Study guide

9.1 EMT Installation & Supports

Arkansas Journeyman Electrician Exam Study Guide 2026

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Arkansas Exam Overview

1.1 Current Exam Facts 1.2 Arkansas Licensing Pathway & Board Process 1.3 Open-Book Rules & Allowed References 1.4 NEC 2023 Navigation & Lookup Strategy

2 Electrical Theory & Trade Calculations

2.1 Ohm's Law, Power, and Basic Circuits 2.2 Series, Parallel, and Combination Circuits 2.3 Voltage Drop Calculations 2.4 Box Fill Calculations (314.16)

3 Load Calculations (Article 220)

3.1 Standard Dwelling Unit Load Calculations 3.2 Optional Dwelling & Multifamily Demand 3.3 Commercial / Non-Dwelling Demand Factors 3.4 Ampacity Adjustment & Correction (310.15)

4 Grounding Electrode Systems

4.1 Grounding Electrode Types & Installation 4.2 Grounding Electrode Conductor Sizing (250.66) 4.3 Main Bonding Jumper & Service Bonding

5 Equipment Grounding & Bonding

5.1 Equipment Grounding Conductors (250.122) 5.2 Bonding Raceways, Enclosures & Equipment 5.3 Separately Derived Systems Grounding

6 Services & Service Equipment

6.1 Service Entrance Conductors & Clearances 6.2 Service Disconnecting Means 6.3 Service Equipment & Working Space 6.4 Grounding Connections at the Service

7 Feeders & Overcurrent Protection

7.1 Feeder Conductor Sizing 7.2 Overcurrent Device Selection (Art 240) 7.3 Feeder and Branch-Circuit Tap Rules 7.4 Continuous Loads & OCPD Sizing

8 Branch Circuits, GFCI & AFCI

8.1 Branch-Circuit Ratings & Required Circuits 8.2 Dwelling Receptacle Placement & Kitchen/Bath Circuits 8.3 GFCI Protection Requirements 8.4 AFCI Protection Requirements

9 Metal Raceways

9.1 EMT Installation & Supports 9.2 RMC and IMC 9.3 Flexible Metal & Liquidtight Flexible Metal Conduit

10 Nonmetallic Raceways & Enclosures

10.1 PVC and ENT 10.2 Conduit Fill (Chapter 9 Tables) 10.3 Boxes, Conduit Bodies & Fill 10.4 Cabinets, Cutout Boxes & Meter Enclosures

11 Conductor Ampacity & Selection

11.1 Ampacity Table 310.16 Application 11.2 Termination Temperature Limitations 11.3 Conductor Insulation Types & Uses 11.4 Parallel Conductors

12 Cable Assemblies & Terminations

12.1 NM, MC, and AC Cable Assemblies 12.2 Conductor Identification & Color Coding 12.3 Splices, Taps & Terminations

13 Motors (Article 430)

13.1 Motor Nameplate Data & FLC Tables 13.2 Motor Branch-Circuit Conductors 13.3 Motor Overload Protection 13.4 Motor Short-Circuit / Ground-Fault Protection

14 Motor Controls & Transformers

14.1 Motor Disconnects & Controllers 14.2 Motor Control Circuits 14.3 Transformers (Article 450) for Journeymen

15 Utilization & General-Use Equipment

15.1 Luminaires & Lighting (Art 410) 15.2 Receptacles & Switches (Arts 406/404) 15.3 Appliances & Fixed Electric Space-Heating 15.4 Panelboards (Art 408)

16 Special Occupancies

16.1 Hazardous (Classified) Locations Overview 16.2 Health Care, Assembly & Temporary Installations 16.3 Swimming Pools, Spas & Similar Installations

17 Special Equipment Highlights

17.1 Signs & Outline Lighting 17.2 Elevators & Electric Vehicle Power Transfer 17.3 Emergency & Standby Systems Basics

18 Low-Voltage, Alarms & Communications

18.1 Class 1, 2, and 3 Circuits (Art 725) 18.2 Fire Alarm Systems (Art 760) 18.3 Communications Circuits Overview (Art 800+)

19 Electrical Safety

19.1 Working Space & Dedicated Equipment Space (110.26) 19.2 Lockout/Tagout & Safe Work Practices 19.3 Arc-Flash Awareness for the Exam

20 Exam Strategy & Test Day

20.1 Mixed Calculation Lab 20.2 Timed Code Lookup Drills 20.3 Test-Day Checklist, Scoring & Retakes

9.1 EMT Installation & Supports

Key Takeaways Explain This Topic AI

Article 358 governs Electrical Metallic Tubing (EMT): threadless thin-wall steel or aluminum raceway joined with listed couplings and connectors

Secure EMT within 3 ft of each box, cabinet, conduit body, or other termination and support at intervals not exceeding 10 ft (358.30)

Know 358.10 uses permitted versus 358.12 uses not permitted—severe physical damage and many hazardous locations are classic Prov traps

Total bend angle between pull points must not exceed 360° (358.26); keep the tubing round so conductors pull cleanly

Listed EMT with listed fittings may serve as an equipment grounding conductor under 250.118 when continuity is maintained

Last updated: August 2026

9.1 EMT Installation & Supports

Quick Answer: Electrical Metallic Tubing (EMT) is the thin-wall, threadless metal raceway in Article 358 . Fasten it within 3 ft of every box, cabinet, conduit body, or other termination, and support the run at intervals not exceeding 10 ft ( 358.30 ). Use listed couplings/connectors made up tight so the tubing can serve as an equipment grounding conductor when 250.118 permits. Do not use EMT where 358.12 forbids it (severe physical damage is the most common exam killer).

