal 120-volt AC circuit represents an RMS value whose waveform reaches peaks of 120 × 1.4142 = 169.7 volts 120 \times 1.4142 = 169.7\text{ volts} 120 × 1.4142 = 169.7 volts .
The AC Power Triangle: True, Reactive, and Apparent Power
In resistive AC circuits, current and voltage remain in phase ( θ = 0 ∘ \theta = 0^\circ θ = 0 ∘ ). In inductive circuits (motors, transformers), magnetic fields cause current to lag voltage. In capacitive circuits, current leads voltage. This phase angle divides AC power into three vector components:
True Power ( P P P ) : Expressed in watts ( W \text{W} W ) or kilowatts ( kW \text{kW} kW ), true power represents work converted to heat or mechanical output ( P = E × I × cos θ P = E \times I \times \cos\theta P = E × I × cos θ ).
Reactive Power ( Q Q Q ) : Expressed in volt-amperes reactive ( VAR \text{VAR} VAR ) or kilovars ( kVAR \text{kVAR} kVAR ), reactive power sustains electromagnetic fields without performing mechanical work.
Apparent Power ( S S S ) : Expressed in volt-amperes ( VA \text{VA} VA ) or kilovolt-amperes ( kVA \text{kVA} kVA ), apparent power is the vector sum of true and reactive power ( S = P 2 + Q 2 = E × I S = \sqrt{P^2 + Q^2} = E \times I S = P 2 + Q 2 = E × I ).
Power Factor ( PF \text{PF} PF ) : Ratio of true power to apparent power ( PF = P S = kW kVA = cos θ \text{PF} = \frac{P}{S} = \frac{\text{kW}}{\text{kVA}} = \cos\theta PF = S P = kVA kW = cos θ ). Low power factor requires larger conductors to deliver equivalent working wattage.
Three-Phase Calculations: Wye and Delta Systems
Three-phase systems deliver three sinusoidal voltages displaced by 120 electrical degrees, introducing the factor 3 ≈ 1.732 \sqrt{3} \approx 1.732 3 ≈ 1.732 :
Wye ( Y Y Y ) Systems : V line = 3 × V phase = 1.732 × V phase V_{\text{line}} = \sqrt{3} \times V_{\text{phase}} = 1.732 \times V_{\text{phase}} V line = 3 × V phase = 1.732 × V phase I line = I phase I_{\text{line}} = I_{\text{phase}} I line = I phase Typical configurations include 120 / 208 V 120/208\text{V} 120/208 V and 277 / 480 V 277/480\text{V} 277/480 V .
Delta ( Δ \Delta Δ ) Systems : V line = V phase V_{\text{line}} = V_{\text{phase}} V line = V phase I line = 3 × I phase = 1.732 × I phase I_{\text{line}} = \sqrt{3} \times I_{\text{phase}} = 1.732 \times I_{\text{phase}} I line = 3 × I phase = 1.732 × I phase
Three-Phase Power Equations :
Apparent Power: S = 3 × V line × I line S = \sqrt{3} \times V_{\text{line}} \times I_{\text{line}} S = 3 × V line × I line
True Power: P = 3 × V line × I line × PF P = \sqrt{3} \times V_{\text{line}} \times I_{\text{line}} \times \text{PF} P = 3 × V line × I line × PF
Line Current: I line = P 3 × V line × PF I_{\text{line}} = \frac{P}{\sqrt{3} \times V_{\text{line}} \times \text{PF}} I line = 3 × V line × PF P
Motor Horsepower, Efficiency, and Calculations
Electric motors convert electrical power to mechanical shaft output rated in horsepower:
1 Horsepower (HP) = 746 Watts 1\text{ Horsepower (HP)} = 746\text{ Watts} 1 Horsepower (HP) = 746 Watts
Efficiency ( η \eta η ) : Ratio of mechanical output power to electrical input power ( η = P out P in \eta = \frac{P_{\text{out}}}{P_{\text{in}}} η = P in P out ).
Input Power : P in = HP × 746 η P_{\text{in}} = \frac{\text{HP} \times 746}{\eta} P in = η HP × 746 .
Worked Example: Three-Phase Motor Line Current
Calculate full-load line current for a 15-HP, 460-volt, three-phase motor operating at 89% efficiency with an 0.84 lagging power factor.
Determine input power in watts : P in = 15 HP × 746 W/HP 0.89 = 11 , 190 0.89 = 12 , 573.03 Watts P_{\text{in}} = \frac{15\text{ HP} \times 746\text{ W/HP}}{0.89} = \frac{11,190}{0.89} = 12,573.03\text{ Watts} P in = 0.89 15 HP × 746 W/HP = 0.89 11 , 190 = 12 , 573.03 Watts
Determine input apparent power : S = 12 , 573.03 W 0.84 = 14 , 967.89 VA S = \frac{12,573.03\text{ W}}{0.84} = 14,967.89\text{ VA} S = 0.84 12 , 573.03 W = 14 , 967.89 VA
Calculate full-load line current : I line = 14 , 967.89 VA 1.73205 × 460 V = 14 , 967.89 796.74 = 18.79 Amperes I_{\text{line}} = \frac{14,967.89\text{ VA}}{1.73205 \times 460\text{ V}} = \frac{14,967.89}{796.74} = 18.79\text{ Amperes} I line = 1.73205 × 460 V 14 , 967.89 VA = 796.74 14 , 967.89 = 18.79 Amperes