5.3 Commercial Load Calculations & Non-Dwelling Demands

Alabama Journeyman Electrician Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Licensing, Exam Strategy & General Electrical Theory

1.1 Alabama Electrical Licensing, AECB Regulations & Prov Exam Structure 1.2 Electrical Fundamentals, Ohm's Law, Joule's Law & Power Formulas 1.3 Circuit Analysis: Series, Parallel & Combination Circuits

2 Chapter 2: NEC General Requirements, Working Spaces & Trade Knowledge

2.1 NEC Structure, Article 90 & Mandatory Article 100 Definitions 2.2 Electrical Equipment Spaces, Working Clearances & Dedicated Spaces 2.3 Electrical Connections, Terminations & Temperature Ratings 2.4 Electrical Plans, Symbols, Test Instruments & Troubleshooting

3 Chapter 3: Branch Circuits & Receptacle Outlets

3.1 Branch Circuit Ratings, Multiwire Branch Circuits & Required Outlets 3.2 Receptacle Spacing & Placement Requirements 3.3 GFCI Protection Requirements 3.4 AFCI Protection Requirements & Tamper-Resistant Receptacles

4 Chapter 4: Feeders, Services & System Disconnects

4.1 Feeder Sizing, Demand Factors & Neutral Calculations 4.2 Service-Entrance Conductors & Service Disconnecting Means 4.3 Service Equipment Rating, Emergency Disconnects & Surge Protection

5 Chapter 5: Load Calculations

5.1 Standard Dwelling Unit Load Calculations 5.2 Optional Dwelling Unit Load Calculations 5.3 Commercial Load Calculations & Non-Dwelling Demands

6 Chapter 6: Conductors, Cables & Flexible Cords

6.1 Conductor Types, Insulation & Temperature Ratings 6.2 Conductor Ampacity Derating & Correction Factors 6.3 Nonmetallic-Sheathed Cable (Type NM) & Underground Feeder (Type UF) 6.4 Armored Cable (Type AC) & Metal-Clad Cable (Type MC) 6.5 Service-Entrance Cable (Types SE & USE), Other Cables & Flexible Cords

7 Chapter 7: Raceways, Conduit Fill & Enclosures

7.1 Conduit Systems: EMT, RMC, IMC, and PVC 7.2 Flexible Raceways: FMC, LFMC, and LFNC 7.3 Conduit Fill Calculations & Chapter 9 Tables 7.4 Outlet, Device & Junction Box Sizing 7.5 Wireways, Auxiliary Gutters, Surface Raceways & Cable Trays 7.6 Underground Raceways, ENT & Protection from Physical Damage

8 Chapter 8: Grounding & Bonding Systems

8.1 Grounding Electrode System & Grounding Electrodes 8.2 Grounding Electrode Conductor (GEC) Sizing & Installation 8.3 Main & System Bonding Jumpers 8.4 Equipment Grounding Conductors (EGC) Sizing & Identification

9 Chapter 9: Overcurrent Protection & Ground-Fault Protection

9.1 Standard Fuse & Circuit Breaker Ratings & Sizing 9.2 Small Conductor Rules & Overcurrent Exceptions 9.3 Tap Rules & Ground-Fault Protection of Equipment

10 Chapter 10: Motors, Motor Circuits & Transformers

10.1 Motor Conductor Sizing & Full-Load Current Tables 10.2 Motor Overload Protection 10.3 Motor Branch-Circuit Short-Circuit & Ground-Fault Protection 10.4 Transformer Sizing, Installation & Overcurrent Protection

11 Chapter 11: Special Occupancies, Hazardous Locations & Special Equipment

11.1 Hazardous (Classified) Locations: Class I, II, III 11.2 Healthcare Facilities & Patient Care Spaces 11.3 Swimming Pools, Spas & Hot Tubs 11.4 Agricultural Buildings, Mobile Homes, Marinas & RV Parks 11.5 Appliances, Electric Space Heating, Water Heaters & Special Equipment

12 Chapter 12: Lighting, Signs, Low Voltage, Communications & Safety

12.1 Luminaires, Lighting Outlets & Electric Signs 12.2 Fire Alarm Systems, Class 1, 2, 3 Circuits & Power-Limited Cables 12.3 Solar Photovoltaic (PV) & Energy Storage Systems 12.4 Electrical Safety, OSHA Regulations & NFPA 70E Fundamentals 12.5 Communications, CATV & Optical Fiber Systems (NEC Chapter 8) 12.6 OSHA Electrical Standards, Lockout/Tagout & Jobsite Safety

5.3 Commercial Load Calculations & Non-Dwelling Demands

Key Takeaways Explain This Topic AI

Commercial general lighting loads are determined from the occupancy unit loads in NEC 2023 Table 220.42(A) and must be multiplied by 125% where lighting operates continuously for 3 hours or more per NEC 210.20 and 215.2.

