8.2 Secondary (Emergency) Roof Drainage, Scuppers, Controlled Flow, Subsoil Drains & Storm Sumps

Alabama Journeyman Plumber Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Alabama Law, General Regulations, Trade Math, Tools & Safety

1.1 Alabama Exam Format, Licensing Law & Board Rules 1.2 IPC Chapter 3 General Regulations: Protection, Sleeves, Trenching & Structural Safety 1.3 Trade Math I: Pressure, Head, Fall, Volume & Expansion 1.4 Trade Math II: Fractions, Offsets, Areas & Heat Calculations 1.5 Plumbing Tools: Layout, Cutting, Joining, Threading & Test Equipment 1.6 Jobsite Safety: Trenches, Ladders, Confined Spaces, Hot Work & PPE

2 Chapter 2: Plumbing Fixtures, Fittings & Clearances

2.1 Minimum Plumbing Facilities, Fixture Clearances & Accessibility 2.2 Fixture Materials, Prohibited Fixtures, Overflows, Waste Outlets & Fixture Setting 2.3 Flushing Devices, Water Conservation & Temperature-Limiting Controls

3 Chapter 3: Water Supply, Distribution, Backflow & Water Heaters

3.1 Water Service & Distribution Sizing: WSFU, Demand, Pressure & Friction 3.2 Water Piping Materials, Joints, Valves, Supports & Disinfection 3.3 Cross-Connection Control & Backflow Prevention (IPC 608 & 312.10) 3.4 Water Heaters: Installation, Relief Valves, Pans & Thermal Expansion

4 Chapter 4: Sanitary Drainage Systems & DWV Sizing

4.1 Drainage Fixture Units & Sizing Branches, Stacks and Building Drains 4.2 Drainage Slopes, Building Drain & Sewer Rules, Offsets and Backwater Valves 4.3 DWV Materials, Fittings, Joints, Supports & Underground Installation 4.4 Indirect Waste, Special Waste, Sumps and Sewage Ejectors

5 Chapter 5: Traps, Cleanouts, Interceptors & Separators

5.1 Fixture Traps, Trap Seals, Prohibited Traps & Trap Seal Protection 5.2 Cleanouts: Required Locations, Size, Arrangement, Clearance & Access 5.3 Grease Interceptors, Oil Separators & Other Interceptors (IPC 1003)

6 Chapter 6: Vents and Venting Methods

6.1 Vent Purpose, Vent Stacks, Connections, Terminals & Vent Sizing 6.2 Fixture Vents, Individual Vents, Common Vents & Wet Venting 6.3 Circuit Vents, Combination Waste & Vent, Island, Waste Stack & Single-Stack Venting 6.4 Air Admittance Valves: Standards, Where Permitted, Location & Prohibitions

7 Chapter 7: Plan Reading, Sizing Practice, Testing & Fuel Gas

7.1 Reading Plumbing Drawings, Isometrics, Symbols & Schedules 7.2 Plan-Based Sizing Practice: Branches, Stacks, Building Drain, Vents & Water 7.3 Inspections and Tests: DWV, Water, Sewers, Storm, Shower Pans & Backflow 7.4 Fuel Gas Basics, Combustion Air, Venting & Alabama Gas Fitting Scope

8 Chapter 8: Roof Drain & Storm Drainage Systems

8.1 Roof Drains, Rainfall Rates & Storm Drain Sizing (IPC 1101–1106) 8.2 Secondary (Emergency) Roof Drainage, Scuppers, Controlled Flow, Subsoil Drains & Storm Sumps

8.2 Secondary (Emergency) Roof Drainage, Scuppers, Controlled Flow, Subsoil Drains & Storm Sumps

Key Takeaways Explain This Topic AI

Secondary (emergency overflow) roof drains or scuppers are required where the roof perimeter would trap water if the primary drains backed up (IPC 1108.1).

Secondary roof drain systems must have a discharge point separate from the primary system, above grade where building occupants or maintenance staff would normally see it (IPC 1108.2).

Secondary drains are sized under 1106 without counting any flow through the primary system, and scuppers must be at least 4 inches high and as wide as the circumference of the roof drain required for the same area (IPC 1108.3, 1106.5).

Controlled-flow roof drain systems must be engineered, with at least two roof drains on roofs of 10,000 square feet or less and at least four on larger roofs (IPC 1110.1, 1110.4).

Subsoil drains must be at least 4 inches, discharge to a trapped area drain, sump, dry well or approved location above ground, and have an accessible backwater valve where backwater is possible (IPC 1111.1).

Last updated: October 2026

Why this section matters

A blocked roof drain on a flat roof with parapets can collapse the roof under ponded water. The IPC therefore requires a separate secondary (emergency overflow) system wherever water could be trapped. This section also covers the groundwater side of storm drainage: subsoil drains, subdrains and storm sumps. All rules are from IPC Chapter 11, 2021 edition .

