12.1 Electric Motors, Compressors & Motor Protection

Alabama HVAC Contractor License Exam

Track your progress as you read

Finished sections get a check mark.

1 Alabama HACR Laws, Rules & Licensing

1.1 Alabama HACR Board Authority, Licensing Pathways & Experience Requirements 1.2 Contractor Bonding, Insurance, Fees & Annual Renewal 1.3 Permits, Local Jurisdictions, Inspections & Disciplinary Actions

2 Contractor Business, Contracts, Estimating & Alabama Lien Law

2.1 Business Organization, Risk Management & Project Administration 2.2 Construction Contracts, Change Orders & Warranties 2.3 Alabama Mechanics' Lien Law & Financial Management 2.4 Construction Estimating, Markup & Bid Preparation 2.5 Project Management, Scheduling & Field Supervision 2.6 Risk Management, Contractor Insurance & Surety Bonds

3 Safety Standards, OSHA & EPA Section 608

3.1 OSHA Construction Safety (29 CFR 1926) for HVAC Contractors 3.2 EPA Section 608 Refrigerant Regulations & Recovery Requirements 3.3 Refrigerant Management, Leak Repair Rules & A2L Transition

4 General Technical Knowledge & Thermodynamics

4.1 Principles of Heat Transfer, Temperature & Pressure 4.2 The Mechanical Refrigeration Cycle & Refrigerant Properties 4.3 Psychrometrics & Air Properties for Humid Climates 4.4 Basic Electricity, Ohm's Law & Electrical Power for HVAC

5 Piping Systems, Refrigerant Lines & Fuel Gas Piping

5.1 Refrigerant Piping Sizing, Materials & Installation 5.2 Fuel Gas Piping Sizing & Installation (IRC Chapter 24) 5.3 Condensate Drain Systems & Trapping

6 System Sizing & ACCA Manual J Load Calculations

6.1 ACCA Manual J Fundamentals & Design Conditions 6.2 Envelope Loads: Conduction, Radiation & Fenestration 6.3 Infiltration, Ventilation & Internal Heat Gains

7 Duct System Design & ACCA Manual D

7.1 Airflow Principles, Static Pressure & Fan Performance 7.2 ACCA Manual D Duct Sizing & Friction Rate 7.3 Duct Materials, Installation Standards & Air Distribution

8 Heating & Cooling Equipment Operation

8.1 Heat Pump Systems & Supplemental Heating 8.2 Gas Furnaces & Combustion Systems 8.3 Air Conditioning Units, Compressors & Metering Devices

9 Mechanical Codes, Electrical Applications & Maintenance Diagnostics

9.1 Combustion Air & Venting Systems (IRC Chapter 24) 9.2 Electrical Applications for HVAC (NFPA 70 / NEC Article 440) 9.3 Preventative Maintenance, Troubleshooting & Plan Reading

10 Employment Law, Payroll Taxes & Contractor Finance

10.1 Federal & Alabama Labor Laws for HVAC Employers 10.2 Payroll, Employment Taxes & Worker Classification 10.3 Job Costing, Break-Even Analysis & Cash Flow Forecasting

11 Preventative Maintenance, Service Procedures & Commissioning

11.1 Preventative Maintenance Programs & Service Agreements 11.2 Filter, Coil & Drain Maintenance for Alabama's Humid Climate 11.3 Evacuation, Dehydration & Refrigerant Charging Procedures 11.4 Airflow Verification, Static Pressure Testing & Commissioning

12 Electrical Applications & Construction Documents

12.1 Electric Motors, Compressors & Motor Protection 12.2 Transformers, Control Circuits & Low-Voltage Wiring 12.3 Branch Circuits, Conductors, Grounding & Disconnects 12.4 Construction Documents, Specifications & Submittals

12.1 Electric Motors, Compressors & Motor Protection

Key Takeaways Explain This Topic AI

On a hermetic compressor the three terminals are identified by resistance: common to run is the lowest reading, common to start is higher, and start to run equals the sum of the other two.

Locked rotor amperage typically runs five to eight times rated load amperage, which is why a compressor that will not start pulls LRA until the overload opens.

A potential relay senses back electromotive force across the start winding through its coil and opens its normally closed contacts to drop the start capacitor out of the circuit.

A permanent split capacitor motor uses a run capacitor continuously and has no start winding switch, while a capacitor-start capacitor-run motor adds a start capacitor and a relay for high starting torque.

A winding-to-ground reading below roughly one megohm indicates insulation breakdown, and a compressor that reads shorted to ground must be replaced, not restarted.

Last updated: September 2026

12.1 Electric Motors, Compressors & Motor Protection

Note

Electrical Applications for HAC Systems is a ten-question block on the Alabama blueprint - the largest single technical block outside Systems and Sizing. This section covers motors and compressors; the two sections that follow cover control circuits and branch-circuit wiring.

