13.1 Motor Nameplate Data & FLC Tables

Arkansas Journeyman Electrician Exam Study Guide 2026

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Arkansas Exam Overview

1.1 Current Exam Facts 1.2 Arkansas Licensing Pathway & Board Process 1.3 Open-Book Rules & Allowed References 1.4 NEC 2023 Navigation & Lookup Strategy

2 Electrical Theory & Trade Calculations

2.1 Ohm's Law, Power, and Basic Circuits 2.2 Series, Parallel, and Combination Circuits 2.3 Voltage Drop Calculations 2.4 Box Fill Calculations (314.16)

3 Load Calculations (Article 220)

3.1 Standard Dwelling Unit Load Calculations 3.2 Optional Dwelling & Multifamily Demand 3.3 Commercial / Non-Dwelling Demand Factors 3.4 Ampacity Adjustment & Correction (310.15)

4 Grounding Electrode Systems

4.1 Grounding Electrode Types & Installation 4.2 Grounding Electrode Conductor Sizing (250.66) 4.3 Main Bonding Jumper & Service Bonding

5 Equipment Grounding & Bonding

5.1 Equipment Grounding Conductors (250.122) 5.2 Bonding Raceways, Enclosures & Equipment 5.3 Separately Derived Systems Grounding

6 Services & Service Equipment

6.1 Service Entrance Conductors & Clearances 6.2 Service Disconnecting Means 6.3 Service Equipment & Working Space 6.4 Grounding Connections at the Service

7 Feeders & Overcurrent Protection

7.1 Feeder Conductor Sizing 7.2 Overcurrent Device Selection (Art 240) 7.3 Feeder and Branch-Circuit Tap Rules 7.4 Continuous Loads & OCPD Sizing

8 Branch Circuits, GFCI & AFCI

8.1 Branch-Circuit Ratings & Required Circuits 8.2 Dwelling Receptacle Placement & Kitchen/Bath Circuits 8.3 GFCI Protection Requirements 8.4 AFCI Protection Requirements

9 Metal Raceways

9.1 EMT Installation & Supports 9.2 RMC and IMC 9.3 Flexible Metal & Liquidtight Flexible Metal Conduit

10 Nonmetallic Raceways & Enclosures

10.1 PVC and ENT 10.2 Conduit Fill (Chapter 9 Tables) 10.3 Boxes, Conduit Bodies & Fill 10.4 Cabinets, Cutout Boxes & Meter Enclosures

11 Conductor Ampacity & Selection

11.1 Ampacity Table 310.16 Application 11.2 Termination Temperature Limitations 11.3 Conductor Insulation Types & Uses 11.4 Parallel Conductors

12 Cable Assemblies & Terminations

12.1 NM, MC, and AC Cable Assemblies 12.2 Conductor Identification & Color Coding 12.3 Splices, Taps & Terminations

13 Motors (Article 430)

13.1 Motor Nameplate Data & FLC Tables 13.2 Motor Branch-Circuit Conductors 13.3 Motor Overload Protection 13.4 Motor Short-Circuit / Ground-Fault Protection

14 Motor Controls & Transformers

14.1 Motor Disconnects & Controllers 14.2 Motor Control Circuits 14.3 Transformers (Article 450) for Journeymen

15 Utilization & General-Use Equipment

15.1 Luminaires & Lighting (Art 410) 15.2 Receptacles & Switches (Arts 406/404) 15.3 Appliances & Fixed Electric Space-Heating 15.4 Panelboards (Art 408)

16 Special Occupancies

16.1 Hazardous (Classified) Locations Overview 16.2 Health Care, Assembly & Temporary Installations 16.3 Swimming Pools, Spas & Similar Installations

17 Special Equipment Highlights

17.1 Signs & Outline Lighting 17.2 Elevators & Electric Vehicle Power Transfer 17.3 Emergency & Standby Systems Basics

18 Low-Voltage, Alarms & Communications

18.1 Class 1, 2, and 3 Circuits (Art 725) 18.2 Fire Alarm Systems (Art 760) 18.3 Communications Circuits Overview (Art 800+)

