4.1 Drainage Fixture Units & Sizing Branches, Stacks and Building Drains
Alabama Journeyman Plumber Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Alabama Law, General Regulations, Trade Math, Tools & Safety
1.1 Alabama Exam Format, Licensing Law & Board Rules 1.2 IPC Chapter 3 General Regulations: Protection, Sleeves, Trenching & Structural Safety 1.3 Trade Math I: Pressure, Head, Fall, Volume & Expansion 1.4 Trade Math II: Fractions, Offsets, Areas & Heat Calculations 1.5 Plumbing Tools: Layout, Cutting, Joining, Threading & Test Equipment 1.6 Jobsite Safety: Trenches, Ladders, Confined Spaces, Hot Work & PPE
2 Chapter 2: Plumbing Fixtures, Fittings & Clearances
2.1 Minimum Plumbing Facilities, Fixture Clearances & Accessibility 2.2 Fixture Materials, Prohibited Fixtures, Overflows, Waste Outlets & Fixture Setting 2.3 Flushing Devices, Water Conservation & Temperature-Limiting Controls
3 Chapter 3: Water Supply, Distribution, Backflow & Water Heaters
3.1 Water Service & Distribution Sizing: WSFU, Demand, Pressure & Friction 3.2 Water Piping Materials, Joints, Valves, Supports & Disinfection 3.3 Cross-Connection Control & Backflow Prevention (IPC 608 & 312.10) 3.4 Water Heaters: Installation, Relief Valves, Pans & Thermal Expansion
4 Chapter 4: Sanitary Drainage Systems & DWV Sizing
4.1 Drainage Fixture Units & Sizing Branches, Stacks and Building Drains 4.2 Drainage Slopes, Building Drain & Sewer Rules, Offsets and Backwater Valves 4.3 DWV Materials, Fittings, Joints, Supports & Underground Installation 4.4 Indirect Waste, Special Waste, Sumps and Sewage Ejectors
5 Chapter 5: Traps, Cleanouts, Interceptors & Separators
5.1 Fixture Traps, Trap Seals, Prohibited Traps & Trap Seal Protection 5.2 Cleanouts: Required Locations, Size, Arrangement, Clearance & Access 5.3 Grease Interceptors, Oil Separators & Other Interceptors (IPC 1003)
6 Chapter 6: Vents and Venting Methods
6.1 Vent Purpose, Vent Stacks, Connections, Terminals & Vent Sizing 6.2 Fixture Vents, Individual Vents, Common Vents & Wet Venting 6.3 Circuit Vents, Combination Waste & Vent, Island, Waste Stack & Single-Stack Venting 6.4 Air Admittance Valves: Standards, Where Permitted, Location & Prohibitions
7 Chapter 7: Plan Reading, Sizing Practice, Testing & Fuel Gas
7.1 Reading Plumbing Drawings, Isometrics, Symbols & Schedules 7.2 Plan-Based Sizing Practice: Branches, Stacks, Building Drain, Vents & Water 7.3 Inspections and Tests: DWV, Water, Sewers, Storm, Shower Pans & Backflow 7.4 Fuel Gas Basics, Combustion Air, Venting & Alabama Gas Fitting Scope
8 Chapter 8: Roof Drain & Storm Drainage Systems
8.1 Roof Drains, Rainfall Rates & Storm Drain Sizing (IPC 1101–1106) 8.2 Secondary (Emergency) Roof Drainage, Scuppers, Controlled Flow, Subsoil Drains & Storm Sumps
4.1 Drainage Fixture Units & Sizing Branches, Stacks and Building Drains
Key Takeaways Explain This Topic AI
In IPC Table 709.1, a 1.6-gallon-per-flush water closet is 3 dfu in private use and 4 dfu in public use, a lavatory is 1 dfu, a bathtub or 5.7-gpm shower is 2 dfu, and a bathroom group with a 1.6-gpf water closet is 5 dfu.
IPC 709.3 counts continuous or semicontinuous flow as 2 dfu for each gpm.
In Table 710.1(2), a 3-inch horizontal branch carries up to 20 dfu, and a 3-inch stack carries 20 dfu per branch interval, 48 dfu total with three or fewer branch intervals, or 72 dfu with more.
In Table 710.1(1), a 3-inch building drain carries 36 dfu at 1/8 inch per foot, 42 dfu at 1/4 inch per foot and 50 dfu at 1/2 inch per foot, and a 4-inch building drain carries 180, 216 and 250 dfu.
Any building drain serving a water closet must be at least 3 inches (Table 710.1(1), note a), and a clothes washer standpipe drain must be at least 2 inches and connect to a branch or stack of 3 inches or more (IPC 406.2).
Last updated: October 2026
Why this section matters
Drain sizing is the core of Sizing and Design and many plan-reading questions. The method is: assign fixture units, add them up in the direction of flow, then choose the correct table. Most mistakes come from reading the wrong table, such as using the building drain table for a horizontal branch.
Drainage fixture units (709)
A drainage fixture unit (dfu) is a load factor that reflects how much a fixture discharges, how fast and how often. It is a probability weighting, not a flow rate. Hunter's original work was based on a lavatory discharging about 1 cubic foot per minute, but on the exam you use only the table values.