Show window lighting must be calculated at not less than 200 VA per linear foot (660 VA/m) under NEC 220.43(A), and commercial signage requires at least one dedicated 1,200 VA branch circuit per NEC 220.14(F) and 600.5.

Multioutlet assemblies under NEC 220.14(H) are calculated at 180 VA per 5-foot section for ordinary use, or 180 VA per 1-foot section where multiple appliances are operated simultaneously.

Commercial receptacle loads are assessed at 180 VA per yoke under NEC 220.14(I), with demand factors under NEC 220.44 allowing the first 10 kVA at 100% and remainder over 10 kVA at 50%.

Commercial electric kitchen equipment is calculated using NEC Table 220.56 demand factors (ranging from 100% for 1-2 units down to 65% for 6 or more units), but the calculated demand can never be less than the sum of the two largest units.

Last updated: September 2026

Commercial Load Calculations & Non-Dwelling Demands

Commercial electrical load calculations govern office buildings, retail spaces, restaurants, and schools. Unlike residential settings, commercial systems are characterized by prolonged continuous duty, intensive multioutlet assemblies, heavy kitchen equipment, and three-phase motor distribution. Mastery of NEC Article 220 , the 125% continuous load multiplier , and demand factors is essential for the Alabama Journeyman examination.

1. Commercial Lighting Loads & The 125% Continuous Rule (NEC 220.42)

2023 renumbering alert. In the 2023 NEC the non-dwelling lighting rule is 220.42 , and the per-occupancy unit loads live in Table 220.42(A) . Table 220.12 is the 2020-edition location. The unit-load values themselves were also revised between recent editions, so read the number out of your own 2023 codebook on exam day rather than trusting a memorized figure.

Under NEC 220.42 and Table 220.42(A) , commercial lighting loads are determined from unit volt-amperes per square foot based on building occupancy. The table lists dozens of occupancy types (office, retail, warehouse, school, restaurant, hospital, parking garage, and so on); find the row that matches the occupancy in the question stem, then multiply: Lighting VA = Floor Area (sq ft) × Table 220.42(A) Unit Load (VA/sq ft) \text{Lighting VA} = \text{Floor Area (sq ft)} \times \text{Table 220.42(A) Unit Load (VA/sq ft)} Lighting VA = Floor Area (sq ft) × Table 220.42(A) Unit Load (VA/sq ft)

Exam questions almost always hand you the unit load or expect you to look it up. The scoreable skill is the arithmetic that follows, not the memorized value.

Continuous Load Multiplier (NEC 210.20(A) & 215.2(A)(1))

Under Article 100 , a continuous load operates for 3 hours or more . Commercial lighting operates continuously during business hours. Under NEC 210.19(A)(1) , 210.20(A) , and 215.2(A)(1) , conductors and overcurrent devices must be sized for: 100 % Non-Continuous + 125 % Continuous Loads \mathbf{100\% \text{ Non-Continuous}} + \mathbf{125\% \text{ Continuous Loads}} 100% Non-Continuous + 125% Continuous Loads

Consequently, general lighting volt-amperes must be multiplied by 1.25 for branch-circuit and feeder calculations.

2. Show Windows, Signs & Multioutlet Assemblies (NEC 220.14)

Specialized commercial loads are governed by NEC 220.14 :

Show Windows (NEC 220.43(A)) : Minimum 200 VA per linear foot (660 VA/m) along the base, sized at 125% continuous duty ( 200 VA × 1.25 = 250 VA/ft 200\text{ VA} \times 1.25 = \mathbf{250\text{ VA/ft}} 200 VA × 1.25 = 250 VA/ft ). In the 2023 NEC, show-window and track lighting for feeder and service calculations sit in 220.43, not 220.14(G).

