13.2 Motor Branch-Circuit Conductors

Arkansas Journeyman Electrician Exam Study Guide 2026

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Arkansas Exam Overview

1.1 Current Exam Facts 1.2 Arkansas Licensing Pathway & Board Process 1.3 Open-Book Rules & Allowed References 1.4 NEC 2023 Navigation & Lookup Strategy

2 Electrical Theory & Trade Calculations

2.1 Ohm's Law, Power, and Basic Circuits 2.2 Series, Parallel, and Combination Circuits 2.3 Voltage Drop Calculations 2.4 Box Fill Calculations (314.16)

3 Load Calculations (Article 220)

3.1 Standard Dwelling Unit Load Calculations 3.2 Optional Dwelling & Multifamily Demand 3.3 Commercial / Non-Dwelling Demand Factors 3.4 Ampacity Adjustment & Correction (310.15)

4 Grounding Electrode Systems

4.1 Grounding Electrode Types & Installation 4.2 Grounding Electrode Conductor Sizing (250.66) 4.3 Main Bonding Jumper & Service Bonding

5 Equipment Grounding & Bonding

5.1 Equipment Grounding Conductors (250.122) 5.2 Bonding Raceways, Enclosures & Equipment 5.3 Separately Derived Systems Grounding

6 Services & Service Equipment

6.1 Service Entrance Conductors & Clearances 6.2 Service Disconnecting Means 6.3 Service Equipment & Working Space 6.4 Grounding Connections at the Service

7 Feeders & Overcurrent Protection

7.1 Feeder Conductor Sizing 7.2 Overcurrent Device Selection (Art 240) 7.3 Feeder and Branch-Circuit Tap Rules 7.4 Continuous Loads & OCPD Sizing

8 Branch Circuits, GFCI & AFCI

8.1 Branch-Circuit Ratings & Required Circuits 8.2 Dwelling Receptacle Placement & Kitchen/Bath Circuits 8.3 GFCI Protection Requirements 8.4 AFCI Protection Requirements

9 Metal Raceways

9.1 EMT Installation & Supports 9.2 RMC and IMC 9.3 Flexible Metal & Liquidtight Flexible Metal Conduit

10 Nonmetallic Raceways & Enclosures

10.1 PVC and ENT 10.2 Conduit Fill (Chapter 9 Tables) 10.3 Boxes, Conduit Bodies & Fill 10.4 Cabinets, Cutout Boxes & Meter Enclosures

11 Conductor Ampacity & Selection

11.1 Ampacity Table 310.16 Application 11.2 Termination Temperature Limitations 11.3 Conductor Insulation Types & Uses 11.4 Parallel Conductors

12 Cable Assemblies & Terminations

12.1 NM, MC, and AC Cable Assemblies 12.2 Conductor Identification & Color Coding 12.3 Splices, Taps & Terminations

13 Motors (Article 430)

13.1 Motor Nameplate Data & FLC Tables 13.2 Motor Branch-Circuit Conductors 13.3 Motor Overload Protection 13.4 Motor Short-Circuit / Ground-Fault Protection

14 Motor Controls & Transformers

14.1 Motor Disconnects & Controllers 14.2 Motor Control Circuits 14.3 Transformers (Article 450) for Journeymen

15 Utilization & General-Use Equipment

15.1 Luminaires & Lighting (Art 410) 15.2 Receptacles & Switches (Arts 406/404) 15.3 Appliances & Fixed Electric Space-Heating 15.4 Panelboards (Art 408)

16 Special Occupancies

16.1 Hazardous (Classified) Locations Overview 16.2 Health Care, Assembly & Temporary Installations 16.3 Swimming Pools, Spas & Similar Installations

17 Special Equipment Highlights

17.1 Signs & Outline Lighting 17.2 Elevators & Electric Vehicle Power Transfer 17.3 Emergency & Standby Systems Basics

18 Low-Voltage, Alarms & Communications

18.1 Class 1, 2, and 3 Circuits (Art 725) 18.2 Fire Alarm Systems (Art 760) 18.3 Communications Circuits Overview (Art 800+)

19 Electrical Safety

19.1 Working Space & Dedicated Equipment Space (110.26) 19.2 Lockout/Tagout & Safe Work Practices 19.3 Arc-Flash Awareness for the Exam

20 Exam Strategy & Test Day

20.1 Mixed Calculation Lab 20.2 Timed Code Lookup Drills 20.3 Test-Day Checklist, Scoring & Retakes

13.2 Motor Branch-Circuit Conductors

Key Takeaways Explain This Topic AI

NEC 430.22(A) requires branch-circuit conductors supplying a single continuous-duty motor to have ampacity not less than 125% of the motor’s Table FLC

Select conductor size from Table 310.16 (or other applicable ampacity tables) after 110.14(C) termination limits and any 310.15 adjustment/correction — 125% of FLC is the motor-circuit minimum, not a free pass to the 90°C column

Several motors on one circuit / feeder follow 430.24: 125% of the highest-rated motor FLC plus the sum of the other motor FLCs (plus other loads as applicable)

Do not size motor branch conductors from nameplate FLA or from the overload heater rating

Motor circuit EGCs still follow 250.122 based on the branch-circuit SC/GF device rating — Article 430 does not replace the EGC table

Last updated: August 2026

Conductor Sizing After You Have the Right FLC

Section 13.1 locked the current source: Table FLC . This section applies Article 430 Part II conductor rules that produce the wire size Prov expects on Motors and Controls items.

