6.3 Draft Systems
Arkansas Boiler Operator Licensing Exam Exam
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Exam Overview
1.1 About the Arkansas Boiler Operator Exam 1.2 Licensing Path, Training & Fees 1.3 How to Use This Study Guide
2 Arkansas Law, Licensing & Enforcement
2.1 Arkansas Boiler Safety Law & the Boiler Inspection Division 2.2 License Types & Eligibility 2.3 Attendance Requirements & Permit-to-Operate 2.4 Enforcement, Penalties & Reciprocity
3 Boiler Types, Pressure Class & Steam Fundamentals
3.1 Fire-Tube and Water-Tube Boilers 3.2 Low-Pressure vs High-Pressure Boilers 3.3 Steam, Heat Transfer & Boiler Horsepower 3.4 Construction, Pressure Parts & Furnace Components
4 Required Valves, Fittings & Water-Level Devices
4.1 Safety Valves & Safety Relief Valves 4.2 Water Column, Gauge Glass & Try Cocks 4.3 Pressure Gauges, Siphons & Inspector Test Connections 4.4 Feedwater Valves, Blowoff Valves & Steam Stops
5 Automatic Safety Controls & Flame Safeguards
5.1 Low-Water Fuel Cutoff (LWCO) 5.2 Operating Pressure Controls & High-Limit Controls 5.3 Flame Safeguard, Pilot Proving & Burner Interlocks
6 Combustion, Fuels & Draft Systems
6.1 Combustion Principles 6.2 Fuels & Burners 6.3 Draft Systems 6.4 Combustion Efficiency & Flue Gas Monitoring
7 Startup, Normal Operation, Blowdown & Shutdown
7.1 Cold Startup Procedures 7.2 Normal Operation, Watchstanding & Logs 7.3 Blowdown Procedures 7.4 Shutdown & Boiler Lay-Up
8 Water Chemistry, Treatment & Testing
8.1 Water Chemistry Fundamentals 8.2 External Water Treatment 8.3 Internal Treatment & Chemical Control 8.4 Testing, Monitoring & Blowdown Control
9 Emergencies, Inspection & Maintenance
9.1 Emergency Conditions & Response 9.2 Certificate Inspections & Hydrostatic Tests 9.3 Preventive Maintenance, Repairs & Personal Safety
6.3 Draft Systems
Key Takeaways Explain This Topic AI
Draft is the pressure difference that causes air and combustion gases to flow through the boiler and out the stack
Three draft types often tested on Arkansas sample material: natural draft, forced draft, and induced draft
Forced draft uses a fan to push (supply) air into the furnace; induced draft uses a fan between the boiler and chimney to pull gases out
Natural draft relies on the chimney effect — hot light gas column inside the stack versus cooler denser outside air
Balanced draft combines forced and induced fans so furnace pressure is controlled near neutral; dampers and breeching are part of the gas path
Last updated: July 2026
6.3 Draft Systems
Quick Answer: Draft is the pressure difference that causes flow of air and combustion gases. The three types Arkansas often tests are natural, forced, and induced . Forced = fan supplying the furnace. Induced = fan between boiler and chimney pulling gases out. Natural = chimney effect (hot column vs cold outside air). Balanced draft uses both push and pull. Dampers control flow; breeching is the duct from boiler to stack.
What “Draft” Means
In boiler language, draft is not a cold breeze from an open door. It is the pressure difference that causes air and gases of combustion to flow through the fuel bed or burner, across heating surfaces, through the breeching, and up the chimney. Without draft (natural or mechanical), the fire starves for oxygen and products of combustion cannot leave the furnace.
Draft is measured in inches of water column (not psi) with a draft gauge. Furnace draft is often a slight negative pressure on induced/natural systems, or carefully controlled near zero/slight negative on balanced systems, or slightly positive on some forced-draft package arrangements. Exact setpoints come from manufacturer data — your job is to know what creates the pressure difference and which fan does what .
Three Types Often Tested (Arkansas Sample Focus)
Arkansas sample questions and standard operator texts repeatedly test this trio:
Type How flow is produced Fan location / mechanism
Natural draft Chimney effect only — no mechanical fan required for basic draft Tall hot stack; density difference
- Forced draft (FD) Fan pushes air into the furnace/burner Fan on the inlet (supply) side of the furnace
- Induced draft (ID) Fan pulls gases out of the boiler toward the stack Fan between the boiler and the chimney
Memorize the short Arkansas-friendly lines:
Forced draft — a fan supplying air to the furnace.