Sign Circuits (NEC 220.14(F) & 600.5(A)) : Commercial occupancies with pedestrian access require at least one 20A sign circuit, calculated at a minimum of 1,200 VA , treated as continuous ( 1 , 200 VA × 1.25 = 1 , 500 VA 1,200\text{ VA} \times 1.25 = \mathbf{1,500\text{ VA}} 1 , 200 VA × 1.25 = 1 , 500 VA ).

Multioutlet Assemblies (NEC 220.14(H)) :

Ordinary Use (220.14(H)(2)) : Where simultaneous use is unlikely, each 5 feet (1.5 m) or fraction is calculated at 180 VA .

Simultaneous Use (220.14(H)(1)) : Where appliances operate concurrently (repair benches, testing labs), each 1 foot (300 mm) or fraction is calculated at 180 VA .

3. Commercial General Receptacles & Demand Factors (NEC 220.14(I) & 220.44)

Under NEC 220.14(I) , convenience receptacle outlets are calculated at 180 VA for each single or multiple receptacle on one yoke or strap :

Single or duplex receptacle on one strap = 180 VA

Two duplex receptacles on separate yokes in a 2-gang box = 2 × 180 = 360 VA 2 \times 180 = \mathbf{360\text{ VA}} 2 × 180 = 360 VA

Non-Dwelling Receptacle Demand Factors (NEC Table 220.44):

Demand factors may be applied to commercial receptacle loads calculated under 220.14(I):

  • Receptacle Connected Volt-Amperes Table 220.44 Demand Factor
  • First 10 kVA (10,000 VA) or less 100% (1.00)
  • Remainder over 10 kVA 50% (0.50)

For example, 100 duplex receptacles ( 18 , 000 VA 18,000\text{ VA} 18 , 000 VA ) yield: 10 , 000 VA @ 100 % + 8 , 000 VA @ 50 % = 14 , 000 VA 10,000\text{ VA} @ 100\% + 8,000\text{ VA} @ 50\% = \mathbf{14,000\text{ VA}} 10 , 000 VA @100% + 8 , 000 VA @50% = 14 , 000 VA .

4. Commercial Kitchen Equipment Demand Factors (NEC Table 220.56)

Commercial electric kitchen equipment—such as commercial dishwashers, water booster heaters, fryers, griddles, ovens, and warmers—is calculated under NEC 220.56 and Table 220.56 :

  • Number of Units of Equipment Table 220.56 Demand Factor
  • 1 to 2 units 100%
  • 3 units 90%
  • 4 units 80%
  • 5 units 70%
  • 6 or more units 65%

The Two-Largest Unit Floor Rule:

NEC 220.56 mandates that the calculated feeder demand shall never be less than the sum of the two largest kitchen equipment loads . If applying the table percentage yields a smaller value, the sum of the two largest units must be used.

5. Commercial Motor Loads (NEC 220.50 & 430.24)

Feeders supplying multiple electric motors are sized pursuant to NEC 220.50 and NEC 430.24 : Motor Feeder Load = ( 125 % × FLC of Largest Motor ) + ∑ ( 100 % × FLC of Other Motors ) \mathbf{\text{Motor Feeder Load}} = (125\% \times \text{FLC of Largest Motor}) + \sum (100\% \times \text{FLC of Other Motors}) Motor Feeder Load = ( 125% × FLC of Largest Motor ) + ∑ ( 100% × FLC of Other Motors )

Full-load current (FLC) ratings must be taken from NEC Table 430.248 (single-phase) or Table 430.250 (three-phase), never from the physical motor nameplate.

6. Worked Commercial Service Calculation (208Y/120V, 3-Phase)

Calculate the service load and minimum ampacity for a 6,000 sq ft retail facility with a cafe served at 208Y/120V, 3-phase, 4-wire:

Lighting : 6,000 sq ft retail; assume the Table 220.42(A) unit load for this occupancy is 1.5 VA/sq ft, continuous

  • Show Windows : 40 linear feet continuous
  • Sign : One 1,200 VA circuit continuous
  • Multioutlet Assembly : 30 feet of repair bench (simultaneous use)
  • Convenience Receptacles : 80 duplex receptacles on separate yokes
  • Cafe Kitchen Equipment : 6 commercial appliances totaling 34,000 VA (largest two: 8,000 VA and 7,000 VA)
  • Motors (208V, 3-Phase) : One 5-HP air handler (FLC = 16.7A) and one 2-HP exhaust fan (FLC = 7.5A)

