11.1 Ampacity Table 310.16 Application
Arkansas Journeyman Electrician Exam Study Guide 2026
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Arkansas Exam Overview
1.1 Current Exam Facts 1.2 Arkansas Licensing Pathway & Board Process 1.3 Open-Book Rules & Allowed References 1.4 NEC 2023 Navigation & Lookup Strategy
2 Electrical Theory & Trade Calculations
2.1 Ohm's Law, Power, and Basic Circuits 2.2 Series, Parallel, and Combination Circuits 2.3 Voltage Drop Calculations 2.4 Box Fill Calculations (314.16)
3 Load Calculations (Article 220)
3.1 Standard Dwelling Unit Load Calculations 3.2 Optional Dwelling & Multifamily Demand 3.3 Commercial / Non-Dwelling Demand Factors 3.4 Ampacity Adjustment & Correction (310.15)
4 Grounding Electrode Systems
4.1 Grounding Electrode Types & Installation 4.2 Grounding Electrode Conductor Sizing (250.66) 4.3 Main Bonding Jumper & Service Bonding
5 Equipment Grounding & Bonding
5.1 Equipment Grounding Conductors (250.122) 5.2 Bonding Raceways, Enclosures & Equipment 5.3 Separately Derived Systems Grounding
6 Services & Service Equipment
6.1 Service Entrance Conductors & Clearances 6.2 Service Disconnecting Means 6.3 Service Equipment & Working Space 6.4 Grounding Connections at the Service
7 Feeders & Overcurrent Protection
7.1 Feeder Conductor Sizing 7.2 Overcurrent Device Selection (Art 240) 7.3 Feeder and Branch-Circuit Tap Rules 7.4 Continuous Loads & OCPD Sizing
8 Branch Circuits, GFCI & AFCI
8.1 Branch-Circuit Ratings & Required Circuits 8.2 Dwelling Receptacle Placement & Kitchen/Bath Circuits 8.3 GFCI Protection Requirements 8.4 AFCI Protection Requirements
9 Metal Raceways
9.1 EMT Installation & Supports 9.2 RMC and IMC 9.3 Flexible Metal & Liquidtight Flexible Metal Conduit
10 Nonmetallic Raceways & Enclosures
10.1 PVC and ENT 10.2 Conduit Fill (Chapter 9 Tables) 10.3 Boxes, Conduit Bodies & Fill 10.4 Cabinets, Cutout Boxes & Meter Enclosures
11 Conductor Ampacity & Selection
11.1 Ampacity Table 310.16 Application 11.2 Termination Temperature Limitations 11.3 Conductor Insulation Types & Uses 11.4 Parallel Conductors
12 Cable Assemblies & Terminations
12.1 NM, MC, and AC Cable Assemblies 12.2 Conductor Identification & Color Coding 12.3 Splices, Taps & Terminations
13 Motors (Article 430)
13.1 Motor Nameplate Data & FLC Tables 13.2 Motor Branch-Circuit Conductors 13.3 Motor Overload Protection 13.4 Motor Short-Circuit / Ground-Fault Protection
14 Motor Controls & Transformers
14.1 Motor Disconnects & Controllers 14.2 Motor Control Circuits 14.3 Transformers (Article 450) for Journeymen
15 Utilization & General-Use Equipment
15.1 Luminaires & Lighting (Art 410) 15.2 Receptacles & Switches (Arts 406/404) 15.3 Appliances & Fixed Electric Space-Heating 15.4 Panelboards (Art 408)
16 Special Occupancies
16.1 Hazardous (Classified) Locations Overview 16.2 Health Care, Assembly & Temporary Installations 16.3 Swimming Pools, Spas & Similar Installations
17 Special Equipment Highlights
17.1 Signs & Outline Lighting 17.2 Elevators & Electric Vehicle Power Transfer 17.3 Emergency & Standby Systems Basics
18 Low-Voltage, Alarms & Communications
18.1 Class 1, 2, and 3 Circuits (Art 725) 18.2 Fire Alarm Systems (Art 760) 18.3 Communications Circuits Overview (Art 800+)
19 Electrical Safety
19.1 Working Space & Dedicated Equipment Space (110.26) 19.2 Lockout/Tagout & Safe Work Practices 19.3 Arc-Flash Awareness for the Exam
20 Exam Strategy & Test Day
20.1 Mixed Calculation Lab 20.2 Timed Code Lookup Drills 20.3 Test-Day Checklist, Scoring & Retakes
11.1 Ampacity Table 310.16 Application
Key Takeaways Explain This Topic AI
NEC 2023 Table 310.16 lists ampacity for insulated conductors through 2000 V in raceway, cable, or earth at 30°C ambient with not more than three current-carrying conductors.
Read the table by intersecting conductor size (row), copper or aluminum (material block), and the 60°C / 75°C / 90°C insulation-temperature column.
Table ampacity is a starting value — ambient correction, more than three current-carrying conductors, and termination limits can all reduce the usable ampacity.
Small-conductor overcurrent caps in 240.4(D) often control 14, 12, and 10 AWG copper even when Table 310.16 shows a higher number.
Arkansas journeyman items commonly ask which column applies and whether the table assumptions still match the installation described.
