7.4 Continuous Loads & OCPD Sizing

Arkansas Journeyman Electrician Exam Study Guide 2026

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Arkansas Exam Overview

1.1 Current Exam Facts 1.2 Arkansas Licensing Pathway & Board Process 1.3 Open-Book Rules & Allowed References 1.4 NEC 2023 Navigation & Lookup Strategy

2 Electrical Theory & Trade Calculations

2.1 Ohm's Law, Power, and Basic Circuits 2.2 Series, Parallel, and Combination Circuits 2.3 Voltage Drop Calculations 2.4 Box Fill Calculations (314.16)

3 Load Calculations (Article 220)

3.1 Standard Dwelling Unit Load Calculations 3.2 Optional Dwelling & Multifamily Demand 3.3 Commercial / Non-Dwelling Demand Factors 3.4 Ampacity Adjustment & Correction (310.15)

4 Grounding Electrode Systems

4.1 Grounding Electrode Types & Installation 4.2 Grounding Electrode Conductor Sizing (250.66) 4.3 Main Bonding Jumper & Service Bonding

5 Equipment Grounding & Bonding

5.1 Equipment Grounding Conductors (250.122) 5.2 Bonding Raceways, Enclosures & Equipment 5.3 Separately Derived Systems Grounding

6 Services & Service Equipment

6.1 Service Entrance Conductors & Clearances 6.2 Service Disconnecting Means 6.3 Service Equipment & Working Space 6.4 Grounding Connections at the Service

7 Feeders & Overcurrent Protection

7.1 Feeder Conductor Sizing 7.2 Overcurrent Device Selection (Art 240) 7.3 Feeder and Branch-Circuit Tap Rules 7.4 Continuous Loads & OCPD Sizing

8 Branch Circuits, GFCI & AFCI

8.1 Branch-Circuit Ratings & Required Circuits 8.2 Dwelling Receptacle Placement & Kitchen/Bath Circuits 8.3 GFCI Protection Requirements 8.4 AFCI Protection Requirements

9 Metal Raceways

9.1 EMT Installation & Supports 9.2 RMC and IMC 9.3 Flexible Metal & Liquidtight Flexible Metal Conduit

10 Nonmetallic Raceways & Enclosures

10.1 PVC and ENT 10.2 Conduit Fill (Chapter 9 Tables) 10.3 Boxes, Conduit Bodies & Fill 10.4 Cabinets, Cutout Boxes & Meter Enclosures

11 Conductor Ampacity & Selection

11.1 Ampacity Table 310.16 Application 11.2 Termination Temperature Limitations 11.3 Conductor Insulation Types & Uses 11.4 Parallel Conductors

12 Cable Assemblies & Terminations

12.1 NM, MC, and AC Cable Assemblies 12.2 Conductor Identification & Color Coding 12.3 Splices, Taps & Terminations

13 Motors (Article 430)

13.1 Motor Nameplate Data & FLC Tables 13.2 Motor Branch-Circuit Conductors 13.3 Motor Overload Protection 13.4 Motor Short-Circuit / Ground-Fault Protection

14 Motor Controls & Transformers

14.1 Motor Disconnects & Controllers 14.2 Motor Control Circuits 14.3 Transformers (Article 450) for Journeymen

15 Utilization & General-Use Equipment

15.1 Luminaires & Lighting (Art 410) 15.2 Receptacles & Switches (Arts 406/404) 15.3 Appliances & Fixed Electric Space-Heating 15.4 Panelboards (Art 408)

16 Special Occupancies

16.1 Hazardous (Classified) Locations Overview 16.2 Health Care, Assembly & Temporary Installations 16.3 Swimming Pools, Spas & Similar Installations

17 Special Equipment Highlights

17.1 Signs & Outline Lighting 17.2 Elevators & Electric Vehicle Power Transfer 17.3 Emergency & Standby Systems Basics

18 Low-Voltage, Alarms & Communications

18.1 Class 1, 2, and 3 Circuits (Art 725) 18.2 Fire Alarm Systems (Art 760) 18.3 Communications Circuits Overview (Art 800+)