Step-by-Step Solution:

Continuous Lighting & Display :

Lighting: 6 , 000 × 1.5 VA × 1.25 = 11 , 250 VA 6,000 \times 1.5\text{ VA} \times 1.25 = \mathbf{11,250\text{ VA}} 6 , 000 × 1.5 VA × 1.25 = 11 , 250 VA

Show Windows: 40 ft × 200 VA/ft × 1.25 = 10 , 000 VA 40\text{ ft} \times 200\text{ VA/ft} \times 1.25 = \mathbf{10,000\text{ VA}} 40 ft × 200 VA/ft × 1.25 = 10 , 000 VA

Sign: 1 , 200 VA × 1.25 = 1 , 500 VA 1,200\text{ VA} \times 1.25 = \mathbf{1,500\text{ VA}} 1 , 200 VA × 1.25 = 1 , 500 VA

Multioutlet & Receptacles :

Multioutlet (simultaneous): 30 ft × 180 VA/ft = 5 , 400 VA 30\text{ ft} \times 180\text{ VA/ft} = \mathbf{5,400\text{ VA}} 30 ft × 180 VA/ft = 5 , 400 VA

Receptacles: 80 × 180 = 14 , 400 VA 80 \times 180 = 14,400\text{ VA} 80 × 180 = 14 , 400 VA

First 10,000 VA @ 100% = 10 , 000 VA 10,000\text{ VA} 10 , 000 VA ; Remainder 4 , 400 VA × 0.50 = 2 , 200 VA 4,400\text{ VA} \times 0.50 = 2,200\text{ VA} 4 , 400 VA × 0.50 = 2 , 200 VA

Net Receptacle Demand = 12 , 200 VA \mathbf{12,200\text{ VA}} 12 , 200 VA

Cafe Kitchen Equipment (Table 220.56) :

6 pieces @ 65% = 34 , 000 VA × 0.65 = 22 , 100 VA 34,000\text{ VA} \times 0.65 = \mathbf{22,100\text{ VA}} 34 , 000 VA × 0.65 = 22 , 100 VA

Check: 8 , 000 + 7 , 000 = 15 , 000 VA ≤ 22 , 100 VA 8,000 + 7,000 = 15,000\text{ VA} \le 22,100\text{ VA} 8 , 000 + 7 , 000 = 15 , 000 VA ≤ 22 , 100 VA (governs).

Three-Phase Motors (208V) :

Largest (5 HP, 16.7A): 16.7 A × 208 V × 3 × 1.25 = 7 , 520 VA 16.7\text{ A} \times 208\text{ V} \times \sqrt{3} \times 1.25 = \mathbf{7,520\text{ VA}} 16.7 A × 208 V × 3 ​ × 1.25 = 7 , 520 VA

Second (2 HP, 7.5A): 7.5 A × 208 V × 3 = 2 , 702 VA 7.5\text{ A} \times 208\text{ V} \times \sqrt{3} = \mathbf{2,702\text{ VA}} 7.5 A × 208 V × 3 ​ = 2 , 702 VA

Total Motor Demand = 7 , 520 + 2 , 702 = 10 , 222 VA 7,520 + 2,702 = \mathbf{10,222\text{ VA}} 7 , 520 + 2 , 702 = 10 , 222 VA

Total Service Load & Line Current : Total VA = 11 , 250 + 10 , 000 + 1 , 500 + 5 , 400 + 12 , 200 + 22 , 100 + 10 , 222 = 72 , 672 VA \text{Total VA} = 11,250 + 10,000 + 1,500 + 5,400 + 12,200 + 22,100 + 10,222 = \mathbf{72,672\text{ VA}} Total VA = 11 , 250 + 10 , 000 + 1 , 500 + 5 , 400 + 12 , 200 + 22 , 100 + 10 , 222 = 72 , 672 VA I line = 72 , 672 VA 3 × 208 V = 72 , 672 360.27 = 201.72 Amperes I_{\text{line}} = \frac{72,672\text{ VA}}{\sqrt{3} \times 208\text{ V}} = \frac{72,672}{360.27} = \mathbf{201.72\text{ Amperes}} I line ​ = 3 ​ × 208 V 72 , 672 VA ​ = 360.27 72 , 672 ​ = 201.72 Amperes (Requires a standard commercial 225A, 3-phase, 4-wire service panelboard).