Study guide

4.2 Grounding Electrode Conductor Sizing (250.66)

Arkansas Journeyman Electrician Exam Study Guide 2026

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Arkansas Exam Overview

1.1 Current Exam Facts 1.2 Arkansas Licensing Pathway & Board Process 1.3 Open-Book Rules & Allowed References 1.4 NEC 2023 Navigation & Lookup Strategy

2 Electrical Theory & Trade Calculations

2.1 Ohm's Law, Power, and Basic Circuits 2.2 Series, Parallel, and Combination Circuits 2.3 Voltage Drop Calculations 2.4 Box Fill Calculations (314.16)

3 Load Calculations (Article 220)

3.1 Standard Dwelling Unit Load Calculations 3.2 Optional Dwelling & Multifamily Demand 3.3 Commercial / Non-Dwelling Demand Factors 3.4 Ampacity Adjustment & Correction (310.15)

4 Grounding Electrode Systems

4.1 Grounding Electrode Types & Installation 4.2 Grounding Electrode Conductor Sizing (250.66) 4.3 Main Bonding Jumper & Service Bonding

5 Equipment Grounding & Bonding

5.1 Equipment Grounding Conductors (250.122) 5.2 Bonding Raceways, Enclosures & Equipment 5.3 Separately Derived Systems Grounding

6 Services & Service Equipment

6.1 Service Entrance Conductors & Clearances 6.2 Service Disconnecting Means 6.3 Service Equipment & Working Space 6.4 Grounding Connections at the Service

7 Feeders & Overcurrent Protection

7.1 Feeder Conductor Sizing 7.2 Overcurrent Device Selection (Art 240) 7.3 Feeder and Branch-Circuit Tap Rules 7.4 Continuous Loads & OCPD Sizing

8 Branch Circuits, GFCI & AFCI

8.1 Branch-Circuit Ratings & Required Circuits 8.2 Dwelling Receptacle Placement & Kitchen/Bath Circuits 8.3 GFCI Protection Requirements 8.4 AFCI Protection Requirements

9 Metal Raceways

9.1 EMT Installation & Supports 9.2 RMC and IMC 9.3 Flexible Metal & Liquidtight Flexible Metal Conduit

10 Nonmetallic Raceways & Enclosures

10.1 PVC and ENT 10.2 Conduit Fill (Chapter 9 Tables) 10.3 Boxes, Conduit Bodies & Fill 10.4 Cabinets, Cutout Boxes & Meter Enclosures

11 Conductor Ampacity & Selection

11.1 Ampacity Table 310.16 Application 11.2 Termination Temperature Limitations 11.3 Conductor Insulation Types & Uses 11.4 Parallel Conductors

12 Cable Assemblies & Terminations

12.1 NM, MC, and AC Cable Assemblies 12.2 Conductor Identification & Color Coding 12.3 Splices, Taps & Terminations

13 Motors (Article 430)

13.1 Motor Nameplate Data & FLC Tables 13.2 Motor Branch-Circuit Conductors 13.3 Motor Overload Protection 13.4 Motor Short-Circuit / Ground-Fault Protection

14 Motor Controls & Transformers

14.1 Motor Disconnects & Controllers 14.2 Motor Control Circuits 14.3 Transformers (Article 450) for Journeymen

15 Utilization & General-Use Equipment

15.1 Luminaires & Lighting (Art 410) 15.2 Receptacles & Switches (Arts 406/404) 15.3 Appliances & Fixed Electric Space-Heating 15.4 Panelboards (Art 408)

16 Special Occupancies

16.1 Hazardous (Classified) Locations Overview 16.2 Health Care, Assembly & Temporary Installations 16.3 Swimming Pools, Spas & Similar Installations

17 Special Equipment Highlights

17.1 Signs & Outline Lighting 17.2 Elevators & Electric Vehicle Power Transfer 17.3 Emergency & Standby Systems Basics

18 Low-Voltage, Alarms & Communications

18.1 Class 1, 2, and 3 Circuits (Art 725) 18.2 Fire Alarm Systems (Art 760) 18.3 Communications Circuits Overview (Art 800+)

19 Electrical Safety

19.1 Working Space & Dedicated Equipment Space (110.26) 19.2 Lockout/Tagout & Safe Work Practices 19.3 Arc-Flash Awareness for the Exam