19 Electrical Safety

19.1 Working Space & Dedicated Equipment Space (110.26) 19.2 Lockout/Tagout & Safe Work Practices 19.3 Arc-Flash Awareness for the Exam

20 Exam Strategy & Test Day

20.1 Mixed Calculation Lab 20.2 Timed Code Lookup Drills 20.3 Test-Day Checklist, Scoring & Retakes

13.1 Motor Nameplate Data & FLC Tables

Key Takeaways Explain This Topic AI

NEC 430.6(A)(1) requires Table FLC from Tables 430.247–430.250 for conductor ampacity (430.22), branch-circuit short-circuit/ground-fault protection (430.52), and disconnect ratings (430.110) — not the motor nameplate FLA

NEC 430.6(A)(2) requires the motor nameplate full-load current for separate overload device sizing under 430.32 — opposite current from conductor/OCPD work

Table 430.250 covers three-phase AC motors; Table 430.248 covers single-phase AC; Table 430.247 covers DC — match voltage and horsepower columns exactly

Nameplate data you must still read: horsepower, voltage, FLA, service factor, temperature rise, Code letter, and design letter — SF and temp rise drive overload percentages in §13.3

Prov Motors and Controls is 7 items on the Arkansas JW exam (NEC 2023, 60Q/3hr/70%) — wrong-current mistakes cost more time than wrong table lookups

Last updated: August 2026

Why FLC vs Nameplate Is the Motor Chapter Gate

The Arkansas Journeyman Electrician exam (Prov / ADLL, NEC 2023 , 60 questions, 3 hours, 70% pass) weights Motors and Controls at 7 items . Nearly every motor stem starts with the same fork: which current do I use?

Table full-load current (FLC) from Article 430 tables → conductors, short-circuit/ground-fault OCPDs, and disconnect ampere ratings

Nameplate full-load amperes (FLA) → separate overload protection

If you reverse those currents, you can “do the math” perfectly and still miss the item. Tab 430.6 , Tables 430.248 / 430.250 , 430.22 , 430.32 , and Table 430.52 as one cluster before exam day. Controllers, control circuits, and disconnect location details continue in Chapter 14.

  • The Master Rule — 430.6(A)
  • 430.6(A)(1) — Table values (not nameplate)

Except as required for overload protection, the motor current used for ampacity, short-circuit/ground-fault protection, and disconnect sizing is taken from the tables , not from the nameplate. Applicable tables:

  • Motor type NEC table
  • Direct-current motors Table 430.247
  • Single-phase AC motors Table 430.248
  • Two-phase AC motors Table 430.249
  • Three-phase AC motors Table 430.250

On Prov, three-phase induction motors dominate. Open Table 430.250 , find the hp row, then the voltage column that matches the stem (208 V, 230 V, 460 V, 575 V, etc.). Use that FLC for every calculation that 430.6(A)(1) covers.

430.6(A)(2) — Nameplate for overload

Separate motor overload protection is based on the motor nameplate current rating . That is the only place in the everyday motor-sizing workflow where nameplate FLA replaces Table FLC.

Exam mantra: Table for wire and breaker; nameplate for overload heater/setting.

What the Nameplate Still Tells You

Even when you refuse nameplate FLA for conductor sizing, you still need the nameplate for:

  • Nameplate field Why it matters on Prov
  • Horsepower Selects the FLC table row
  • Voltage / phase Selects the FLC table column and which table
  • Full-load amperes (FLA) Overload sizing under 430.32
  • Service factor (SF) 125% vs 115% overload path
  • Temperature rise Alternate path into the 125% overload rule
  • Design letter / Code letter Starting characteristics / locked-rotor context
  • RPM / enclosure Identity checks; rarely the ampacity driver

Trap: A stem that prints both “nameplate 12.4 A” and “10 hp, 460 V, 3-phase” is bait. For 430.22 conductor ampacity, open Table 430.250 (10 hp @ 460 V → 14 A ), not 12.4 A. Save 12.4 A for the overload question in the next stem.