Induced draft — a fan between the boiler and the chimney that pulls the gases of combustion out.
Natural draft — produced by the chimney because hot gases inside are lighter than cooler outside air.
Natural Draft — The Chimney Effect
Natural draft depends on a column of hot, light gases inside the chimney compared with a column of cooler, denser outside air of the same height. The density difference creates a pressure difference that pulls air through the boiler. Factors that strengthen natural draft:
- Taller stack (longer hot column)
- Hotter flue gas (lower density inside the stack)
- Clean, unrestricted gas path (no soot-choked breeching)
Factors that weaken natural draft:
- Cold stack on light-off
- Low fire / cool flue gas
- High outside air temperature (smaller density difference)
- Dirty tubes, closed dampers, or blocked breeching
Many modern package boilers do not rely on natural draft alone; fans provide reliable air regardless of weather and load. Natural draft still appears on exams and on older or simple installations.
Forced Draft
A forced-draft fan is on the supply side. It forces air through burners, windboxes, or grates into the furnace. Advantages:
- Positive, controllable air supply independent of stack temperature
- Better mixing and higher heat release rates in compact packages
- Works well with low chimneys
Because the fan is pushing, furnace pressure may be neutral to slightly positive depending on design and outlet restriction. Observation ports and casings must be maintained; a positive furnace can push hot gas or flame toward the operator if ports are open carelessly. Forced-draft package boilers are extremely common in Arkansas commercial plants.
Induced Draft
An induced-draft fan sits in the gas path after the boiler heating surface — typically in or near the breeching/stack connection — and extracts flue gas, creating a negative pressure (suction) in the furnace that draws air in through burners or dampers. Advantages:
- Keeps the furnace under suction so leaks tend to pull room air in rather than push fire out
- Helps overcome resistance of economizers, air heaters, and long breeching
- Common on larger industrial boilers and many multi-pass designs
If the ID fan fails or trips while fuel continues, combustion products and incomplete combustion hazards rise quickly — another reason air-flow and fan interlocks exist on automatic burners.
Balanced Draft
Balanced draft uses both a forced-draft fan and an induced-draft fan. The FD fan supplies combustion air; the ID fan removes flue gas. Operators (or automatic draft controls) adjust fan speeds/dampers so furnace pressure stays near the desired setpoint — often slightly negative. Balanced draft is the industrial standard for large boilers with high gas-side resistance.
- System Push Pull Typical furnace feel
- Natural only No FD fan Stack suction Slight negative if stack strong
- Forced only FD fan Stack/natural residual Near zero to positive
- Induced only Atmospheric/registers ID fan Negative
- Balanced FD fan ID fan Controlled near neutral/slight negative
- Dampers
Dampers are adjustable plates or vanes that throttle air or flue-gas flow. Locations include:
- Burner air registers / inlet dampers (control combustion air)
- FD fan inlet or outlet dampers
- ID fan inlet dampers or variable-speed control
- Stack or breeching dampers (isolation or draft control on some plants)
Damper position is part of the air–fuel ratio . A stuck closed inlet damper starves the fire; a stuck open damper can overcool the furnace with excess air. On automatic package burners, damper motors and linkages are calibrated with the fuel valve (parallel positioning or fully metered systems). Never “fix” a linkage without understanding the combustion curve — you can create a smoky or oxidizing fire that damages tubes and wastes fuel.
Breeching and Chimney
- Component Role
- Breeching The ductwork that carries flue gas from the boiler outlet to the chimney/stack or ID fan
- Chimney / stack Vertical path that discharges gases outdoors and, on natural-draft plants, helps create draft
- Baffles (inside boiler) Direct gases across heating surface before they enter the breeching
Keep breeching gas-tight where designed , supported, and free of heavy soot accumulation. Leaks on a negative system pull cold air into the gas path and hurt draft/efficiency; leaks on a positive system can spill flue gas into the boiler room — a carbon monoxide hazard.
Draft and the Combustion Triangle
Draft equipment is how the plant delivers the oxygen leg and removes products of combustion :
- Too little draft/air → incomplete combustion, smoke, soot, CO (Section 6.1)
- Too much draft/air → excess air heat loss (Section 6.4)
- Unstable draft → unstable flame, nuisance flame-safeguard trips, hard light-offs
When Arkansas sample material asks you to name draft types or define forced vs induced, answer with fan location and push vs pull , not with brand names. When you walk a real Arkansas boiler room, find the FD fan, the ID fan (if any), the breeching, and the stack dampers — that map is your airflow story for every light-off and every smoky stack complaint.