19 Electrical Safety

19.1 Working Space & Dedicated Equipment Space (110.26) 19.2 Lockout/Tagout & Safe Work Practices 19.3 Arc-Flash Awareness for the Exam

20 Exam Strategy & Test Day

20.1 Mixed Calculation Lab 20.2 Timed Code Lookup Drills 20.3 Test-Day Checklist, Scoring & Retakes

7.4 Continuous Loads & OCPD Sizing

Key Takeaways Explain This Topic AI

A continuous load is expected to continue for 3 hours or more (Art. 100) — lighting and process loads are frequent continuous-load flags on Prov stems

Branch-circuit and feeder OCPDs are generally sized at not less than 125% of continuous load plus 100% of noncontinuous load (210.19/210.20 and 215.2/215.3 parallel logic)

NEC 215.3 requires feeder overcurrent devices to have a rating not less than the noncontinuous load plus 125% of the continuous load unless listed for 100% operation

Conductor ampacity (215.2) and OCPD rating (215.3 / 210.20) both carry 125% continuous-load logic — calculate each, then apply 240.4 pairing

Next-size-up under 240.4(B) does not erase the continuous-load 125% calculation; compute the minimum rating first, then select a standard device

Last updated: August 2026

Continuous Loads Tie Feeder Ampacity to Breaker Size

Sections 7.1–7.3 taught feeder ampacity, Article 240 device selection, and taps. This section welds them together with the continuous-load 125% rules that appear repeatedly on the Arkansas Journeyman (Prov) exam. If you remember only one sizing slogan for this chapter, make it: size for continuous load at 125%, then pick a standard OCPD that protects the conductors under 240.4 .

Tab Article 100 (Continuous Load) , 210.19 , 210.20 , 215.2 , 215.3 , 230.42 (for service comparisons), 240.4 , and 240.6 .

Definition — Continuous Load

Continuous load (Art. 100): A load where the maximum current is expected to continue for 3 hours or more .

Exam recognition cues:

Store or warehouse lighting left on for business hours.

Office lighting and certain receptacle loads treated as continuous in design notes.

Industrial process heaters or equipment specified as continuous.

Stems that explicitly say “continuous load” or “operates for 3 hours or more.”

If the stem does not establish continuity, do not invent a 125% adder for the entire load. Conversely, when the stem says continuous, missing the 125% factor is an instant miss.

Why 125% Exists

Continuous current heats conductors and OCPDs for extended periods. The Code’s 125% factor builds margin into:

Conductor ampacity requirements for feeders and branch circuits.

OCPD ratings that supply those circuits (unless equipment is listed for operation at 100% of its rating under the applicable section).

Think of 125% as applying to the continuous portion , then adding noncontinuous load at 100%, unless a specific rule says otherwise.

Branch-Circuit Continuous-Load Rules — 210.19 / 210.20

For branch circuits (needed because feeder stems sometimes mix in branch math, and the same 125% logic appears in both places):

210.19(A) — branch-circuit conductors shall have ampacity not less than the maximum load to be served; for continuous loads, ampacity not less than noncontinuous + 125% continuous (parallel structure to feeders).

210.20(A) — branch-circuit OCPDs shall have a rating not less than the noncontinuous load plus 125% of the continuous load , with the listed 100%-rated assembly exception path.

These branch rules mirror feeder rules so you do not learn two contradictory formulas.

  • Feeder Continuous-Load Rules — 215.2 / 215.3
  • Conductors — 215.2(A)(1)

Feeder conductor ampacity ≥ noncontinuous load + 125% continuous load (absent the listed-assembly exception).

Overcurrent devices — 215.3

215.3 requires the feeder overcurrent device rating / setting to be not less than the noncontinuous load plus 125% of the continuous load . Exception: where the assembly — including the OCPD — is listed for operation at 100% of its rating, the continuous load may be permitted up to the device’s rating under the exception’s conditions.

Prov paired question pattern:

Compute minimum feeder ampacity (215.2).