On Arkansas’s open-book form, the arithmetic is simple — FLC × 1.25 — but candidates lose points by (1) using nameplate, (2) forgetting 125%, or (3) picking a Table 310.16 size from the wrong temperature column.

Tab 430.22 , 430.24 , Table 430.250 , Table 310.16 , and 110.14(C) .

Single Continuous-Duty Motor — 430.22(A)

430.22(A) general rule: conductors that supply a single motor used in a continuous-duty application shall have an ampacity of not less than 125% of the motor’s full-load current as determined by 430.6(A) — meaning Table FLC for ordinary motors.

Worked example A — 10 hp, 460 V, 3φ

Table 430.250 FLC for 10 hp @ 460 V ≈ 14 A (verify).

Minimum conductor ampacity = 14 × 1.25 = 17.5 A .

From Table 310.16, 12 AWG copper in the 75°C column is typically 25 A — adequate for 17.5 A after termination rules are respected.

Do not stop at “14 A needs 14 AWG.” The motor rule is 125%, so 17.5 A is the floor before ampacity table selection.

Worked example B — 25 hp, 230 V, 3φ

Table 430.250 FLC for 25 hp @ 230 V ≈ 68 A (verify).

Minimum ampacity = 68 × 1.25 = 85 A .

Select copper (or aluminum if the stem says so) with allowable ampacity ≥ 85 A at the permitted termination temperature — often 4 AWG Cu or 3 AWG Cu depending on column and conditions (open Table 310.16; do not memorize from a blog).

Worked example C — single-phase shop motor

A 5 hp, 230 V, single-phase motor uses Table 430.248 FLC (commonly 28 A — verify), then 28 × 1.25 = 35 A minimum ampacity. Mixing in the three-phase 15.2 A value is a classic wrong path.

What “Continuous Duty” Means Here

Most general-purpose motors on Prov stems are treated as continuous duty unless the question specifies intermittent, periodic, or varying duty and points you to other rows in 430.22 / duty-cycle tables. If the stem is silent, apply 430.22(A) 125%.

Other duty types can require different percentages of FLC for conductors — open the specific subsection only when the stem names the duty cycle. Do not invent a reduced percentage for a silent continuous-duty motor just because the machine “only runs eight hours.”

Multi-Motor and Combination Loads — 430.24

430.24 covers conductors supplying several motors, or motors plus other loads. The core pattern for several motors:

Ampacity ≥ 125% of the highest-rated motor FLC + sum of the FLC of all other motors + other load currents as required.

Worked example D — three motors on one feeder/circuit conductor set

Motors (all 460 V, 3φ; FLCs from Table 430.250 — verify):

  • Motor FLC
  • 10 hp 14 A
  • 5 hp 7.6 A
  • 3 hp 4.8 A

Highest-rated motor FLC = 14 A.

Minimum conductor ampacity = (14 × 1.25) + 7.6 + 4.8 = 17.5 + 12.4 = 29.9 A .

Then select conductors ≥ 29.9 A from Table 310.16 under the correct temperature column.

Trap: Applying 125% to every motor (14×1.25 + 7.6×1.25 + 4.8×1.25) oversizes relative to 430.24 and will not match the keyed answer. Only the largest motor gets the 125% factor in this combination rule.

Termination Temperature Still Applies

Motor circuits do not escape 110.14(C) . If the breaker and starter lugs are 75°C-rated, you generally select ampacity from the 75°C column of Table 310.16 even when the insulation is THHN 90°C. You may still use 90°C ampacity as a starting point for adjustment/correction where the Code allows, but the equipment termination limit controls final sizing to the terminations.

Also apply 310.15 ambient correction and more-than-three current-carrying-conductor adjustment when the stem gives those facts. Compute:

Motor minimum from 430.22 / 430.24.

Adjusted/corrected ampacity of the chosen size.

Confirm adjusted ampacity still ≥ the motor minimum.

Motor Circuit Equipment Grounding Conductors

The branch-circuit EGC is sized from Table 250.122 based on the rating of the branch-circuit short-circuit and ground-fault protective device , not from 125% of FLC and not from 250.66. Article 430 tells you how to pick the SC/GF device (§13.4); Article 250 tells you the EGC once that device rating is known.

If a stem asks for the EGC of a motor branch circuit protected by a 70 A breaker, open 250.122 for 70 A — do not open Table 430.250 again looking for a grounding column that is not there.

Conductors on the Load Side of a Drive or Soft Starter

When an adjustable-speed drive or similar equipment is involved, manufacturer markings and Article 430 drive-related sections can change which current is used for load-side conductors. On Prov JW items, if the stem is a plain across-the-line motor starter, stay with 430.22 and Table FLC. If the stem explicitly names a VFD and input/output currents, read the applicable drive conductor rules rather than blindly multiplying motor FLC.

Exam Workflow — Branch Conductor Stems

Identify single motor vs several motors / other loads.

Pull Table FLC (correct table and voltage).

Apply 430.22(A) (×1.25) or 430.24 (1.25× largest + others).

Select from Table 310.16 with 110.14(C) .

Adjust for ambient/bundling if given.

Only then move to overload (§13.3) or SC/GF (§13.4) — those are different percentages and sometimes different currents.

Timed Open-Book Tips for §13.2

Scratch-paper line: FLC = ____; ×1.25 = ____ A min .

Multi-motor: star the largest FLC before multiplying.

Wire size ≠ breaker size; finish conductors before Table 430.52.

Nameplate FLA on the page is usually a distractor for this section.

If ampacity after adjustment falls below 17.5 A (or whatever minimum you calculated), upsize — do not ignore 310.15 facts the stem handed you.