Study guide
18.2 Fire Alarm Systems (Art 760)
Arkansas Journeyman Electrician Exam Study Guide 2026
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Arkansas Exam Overview
1.1 Current Exam Facts 1.2 Arkansas Licensing Pathway & Board Process 1.3 Open-Book Rules & Allowed References 1.4 NEC 2023 Navigation & Lookup Strategy
2 Electrical Theory & Trade Calculations
2.1 Ohm's Law, Power, and Basic Circuits 2.2 Series, Parallel, and Combination Circuits 2.3 Voltage Drop Calculations 2.4 Box Fill Calculations (314.16)
3 Load Calculations (Article 220)
3.1 Standard Dwelling Unit Load Calculations 3.2 Optional Dwelling & Multifamily Demand 3.3 Commercial / Non-Dwelling Demand Factors 3.4 Ampacity Adjustment & Correction (310.15)
4 Grounding Electrode Systems
4.1 Grounding Electrode Types & Installation 4.2 Grounding Electrode Conductor Sizing (250.66) 4.3 Main Bonding Jumper & Service Bonding
5 Equipment Grounding & Bonding
5.1 Equipment Grounding Conductors (250.122) 5.2 Bonding Raceways, Enclosures & Equipment 5.3 Separately Derived Systems Grounding
6 Services & Service Equipment
6.1 Service Entrance Conductors & Clearances 6.2 Service Disconnecting Means 6.3 Service Equipment & Working Space 6.4 Grounding Connections at the Service
7 Feeders & Overcurrent Protection
7.1 Feeder Conductor Sizing 7.2 Overcurrent Device Selection (Art 240) 7.3 Feeder and Branch-Circuit Tap Rules 7.4 Continuous Loads & OCPD Sizing
8 Branch Circuits, GFCI & AFCI
8.1 Branch-Circuit Ratings & Required Circuits 8.2 Dwelling Receptacle Placement & Kitchen/Bath Circuits 8.3 GFCI Protection Requirements 8.4 AFCI Protection Requirements
9 Metal Raceways
9.1 EMT Installation & Supports 9.2 RMC and IMC 9.3 Flexible Metal & Liquidtight Flexible Metal Conduit
10 Nonmetallic Raceways & Enclosures
10.1 PVC and ENT 10.2 Conduit Fill (Chapter 9 Tables) 10.3 Boxes, Conduit Bodies & Fill 10.4 Cabinets, Cutout Boxes & Meter Enclosures
11 Conductor Ampacity & Selection
11.1 Ampacity Table 310.16 Application 11.2 Termination Temperature Limitations 11.3 Conductor Insulation Types & Uses 11.4 Parallel Conductors
12 Cable Assemblies & Terminations
12.1 NM, MC, and AC Cable Assemblies 12.2 Conductor Identification & Color Coding 12.3 Splices, Taps & Terminations
13 Motors (Article 430)
13.1 Motor Nameplate Data & FLC Tables 13.2 Motor Branch-Circuit Conductors 13.3 Motor Overload Protection 13.4 Motor Short-Circuit / Ground-Fault Protection
14 Motor Controls & Transformers
14.1 Motor Disconnects & Controllers 14.2 Motor Control Circuits 14.3 Transformers (Article 450) for Journeymen
15 Utilization & General-Use Equipment
15.1 Luminaires & Lighting (Art 410) 15.2 Receptacles & Switches (Arts 406/404) 15.3 Appliances & Fixed Electric Space-Heating 15.4 Panelboards (Art 408)
16 Special Occupancies
16.1 Hazardous (Classified) Locations Overview 16.2 Health Care, Assembly & Temporary Installations 16.3 Swimming Pools, Spas & Similar Installations
17 Special Equipment Highlights
17.1 Signs & Outline Lighting 17.2 Elevators & Electric Vehicle Power Transfer 17.3 Emergency & Standby Systems Basics
18 Low-Voltage, Alarms & Communications
18.1 Class 1, 2, and 3 Circuits (Art 725) 18.2 Fire Alarm Systems (Art 760) 18.3 Communications Circuits Overview (Art 800+)
19 Electrical Safety
19.1 Working Space & Dedicated Equipment Space (110.26) 19.2 Lockout/Tagout & Safe Work Practices 19.3 Arc-Flash Awareness for the Exam
20 Exam Strategy & Test Day
20.1 Mixed Calculation Lab 20.2 Timed Code Lookup Drills 20.3 Test-Day Checklist, Scoring & Retakes
18.2 Fire Alarm Systems (Art 760)
Key Takeaways Explain This Topic AI
Article 760 covers fire alarm system wiring and splits circuits into non–power-limited (NPLFA) and power-limited (PLFA) fire alarm circuits
PLFA circuits use listed power-limited fire alarm sources and cable types such as FPL, FPLR, and FPLP (and allowed substitutes)