Last updated: August 2026
Why Table 310.16 Dominates Arkansas JW Ampacity Items
Quick Answer: For most copper and aluminum conductors in raceway, cable, or earth, start with NEC 2023 Table 310.16 . It assumes 30°C (86°F) ambient and not more than three current-carrying conductors . You select ampacity by size, material, and temperature column — then check whether correction, adjustment, termination limits, or 240.4(D) reduce what you may actually use.
The Arkansas journeyman electrician exam (Prov, Inc.; NEC 2023; typically scored as a timed multiple-choice open-book code exam with a 70% pass mark) tests whether you can apply ampacity, not whether you memorized every cell. Table 310.16 is the workhorse table for insulated conductors rated 0 through 2000 volts when those conductors are installed in a raceway, in a cable, or directly buried in earth. If the stem describes NM cable in a dwelling wall, THHN in EMT, or USE in a trench, you are usually in 310.16 territory until a special condition pushes you elsewhere.
Ampacity means the maximum current a conductor can carry continuously under the conditions of use without exceeding its temperature rating. The table already embeds assumptions. When the field conditions match those assumptions, the tabulated value is your base. When they do not, you still start from the table, then apply the modifiers required by Article 310 and related rules.
How the Table Is Organized
Read every lookup as three decisions:
Size — AWG or kcmil row (14 AWG through large kcmil sizes).
Material — copper block versus aluminum / copper-clad aluminum block. Aluminum needs a larger size for the same ampacity.
Temperature column — 60°C, 75°C, or 90°C, based on the insulation types listed under that column and the temperature you are allowed to use for the step you are on.
The columns increase left to right for the same size: a given copper conductor shows a lower ampacity at 60°C than at 75°C, and the 90°C value is highest. That does not mean you always take the 90°C number as final circuit ampacity. Insulation rating, wet/dry location suitability, and 110.14(C) termination limits decide which column governs the selected conductor size for the circuit. Section 11.2 covers terminations in depth; here the exam skill is recognizing that Table 310.16 gives multiple numbers for one size and you must know which one you are allowed to claim.
Representative Copper Values (Table 310.16 excerpt)
- Size 60°C 75°C 90°C
- 14 AWG 15 A 20 A 25 A
- 12 AWG 20 A 25 A 30 A
- 10 AWG 30 A 35 A 40 A
- 8 AWG 40 A 50 A 55 A
- 6 AWG 55 A 65 A 75 A
- 4 AWG 70 A 85 A 95 A
- 2 AWG 95 A 115 A 130 A
- 1/0 AWG 125 A 150 A 170 A
- 4/0 AWG 195 A 230 A 260 A
- 500 kcmil 320 A 380 A 430 A
Memorizing every row is unnecessary on an open-book exam, but knowing the pattern and the common branch-circuit sizes (14 through 6 AWG, plus 1/0 and 4/0 for feeders) saves time under the clock.
Table Conditions You Must Verify
Before you treat a tabulated ampacity as usable:
Ambient temperature. Table values assume 30°C . Hotter attics, rooftops, or boiler rooms require ambient correction factors from the Article 310 correction tables. Cooler ambients can allow higher values when the code permits.
Number of current-carrying conductors. More than three CCC in a raceway or cable typically requires an adjustment (derating) factor. Neutrals and EGCs have counting rules of their own — do not confuse raceway fill percentage with ampacity adjustment counting.
Wiring method. Conductors in free air use different tables (for example Table 310.17). Do not apply 310.16 numbers to a free-air stem.
Continuous load. Continuous loads (three hours or more) generally require conductors and overcurrent devices sized at 125% of the continuous portion, which affects the ampacity you must provide even when the table lookup is correct.
Worked Arkansas-style lookup
A feeder uses 4 AWG copper THHN in EMT with three current-carrying conductors in a 30°C space, terminating on 75°C-rated equipment. THHN insulation is listed under the 90°C column, so the 90°C table value is 95 A . Because terminations are 75°C, the conductor must also be adequate at the 75°C value of 85 A . If the calculated load (after continuous-load multipliers) is 80 A, 4 AWG copper works at 75°C. If the load is 90 A continuous-adjusted, you need a larger size even though the 90°C column looked tempting.
Small-Conductor Caps vs Table Numbers
For 14, 12, and 10 AWG , Table 310.16 can show values above everyday breaker sizes. 240.4(D) generally caps overcurrent protection at 15 A (14 AWG copper), 20 A (12 AWG copper), and 30 A (10 AWG copper), with stated exceptions. Exam traps offer the 90°C table ampacity as if it were the breaker rating. Separate “what is the table ampacity?” from “what OCPD is permitted?”
Exam Workflow Margin Notes
Identify copper or aluminum and insulation type.
Confirm raceway/cable/earth → Table 310.16 (not free-air).
Read the column allowed for this step (insulation vs termination).
Apply ambient correction and CCC adjustment if required.
Check continuous-load and 240.4(D) limits.
Select the smallest conductor that still meets every limit.
Arkansas JW questions rarely stop at a single cell. They reward the candidate who treats 310.16 as the start of a sizing chain, not the entire answer.