Compute minimum OCPD rating (215.3).

Choose conductors from Table 310.16 that meet ampacity.

Choose a standard OCPD from 240.6(A) that is ≥ the 215.3 minimum.

Verify 240.4 still protects those conductors (including 240.4(B)/(C)/(D) as applicable).

Often the conductor ampacity minimum and the OCPD minimum calculate to the same 125% number before standard-size rounding — then 240.4(B) may allow the next standard size above conductor ampacity when conditions are met.

Worked Example (Open-Book Style)

Feeder load: 80 A continuous + 30 A noncontinuous .

Minimum ampacity / minimum OCPD basis = 30 + (80 × 1.25) = 30 + 100 = 130 A .

Conductors: select a copper size from Table 310.16 (correct temperature column) with ampacity ≥ 130 A after adjustment/correction.

OCPD: 130 A is not a standard 240.6(A) rating. Nearby standards include 125 A and 150 A . Because 125 A is below the 130 A continuous-load minimum, 125 A is too small . Select 150 A if that rating also satisfies conductor protection rules.

Confirm the chosen conductors’ ampacity can be protected by 150 A under 240.4 (next-size-up / ampacity relationship).

Trap: Calculating 80 + 30 = 110 A and picking a 110 A or 125 A breaker without the continuous 125% adder.

100%-Rated Assemblies — Use Only When the Stem Gives Them

The exception path for equipment listed for 100% continuous operation is real, but Prov distractors love it. Apply it only when:

The stem states the breaker/assembly is listed/rated for 100% operation, and

You verify the exception language in 215.3 / 210.20 (and related equipment standards).

Otherwise, default to 125% of continuous + 100% noncontinuous .

Interaction with Services (Do Not Cross-Wire Articles)

230.42 uses the same continuous-load philosophy for service-entrance conductors . That does not mean you cite 230.42 on a feeder stem. Identity check:

  • System part Continuous-load conductor rule Continuous-load OCPD rule
  • Service-entrance 230.42 Service OCPD rules in Art. 230 + 240 as applicable
  • Feeder 215.2 215.3
  • Branch circuit 210.19 210.20

Same math family, different section numbers — answers are often wrong solely because of the wrong article citation in a “which section requires…” stem.

Continuous Loads on Taps

If a feeder tap terminates in an OCPD that supplies continuous load, the terminating device still needs the 215.3 / 210.20 continuous-load rating logic for what it supplies. The upstream feeder OCPD protecting the large feeder is sized for the feeder’s load; the tap rule only allows unprotected (or differently protected) conductor length under 240.21 — it does not erase continuous-load sizing at the load-end device.

Multioutlet and Receptacle Nuances

For branch circuits supplying cord-and-plug connected equipment, continuous-load and receptacle rules interact with Article 210 ratings. Also remember 240.4(B) denies next-size-up for certain multi-receptacle portable-load branch circuits. Continuous-load math and next-size-up permission are independent checks — both must pass.

Practical Exam Checklist — Continuous Load Stems

Does the stem establish a continuous load (definition or explicit label)?

Split continuous vs noncontinuous amperes.

Compute I_req = noncontinuous + 1.25 × continuous .

Apply I_req to conductors ( 215.2 / 210.19 ) and to OCPDs ( 215.3 / 210.20 ).

Select standard OCPD ≥ I_req from 240.6(A) .

Confirm 240.4 conductor protection (small-conductor caps, ≤800 A next size, >800 A no round-up).

Only if listed 100%-rated assembly is in the stem, reopen the exception.

Timed Tips for the Whole Chapter 7 Cluster

Feeder identity first (Art. 100 / 215 vs 230 vs 210).

Continuous 125% next (215.2 / 215.3).

Table 310.16 + 110.14(C) for conductors.

240.6 + 240.4 for device pairing.

240.21 only when length-from-supply / tap language appears.

Mastering that order turns the 8-item Services/Feeders/OCP block into a lookup sequence instead of a memory contest on a 3-hour, 60-question, 70% Prov Arkansas JW exam using NEC 2023 .