Reading Table 430.250 Cleanly

Workflow under time pressure:

Confirm three-phase AC (most commercial/industrial Arkansas stems).

Confirm synchronous speed / induction assumptions — the standard FLC tables are for the motors the section covers; unusual motors may have different rules (open 430.6 notes when the stem flags them).

Find hp .

Find voltage . Do not invent a midpoint between 230 V and 460 V columns.

Record FLC and write it on scratch paper before multiplying by 125% or Table 430.52 percentages.

Worked FLC lookups (verify in your NEC)

These values are the ones Prov-style items reuse constantly — always confirm in Table 430.250 :

  • Motor Table 430.250 FLC (typical)
  • 5 hp, 230 V, 3φ 15.2 A
  • 5 hp, 460 V, 3φ 7.6 A
  • 10 hp, 230 V, 3φ 28 A
  • 10 hp, 460 V, 3φ 14 A
  • 25 hp, 460 V, 3φ 34 A
  • 50 hp, 460 V, 3φ 65 A

Single-phase shop motors use Table 430.248 . Example pattern: a 3 hp, 230 V, 1φ motor uses the single-phase table FLC (commonly 17 A — verify), not the three-phase 9.6 A row.

Voltage trap: A motor labeled 208 V is not automatically the 230 V column. Use the column that matches the stem. If only 230 V and 460 V appear and the stem says 208 V, open the table notes/columns carefully — do not casually “borrow” 230 V without checking.

Why the Code Prefers Tables Over Nameplates

The FLC tables are intentional conservatism for replacement motors . A future motor of the same hp and voltage might draw more nameplate current than today’s efficient unit. Conductors and SC/GF devices sized from today’s low nameplate could be inadequate for the next motor. Overload devices, by contrast, must protect this motor’s windings — so they follow this nameplate.

That policy explanation is useful when two answers both look “numerically right.” Ask: am I protecting the circuit/conductors against faults , or the motor against running overload ?

Multi-Speed, Dual-Voltage, and Special Motors

Prov will occasionally spice a stem:

Dual-voltage motors: Size from the voltage at which the motor is connected. A dual-voltage 230/460 V motor connected for 460 V uses the 460 V FLC column.

Multi-speed motors: Follow the Part / section rules for the winding in use; do not average currents.

Design B vs other designs: Starting current and Code letter affect some protective-device exception paths later; they do not let you skip Table FLC for ordinary continuous-duty conductor sizing.

If the stem says “hermetic refrigerant motor-compressor,” you may be pushed toward Article 440 , not Article 430’s general motor tables. Identity first, article second.

Connecting FLC to the Rest of Article 430 Parts

Keep the Part map in your head so lookups stay short:

  • Task Primary Part / section Current source
  • Branch-circuit conductors Part II / 430.22 Table FLC
  • Overload protection Part III / 430.32 Nameplate FLA
  • Branch SC/GF protection Part IV / 430.52 Table FLC
  • Feeder conductors / OCPD 430.24 , 430.62 Table FLC
  • Controllers Part VII Separate rules
  • Disconnects Part IX / 430.110 Table FLC (115%)

This section owns the current-selection skill. Sections 13.2–13.4 apply the multipliers.

Timed Open-Book Tips for §13.1

First underline: nameplate vs table / FLC / FLA in the stem.

Open 430.6 only long enough to confirm which current — then jump to the table.

Write FLC on scratch paper before any 125% or 250% math.

Never use nameplate FLA for 430.22 or Table 430.52 unless a specific exception in the Code says so for that equipment type.

If both currents are printed, Prov is almost certainly testing whether you know 430.6(A)(1) vs (A)(2) .