Selected values from Table 709.1
- Fixture dfu Minimum trap
- Automatic clothes washer, residential 2 2 in
- Automatic clothes washer, commercial 3 2 in
- Bathroom group, 1.6-gpf water closet 5 —
- Bathroom group, water closet over 1.6 gpf 6 —
- Bathtub (with or without shower head or whirlpool) 2 1-1/2 in
- Bidet, lavatory, dental lavatory 1 1-1/4 in
- Dishwasher, domestic 2 1-1/2 in
- Drinking fountain 1/2 1-1/4 in
- Emergency floor drain 0 2 in
- Floor drain 2 2 in
- Kitchen sink, domestic (with or without disposer and dishwasher) 2 1-1/2 in
- Laundry tray, combination sink and tray, service sink, sink 2 1-1/2 in
- Shower, total flow 5.7 gpm or less 2 1-1/2 in
- Shower, over 5.7 to 12.3 gpm 3 2 in
- Shower, over 12.3 to 25.8 gpm 5 3 in
- Urinal 4 Match outlet
- Urinal, 1 gallon per flush or less 2 Match outlet
- Urinal, nonwater 1/2 Match outlet
- Water closet, private, 1.6 gpf 3 Integral
- Water closet, public, 1.6 gpf 4 Integral
- Water closet, flushometer tank, public or private 4 Integral
- Water closet, private, over 1.6 gpf 4 Integral
- Water closet, public, over 1.6 gpf 6 Integral
Notes to the table:
For drains and sewers, water closets and urinals may not be given lower values unless testing proves them.
Fixtures added to a bathroom group add their own dfu.
709.2: Fixtures not listed use Table 709.2, based on drain or trap size: 1-1/4 in = 1, 1-1/2 in = 2, 2 in = 3, 2-1/2 in = 4, 3 in = 5, 4 in = 6.
709.3: Where only a gpm flow is known, count 1 gpm as 2 dfu . A pump discharging 15 gpm adds 30 dfu.
709.4: An indirect waste receptor carries the total dfu of the fixtures that drain into it, but no less than its own table value. 709.4.1: A receptor taking only clear water from display cases, ice bins, coolers and freezers is 1/2 dfu .
Choosing the right table (710)
- Pipe being sized Table
- Horizontal fixture branch, vertical soil or waste stack Table 710.1(2)
- Building drain, building sewer, horizontal branch of the building drain Table 710.1(1) (by slope)
- Horizontal stack offset Sized like a building drain (710.1.1)
- Table 710.1(2): horizontal branches and stacks
- Diameter Horizontal branch One branch interval Stack, 3 intervals or fewer Stack, more than 3 intervals
- 1-1/2 in 3 2 4 8
- 2 in 6 6 10 24
- 2-1/2 in 12 9 20 42
- 3 in 20 20 48 72
- 4 in 160 90 240 500
- 5 in 360 200 540 1,100
- 6 in 620 350 960 1,900
- 8 in 1,400 600 2,200 3,600
A stack must meet both its total limit and its per-interval limit.
A branch interval is at least 8 feet of stack between branch connections (Section 202).
A stack may get smaller higher up as its load drops, but never smaller than half the largest size required.
Table 710.1(1): building drains and sewers
- Diameter 1/16 in/ft 1/8 in/ft 1/4 in/ft 1/2 in/ft
- 2 in — — 21 26
- 2-1/2 in — — 24 31
- 3 in — 36 42 50
- 4 in — 180 216 250
- 5 in — 390 480 575
- 6 in — 700 840 1,000
- 8 in 1,400 1,600 1,920 2,300
- 10 in 2,500 2,900 3,500 4,200
Note a to the table says any building drain serving a water closet must be at least 3 inches . The 2021 IPC tables do not limit how many water closets a 3-inch branch or stack may carry. The dfu columns govern. (Some older codes had such limits; the single-stack vent system in Section 917 still limits a 3-inch stack to two water closets.)
Other sizing rules:
704.2: Drain piping may not be reduced in size in the direction of flow. A 4 × 3-inch closet flange or closet bend is not a reduction.
704.3: Horizontal branches connect to the base of a stack at least 10 stack diameters downstream .
710.2: Pipe sizes must include the load of any roughed-in future fixtures.
Clothes washer standpipes (406.2 and 802.4.3)
A washer must discharge through an air break into a standpipe or into a laundry sink.
The trap and fixture drain must be at least 2 inches , and the fixture drain must connect to a 3-inch or larger branch or stack.
The standpipe must be individually trapped and extend 18 to 42 inches above the trap weir (802.4.3).
Gravity-discharge washers may drain to a waste receptor or approved trench drain.
Worked example: four-story office stack
Each floor has 2 public 1.6-gpf water closets (4 dfu each), 2 lavatories (1 each), 1 urinal at 1 gpf or less (2) and 1 service sink (2).
Load per floor: 2 ( 4 ) + 2 ( 1 ) + 2 + 2 = 14 2(4) + 2(1) + 2 + 2 = 14 2 ( 4 ) + 2 ( 1 ) + 2 + 2 = 14 dfu.
Branch on each floor: water closets need at least 3 inches, and a 3-inch branch carries 20 dfu, so 14 dfu fits. Use 3 inches .
Stack: 4 floors means 4 branch intervals, which is more than 3, and 4 × 14 = 56 4 \times 14 = 56 4 × 14 = 56 dfu. A 3-inch stack allows 72 dfu total and 20 per interval, and 14 per interval passes. Use a 3-inch stack .
Building drain at 1/4 inch per foot: 56 dfu exceeds the 42-dfu limit for 3 inches, so the drain must be 4 inches (216 dfu).
Lesson: the stack can legally be smaller than the building drain it feeds, because the two are sized from different tables.
Exam traps
Washer dfu: 2 residential, 3 commercial. Both need a 2-inch trap.
Public 1.6-gpf water closet = 4 dfu. The 6-dfu value is for public water closets flushing more than 1.6 gallons.
No "two water closets per 3-inch branch" rule in the 2021 IPC Table 710.1(2).
Branch vs. building drain: a 3-inch horizontal branch carries 20 dfu, but a 3-inch building drain at 1/4 inch per foot carries 42.