20 Exam Strategy & Test Day

20.1 Mixed Calculation Lab 20.2 Timed Code Lookup Drills 20.3 Test-Day Checklist, Scoring & Retakes

4.2 Grounding Electrode Conductor Sizing (250.66)

Key Takeaways Explain This Topic AI

Size the grounding electrode conductor from Table 250.66 based on the largest ungrounded service-entrance conductor or equivalent area for parallel conductors

Table 250.66 copper GEC sizes step from 8 AWG (for 2 AWG or smaller service) up through 3/0 AWG copper for the largest service sizes listed

Exception 250.66(A): the GEC to a rod, pipe, or plate electrode need not be larger than 6 AWG copper

Exception 250.66(B): the GEC to a concrete-encased electrode need not be larger than 4 AWG copper

  • Exception 250.66(C): the GEC to a ground ring need not be larger than the conductor used for the ground ring
  • Last updated: August 2026

Exam Role of 250.66

On the Arkansas Journeyman Prov exam, grounding electrode conductor (GEC) sizing is a high-yield Article 250 calculation. The stem usually gives the ungrounded service-entrance conductor size (or kcmil), names the electrode type, and asks for the minimum GEC. Your workflow is always:

Find the largest ungrounded service-entrance conductor (or equivalent area for parallel conductors).

Open Table 250.66 and read the required copper (or aluminum) GEC.

Check whether the GEC terminates only to a rod/pipe/plate , concrete-encased electrode , or ground ring — if so, apply 250.66(A), (B), or (C) so you do not oversize beyond the Code maximum required for that electrode type.

Still obey installation rules in 250.64 (continuous, protected, splicing limits).

Do not size the GEC from the overcurrent device rating using Table 250.122 — that table is for equipment grounding conductors, covered in the next chapter.

What Table 250.66 Uses as the Input

250.66 sizes the GEC from the largest ungrounded service-entrance conductor or equivalent area for parallel conductors . For a typical 120/240 V residential or light-commercial service, that is the hot service conductor size (for example, 4/0 AWG aluminum or 3/0 AWG copper).

If service-entrance conductors are paralleled, compute the equivalent area (sum of the circular mil areas of the paralleled ungrounded conductors in each set) and enter Table 250.66 with that equivalent size — do not pick one conductor of the parallel set alone.

Where the ungrounded supply conductors are larger than the service-entrance conductors (unusual exam setups), read 250.66 and related notes carefully; most Prov items stick to a clear service-entrance size.

Table 250.66 — Copper GEC Snapshot (verify in your NEC)

Open the live table in NEC 2023 . The copper column relationships you will use constantly are:

  • Largest ungrounded service-entrance conductor or equivalent area (copper AWG/kcmil) Copper GEC (AWG/kcmil)
  • 2 AWG or smaller 8
  • 1 or 1/0 AWG 6
  • 2/0 or 3/0 AWG 4
  • Over 3/0 AWG through 350 kcmil 2
  • Over 350 kcmil through 600 kcmil 1/0
  • Over 600 kcmil through 1100 kcmil 2/0
  • Over 1100 kcmil 3/0

Aluminum or copper-clad aluminum GEC sizes are larger for the same service conductor row — always read the matching column in your book. On timed exams, confirm whether the stem asks for copper or aluminum GEC.

Worked Example 1 — Table only

Service: 4/0 AWG copper ungrounded service-entrance conductors to a service disconnect that bonds to a metal water pipe and building steel (full electrode system).

4/0 AWG copper is over 3/0 through 350 kcmil → Table 250.66 copper GEC = 2 AWG .

No 250.66(A)/(B)/(C) reduction applies to the water-pipe/building-steel connections that require the full table size.

Answer: 2 AWG copper GEC (minimum).

Worked Example 2 — Parallel service conductors

Service: two paralleled 3/0 AWG copper ungrounded conductors per phase.

Equivalent area ≈ 2 × 167,800 cmil = 335,600 cmil → treat as over 3/0 through 350 kcmil for Table 250.66 entry (verify cmil values in Chapter 9 Table 8).

Copper GEC from Table 250.66 = 2 AWG .

If the stem instead gave two paralleled 500 kcmil copper conductors, equivalent area = 1,000,000 cmil → over 600 through 1100 → copper GEC 2/0 AWG .