Single-Phase Motor Types

  • Type Starting torque Start components Typical HVAC use
  • Shaded pole Very low None (shading coil) Small condenser fans, draft inducers
  • Split phase Moderate Start winding + centrifugal switch Legacy open-drive applications

Permanent split capacitor (PSC) Low Run capacitor only , energized continuously Blowers, condenser fans, small compressors

Capacitor start, induction run (CSIR) High Start capacitor + relay, dropped after start Small hermetic compressors

Capacitor start, capacitor run (CSCR) Highest Start and run capacitors + relay Larger single-phase compressors, hard-start retrofits

ECM / variable speed Programmed Electronic module, DC brushless High-efficiency air handlers and inducers

A PSC motor has no centrifugal switch and no start relay. Its run capacitor stays in the circuit at all times, shifting the phase of the current in the start winding to create a rotating field. A failed run capacitor produces the classic symptom: the motor hums, draws locked rotor amperage, and does not turn.

An ECM is a DC brushless motor with an onboard electronic control. Constant-torque and constant-airflow ECMs will increase their own speed to maintain airflow as static pressure rises, which masks a duct restriction until the motor overheats. Always measure static pressure on ECM equipment - the airflow symptom will not appear.

Hermetic Compressor Terminals

A single-phase hermetic compressor has three terminals in a triangle: C (common) , S (start) , and R (run) .

Identifying Them by Resistance

With power off and capacitors discharged, measure between all three pairs:

The highest reading is always S to R .

The terminal not involved in that highest reading is C .

From C, the lower reading goes to R ; the higher reading goes to S .

Verify: R C − S + R C − R = R S − R R_{C-S} + R_{C-R} = R_{S-R} R C − S ​ + R C − R ​ = R S − R ​ .

Worked example : readings are 2 ohms, 6 ohms, and 8 ohms. The 8-ohm pair is S to R. The remaining terminal is C. From C, 2 ohms goes to R (the run winding is heavier wire and lower resistance) and 6 ohms goes to S. Check: 2 + 6 = 8 2 + 6 = 8 2 + 6 = 8 . Consistent.

Reading the Faults

  • Reading Diagnosis
  • Infinite resistance across a winding Open winding - compressor is failed
  • Near-zero resistance where a value is expected Shorted winding - compressor is failed
  • Any winding to the shell below about 1 megohm Grounded winding - compressor is failed

Correct resistances but will not start Check capacitor, start components, supply voltage, and mechanical seizure

Insulation resistance testing uses a megohmmeter, not an ordinary ohmmeter, applying 500 volts direct current between a winding and the compressor shell. A reading above roughly 1 megohm is generally acceptable; below that, insulation is breaking down. Never megger a system containing electronic controls without disconnecting them.

Starting Current and Overloads

Rated load amperage (RLA) is a derived value printed on the nameplate for use in circuit sizing.

Full load amperage (FLA) is the running current of a fan or blower motor at rated load.

Locked rotor amperage (LRA) is the current drawn at the instant of start, or any time the rotor cannot turn. It typically runs five to eight times RLA .

A compressor that will not turn draws LRA continuously until a protective device opens. Two families of device do that job:

Internal (inherent) overload - a bimetallic device embedded in the windings that opens on temperature and current and resets automatically after cooling. A compressor "off on internal overload" is hot; it may take 30 to 60 minutes to reset, and restarting it repeatedly destroys it.

External overload - a line-break device clamped to the shell, used on smaller compressors.

Motor protection modules on larger equipment monitor discharge temperature, phase loss, phase reversal, and current, and lock out until manually reset.

Hard-Start Components

When a compressor struggles to start against unequalized pressures or low voltage, a start assist adds torque.

A start capacitor is a large-value electrolytic device (for example 88 to 108 microfarads) rated for intermittent duty only . Leaving one in the circuit destroys it and the start winding within minutes.

The potential relay removes it. The relay coil is connected across the start winding , where it senses the back electromotive force the motor generates as it comes up to speed. Its contacts are normally closed in the start capacitor circuit. As the motor accelerates, back EMF rises until it reaches the relay pick-up voltage, the coil energizes, and the normally closed contacts open , dropping the start capacitor out. On a standard potential relay, the coil lands on terminals 2 and 5 and the contacts are terminals 1 and 2.

A current relay performs the same job on small compressors by sensing run-winding current instead, using a normally open contact that closes on high inrush.

A start capacitor must carry a bleed resistor across its terminals - commonly 15,000 to 20,000 ohms at 2 watts - to drain the residual charge between cycles so the relay contacts do not arc and weld.

Three-Phase Considerations

Single-phasing is the loss of one of three supply legs. The motor continues to turn but the remaining two legs carry far more current, and the windings overheat quickly. Suspect it when a three-phase motor hums, runs hot, and reads normal voltage on only two legs.

Phase rotation matters on scroll compressors and on three-phase blowers. A scroll compressor running backward makes an abnormal noise, does not build pressure differential, and will be damaged if it is left running. Reverse any two of the three line leads to correct rotation.

Voltage unbalance above 1 percent should be investigated, and current unbalance runs several times the voltage unbalance percentage.

Three-phase motors have no start windings, no start capacitors, and no start relays - the rotating field is inherent in the three-phase supply.