Roof ponding design (1101.7)

Roofs must be designed for the maximum possible depth of ponded water , assuming all primary drains are blocked . That depth includes the head of water over the secondary inlets needed to pass the design rainfall. The roof designer sets this under IBC Section 1611. The plumber's job is to set the secondary inlets at the elevations on the drawings and to keep the two systems separate.

Secondary (emergency) roof drains (1108)

Rule Requirement

1108.1, when required Where roof drains are required and the roof perimeter construction (parapets, walls) extends above the roof so that water would be trapped if the primary drains back up

1108.1, combined assemblies Where primary and secondary drains are made as one assembly, each drain's inlet and outlet must be independent

1108.2, separate systems The secondary system's end point of discharge must be separate from the primary system. It discharges above grade where occupants or maintenance staff would normally see it , so an overflow signals that the primary drains are blocked

1108.3, sizing Sized per Section 1106. The flow through the primary system is not counted when sizing the secondary system

Typical arrangements:

Overflow roof drains: set with a dam or raised inlet about 2 inches above the primary drain inlet, as the design requires. They pipe separately to a visible outlet, such as a downspout nozzle on the wall.

Scuppers: openings through the parapet.

Scuppers (1106.5 and 1108.3)

Scuppers may serve as primary drainage, secondary drainage or both. Their number, size, location and inlet elevation must keep ponding below the depth the roof was designed for (IBC 1611.1 and IPC 1101.7).

A scupper opening must be at least 4 inches high , with a width at least equal to the circumference of the roof drain that would be required for the same roof area.

Do not count primary flow when locating and sizing secondary scuppers.

Example. If a 4-inch roof drain would be required for an area, a secondary scupper serving it must be at least 4 inches high and about 12.6 inches wide , since 3.1416 × 4 ≈ 12.6 3.1416 \times 4 \approx 12.6 3.1416 × 4 ≈ 12.6 .

Siphonic and controlled-flow roofs (1107 and 1110)

Siphonic roof drain systems are engineered to ASME A112.6.9 and ASPE 45 (1107.1).

Controlled-flow roofs (1110) are designed to store water and release it slowly through flow-control devices. They must be engineered under 316.1 and designed for the 1106.1 rainfall rate.

Control devices are protected by strainers (1110.3).

Discharge may not exceed the design values (1110.2).

At least two roof drains are required for roof areas of 10,000 square feet or less , and at least four on larger roofs (1110.4).

Subsoil drains (1111)

A subsoil drain collects groundwater around foundations. It is open-jointed, horizontally split or perforated pipe from Table 1102.5, at least 4 inches in diameter.

Where the building is subject to backwater , protect the subsoil drain with an accessible backwater valve .

Subsoil drains discharge to a trapped area drain, a sump, a dry well, or an approved location above ground .

A subsoil sump does not need a gastight cover or a vent. Its pump and pit follow 1113.1.

Building subdrains (1112)

Building subdrains below the public sewer level discharge into a sump or receiving tank. The contents are lifted automatically into the drainage system, following 1113.1 for storm-type sumps or 712 for sanitary sumps.

Storm sumps and pumps (1113.1)

  • Rule Requirement
  • 1113.1.1 Pump capacity and head suited to the expected use

1113.1.2 Pit at least 18 inches in diameter and 24 inches deep unless approved otherwise; accessible; all drainage enters by gravity; tile, steel, plastic, cast iron, concrete or other approved material; removable cover strong enough for expected loads; solid bottom supporting the pump

1113.1.3 Electrical outlets meet NFPA 70

1113.1.4 Discharge piping meets 1102.2–1102.4, with a gate valve and a full-flow check valve , sized no smaller than the pump discharge. In one- and two-family dwellings only a check valve is required

Compare this with sanitary sumps (712): those need a gastight cover and a vent , and pumps receiving water closets must pass 2-inch solids.

How storm and sanitary systems relate

Storm water never goes into a sanitary-only sewer (1101.3), and floor drains never go into a storm drain (1104.2).

On a combined public sewer, the sanitary and storm building sewers connect independently (703.6, 1109.1), and the storm leaders are trapped (1103.1).

Air-conditioning condensate is regulated by IPC 314. It may discharge to the receptors listed there, or outdoors where it does not cause a nuisance.

Exam traps

Secondary discharge must be separate and visible. Never tie it into the primary storm piping.

Scupper size: at least 4 inches high, and as wide as the circumference of the equivalent roof drain.

Ignore primary flow when sizing the secondary system.

Subsoil drains: at least 4 inches. Their sumps need no gastight cover or vent.

Loading diagram... Primary and secondary roof drainage (IPC 1108)