NPLFA circuits generally follow Chapter 3-style wiring methods because their energy levels are not limited like PLFA
Separation rules keep power-limited fire alarm conductors apart from power/light/Class 1 conductors unless barriers or Code exceptions apply
Survivability, abandoned cable, and correct article choice (760 vs 725 vs Chapter 8) are high-yield Prov open-book themes
Last updated: August 2026
18.2 Fire Alarm Systems (Art 760)
Quick Answer: Fire alarm wiring lives in Article 760 , not Article 725. Decide first whether the circuit is non–power-limited fire alarm (NPLFA) or power-limited fire alarm (PLFA) . NPLFA uses Chapter 3–style methods. PLFA uses listed power-limited sources and fire-alarm cable families ( FPL / FPLR / FPLP and permitted substitutes). Keep PLFA conductors separated from power and light conductors unless 760 separation rules allow a barrier or other method.
Arkansas Prov’s low-voltage outline explicitly includes alarms . Even with only two LV items on the 60-question exam, a fire-alarm stem is a realistic draw: cable type in a riser or plenum, power-limited vs non–power-limited identity, separation from power, or abandoned cable. Journeyman electricians also pull fire-alarm raceways and cables alongside building power work, so Article 760 literacy is professional competence, not niche trivia.
Article 760 scope and boundaries
Article 760 covers the installation of wiring and equipment of fire alarm systems, including all circuits controlled and powered by the fire alarm system. Related signaling that is truly Class 2/Class 3 remote-control under Article 725 is not automatically fire alarm wiring—read the stem. If the system is a fire alarm system circuit, stay in 760 .
Do not confuse:
- System / circuit Primary article
- Fire alarm (NPLFA / PLFA) 760
- Class 1/2/3 remote-control & signaling 725
- Communications (telephone, data premises circuits under Chapter 8) 800+
- Emergency systems / legally required standby (broader power reliability) 700 / 701 (different topic)
Fire alarm circuits may interact with power supplies, batteries, and notification appliances, but the wiring classification questions on Prov almost always want 760 cable/separation answers.
- NPLFA vs PLFA — the first branch in every lookup
- Non–power-limited fire alarm (NPLFA)
NPLFA circuits are not limited to the low energy levels of PLFA. Because the available energy can be hazardous, NPLFA wiring methods generally track Chapter 3 power wiring practices: suitable raceways/cables, boxes, and conductor rules for the voltage and location. Think “fire alarm circuit that behaves like a power circuit for wiring-method purposes.”
Power-limited fire alarm (PLFA)
PLFA circuits are supplied from listed power-limited fire alarm sources meeting the power limitations referenced by Article 760 (aligned with limited-energy philosophy similar to Class 2/3, but under fire-alarm-specific rules and markings). PLFA is the common modern initiating-device and signaling-line style of limited-energy fire alarm wiring on many projects.
Exam key: The label “fire alarm” alone does not tell you NPLFA vs PLFA. The stem must give source type, voltage/power-limited language, or cable marking ( FPL… ). If it says power-limited fire alarm or shows FPL cable, you are in the PLFA part of 760.
PLFA power sources and circuit integrity
Article 760 requires PLFA circuits to be supplied from sources that meet the article’s power-source requirements (listed fire alarm power-limited supplies, and related permitted sources as stated in the Code year). Overcurrent protection, grounding of supplies, and circuit arrangement follow the PLFA sections—do not protect a PLFA circuit with a random 20 A lighting breaker as if it were a general branch circuit.