The Three Electrode Caps — 250.66(A), (B), (C)

These are not free passes to undersize every GEC on the job. They apply when the GEC is the sole connection to that electrode type (read each subsection’s exact connection language).

250.66(A) — Rod, pipe, or plate electrodes

Where the GEC is connected to rod, pipe, or plate electrodes as permitted in 250.52(A)(5) or (A)(7) , that portion of the conductor that is the sole connection to the rod/pipe/plate electrode shall not be required to be larger than 6 AWG copper wire or 4 AWG aluminum wire.

Worked Example 3 — Rod only:

Service ungrounded conductors: 500 kcmil copper . Electrodes present: two ground rods only (no water pipe, no ufer, no ring).

Table 250.66 alone would call for 1/0 AWG copper (over 350 through 600).

Because the GEC is the sole connection to rod electrodes, 250.66(A) caps the required size at 6 AWG copper .

Exam answer: 6 AWG copper , not 1/0.

250.66(B) — Concrete-encased electrode

Where connected to a concrete-encased electrode as permitted in 250.52(A)(3) , that portion of the conductor that is the sole connection to the concrete-encased electrode shall not be required to be larger than 4 AWG copper wire.

Worked Example 4 — Ufer only:

Service: 750 kcmil copper ungrounded service-entrance conductors. Only electrode: concrete-encased rebar electrode.

Table 250.66 → 2/0 AWG copper (over 600 through 1100).

250.66(B) → not required larger than 4 AWG copper for the sole connection to the ufer.

250.66(C) — Ground ring

Where connected to a ground ring , that portion of the conductor that is the sole connection to the ground ring shall not be required to be larger than the conductor used for the ground ring.

Worked Example 5 — Ground ring:

Ground ring installed with 2 AWG bare copper (minimum size under 250.52(A)(4) ). Service conductors would otherwise require 1/0 GEC from Table 250.66.

Sole connection to the ring → GEC need not be larger than the 2 AWG ring conductor.

If the ring were installed with 1/0 AWG copper (larger than Code minimum), the sole-connection GEC would not need to exceed that 1/0 ring conductor — still verify Table 250.66 does not require something smaller; you never install smaller than both the table and the applicable cap require as a minimum pathway.

Mixed Electrode Systems — Do Not Over-Apply the Cap

If the building has a metal water pipe electrode and rods, the GEC that serves the water pipe (and the bonding that creates the full system) is still sized from Table 250.66 without using the 6 AWG rod cap for the water-pipe connection. The tap or bonding jumper that is the sole connection to the rods may be limited per 250.66(A) .

Worked Example 6 — Water pipe + rods:

Service: 3/0 AWG copper → Table 250.66 = 4 AWG copper GEC to the service grounding point / water-pipe electrode system.

A bonding jumper that is the sole connection from that system to a supplemental ground rod need not be larger than 6 AWG copper per 250.66(A) .

Prov will often ask only one piece: either the main GEC size from the table or the capped size to the rod. Match the stem.

Installation Notes That Appear Beside Sizing Questions

Sizing is 250.66 ; routing is 250.64 :

GEC shall be installed in one continuous length without a splice or joint except as permitted (irreversible compression-type connectors listed as grounding and bonding equipment, exothermic welding, busbars, etc.).

Protect where exposed to physical damage; raceway protection rules differ for smaller GECs.

Aluminum or copper-clad aluminum GEC terminations have exterior/enclosure restrictions — read 250.64(A) .

On an open-book Arkansas exam, if the options mix a correctly capped rod GEC with an incorrectly applied Table 250.122 EGC size, pick the Article 250.66 path.

Quick Drill Pattern for Prov Timing

  • Stem pattern First open Then check
  • “Minimum GEC for ___ service conductors” (no electrode named) Table 250.66 Material column
  • “GEC to ground rods only” Table 250.66 Cap at 6 AWG Cu via 250.66(A)
  • “GEC to concrete-encased electrode only” Table 250.66 Cap at 4 AWG Cu via 250.66(B)
  • “GEC to ground ring only” Table 250.66 Cap at ring conductor size via 250.66(C)
  • “Water pipe electrode present” Table 250.66 full size Do not apply rod-only cap to the water-pipe GEC

Memorize the lookup order; verify every AWG in the 2023 tables on exam day.