Battery-backed fire alarm control units and notification-appliance circuits have additional product-listing and manufacturer requirements. For the Journeyman exam, focus on NEC installation rules : wiring method, separation, cable type, support, and abandoned cable—not NFPA 72 design calculations unless the stem expressly goes there. Prov’s reference list for this exam centers on the NEC 2023 ; use that book.
Fire alarm cable types and substitutions
Power-limited fire alarm cables are commonly marked:
- Marking Typical use theme
- FPL General-purpose power-limited fire alarm cable
- FPLR Riser-rated PLFA cable
- FPLP Plenum-rated PLFA cable
Article 760 includes cable substitution allowances: a higher-performing cable (for example, plenum-rated) may substitute for a lower-location rating where the table permits. Riser cable is not automatically acceptable in a plenum just because both are “fire alarm cable”—match the location column in the substitution table.
NPLFA circuits may use Chapter 3 methods and other cables permitted in the NPLFA part of Article 760. If a stem asks for minimum cable marking in an air-handling plenum for a PLFA circuit, look for FPLP or an allowed substitute—not ordinary CL2 thermostat cable unless 760 expressly permits that substitution in your Code edition’s table.
Separation from power and other circuits
PLFA conductors have separation requirements analogous in spirit to Class 2/3 rules: keep them out of the same raceway, cable, or enclosure with electric light, power, and Class 1 conductors unless separated by a barrier or another method Article 760 permits. The safety idea is identical—limited-energy fire alarm conductors must not be exposed to power-circuit voltages through casual sharing.
Practical exam applications:
Do not pull PLFA cable loosely in the same EMT with 120/208 V branch-circuit conductors unless a continuous barrier or Code exception applies.
In boxes, use partitions or separate boxes when required so power terminals and PLFA terminals are not mixed without permitted separation.
Metallic raceways and enclosures still need proper grounding/bonding continuity when they are part of the wiring method—fire alarm does not waive Article 250 where metal methods are used.
NPLFA separation/identification rules differ because NPLFA already uses power-like methods; open the NPLFA part rather than copying PLFA answers blindly.
Survivability, pathway, and abandoned cable themes
Where the Code (and the fire alarm system design) requires circuit integrity / survivability so that evacuation signals continue during a fire for a required time, special CI cable, routing, or protection methods apply. Prov items, when present, usually test recognition that ordinary cable may be insufficient where survivability is required—not a full high-rise design problem.
Abandoned fire alarm cable that is accessible is generally required to be removed (with tagging allowances when reserved for future use under the article’s rules). Leaving abandoned smoke-detector cable in plenums as junk is both a Code and inspection failure mode.
Support and securing of fire alarm cables follow Article 760 support sections—do not assume “low voltage can drape on ceiling grid wires” without checking the article and listing.
Worked scenarios
Scenario A — Plenum PLFA. A power-limited initiating-device circuit in a return-air plenum needs FPLP (or a substitute allowed by the 760 substitution table). FPLR alone is the riser story, not an automatic plenum answer.
Scenario B — Shared box with lighting. A 120 V lighting splice and PLFA conductors in one box need a barrier or another permitted separation method. “They’re both low current” is not a Code argument for PLFA.
Scenario C — NPLFA riser. An NPLFA circuit uses Chapter 3 wiring methods suitable for the voltage and building construction—not CL2 thermostat cable as a default.
Scenario D — Wrong article. A stem about telephone entrance protectors is Article 800 , not 760. A stem about HVAC Class 2 controls is 725 . Only true fire alarm system circuits belong in 760.
Timed Prov tips
Tab Article 760 contents, NPLFA vs PLFA parts, FPL/FPLR/FPLP substitution tables, and separation sections. First question on every alarm stem: power-limited or non–power-limited? Second: location (plenum/riser/general)? Third: separation from power required? That sequence wins the alarm half of Arkansas’s two LV items without burning clock time.