On the Arkansas Journeyman Electrician exam (Prov / ADLL, NEC 2023 , 60 questions, 3 hours, 70% pass), Raceways and Enclosures is 8 items . EMT is the everyday commercial raceway—cheap, light, and bendable—so Prov stems love support spacing, wet-location fittings, and “uses not permitted.” This section trains you to open Article 358 fast, read the right subsection, and avoid confusing EMT rules with RMC/IMC or flexible metal conduit.

What EMT is (and is not)

EMT is a circular metal raceway with a thinner wall than rigid metal conduit. It is not threaded in the field the way RMC is; joints use listed compression, set-screw, or other listed fittings . Trade sizes run from ½ through 6 under 358.20 (2023 raised the maximum to trade size 6). Aluminum EMT exists; corrosion protection and dissimilar-metal rules still apply when the Code and listing require them.

Exam vocabulary:

  • Term Meaning on Prov stems
  • EMT / thin-wall Article 358
  • RMC / rigid Article 344 (threaded heavy wall)
  • IMC Article 342 (threaded intermediate wall)
  • FMC / flex Article 348 (flexible metal)
  • LFMC / liquidtight Article 350

If the stem says “thin-wall,” “EMT,” or “setscrew coupling,” stay in 358 —do not grab Table 344.30(B)(2) unsupported-span numbers meant for threaded rigid.

Uses permitted — 358.10

358.10 permits EMT for both exposed and concealed work in many environments when the tubing and fittings are suitable for the location:

Dry, damp, and wet locations when corrosion protection and wet-location (raintight) fittings are used as required.

Concrete embedment and, where 300.6 and the listing allow, direct burial with supplementary corrosion protection and fittings listed for the burial method—still verify the listing; buried EMT is less common than RMC/IMC on jobsites.

Corrosive environments only when protected per 300.6 / manufacturer instructions.

As a wiring method in manufactured wiring systems where Article 604 recognizes EMT.

Practical translation: EMT is the default for interior commercial walls, ceilings, and exposed shop runs that are not subject to severe abuse. Wet locations are allowed with the right fittings —the Code does not ban EMT outdoors outright; it bans the wrong connector outdoors.

Uses not permitted — 358.12 (memorize the traps)

358.12 is where Prov earns easy points. EMT shall not be used:

Where subject to severe physical damage (loading docks, unprotected warehouse traffic lanes, areas where forklifts or carts can crush thin wall).

In certain hazardous (classified) locations , except where Chapter 5 expressly permits the method.

In cinder fill or cinder concrete subject to permanent moisture unless protected by corrosion-resistant material or other Code-compliant protection.

Where the Code for another article overrides Article 358 for a special occupancy or equipment.

Exam habit: If the stem paints a picture of physical abuse or Class I Division 1 process area, ask whether EMT is even a permitted method before you worry about strap spacing. Wrong raceway choice beats every support calculation.

Securing and supporting — 358.30

This is the highest-yield EMT lookup on an open-book exam.

The two numbers everyone must know

Within 3 ft of each outlet box, junction box, device box, cabinet, conduit body, or other conduit termination — securely fastened .

Supported at intervals not exceeding 10 ft along the run.

Horizontal runs through framing members with openings not more than 10 ft apart may count as supported, but you still need fastening within 3 ft of terminations. Where structural members make the 3 ft fastening impracticable, check the Exception language in 358.30(A) (some editions allow up to 5 ft to the first fastening when members are spaced that way)—always read the exact Exception in your 2023 book rather than guessing.

Unsupported raceways between terminations

358.30 also addresses unbroken lengths installed between boxes where intermediate support is not practicable (existing walls, finished construction). Those exceptions are narrow: do not invent a general “EMT never needs straps” rule. On Prov, if the stem gives a clean unfinished bay with clear joists, expect the 3 ft / 10 ft answer.

Worked support examples

Example A: A straight EMT run from a panel to a junction box 28 ft away in an open ceiling. Fasten within 3 ft of the panel and within 3 ft of the box; place intermediate supports so no span exceeds 10 ft (typically three intermediate straps on a 28 ft run depending on exact layout).

Example B: EMT stubs out of a box, makes a short offset, and enters another box 2 ft away. The termination fastenings within 3 ft of each box usually cover the short run; still verify no free length violates support intent and that fittings are wrench-/screwdriver-tight.

Example C: Rooftop EMT on strut. Same 3 ft / 10 ft rules apply unless a listed support system and Article 300 / rooftop rules impose tighter practice; temperature expansion fittings may be needed for long outdoor runs.

Fittings, continuity, and grounding

Couplings and connectors must be listed for EMT. In wet locations use fittings identified as raintight or otherwise suitable. Make up set-screw and compression fittings so metal-to-metal continuity is reliable—paint, loose screws, and cut tubing burrs break the fault path.

358.60 / 250.118: EMT is recognized as an equipment grounding conductor when installed with listed fittings that maintain continuity. Many commercial jobs still pull a wire-type EGC; if the stem asks whether EMT may serve as the EGC, the answer is yes when Code conditions are met. If the stem asks for the minimum wire-type EGC size , open Table 250.122 —do not answer “EMT” when they want an AWG.

Cut ends must be reamed or otherwise finished so conductor insulation is not damaged ( 358.28 family of construction rules). Bushings may be required where conductors 4 AWG and larger leave the raceway into an enclosure, per Article 300 / box rules.

Bends and the 360° rule

358.24 requires bends so the internal diameter is not effectively reduced—no kinks, no crushed tubing. 358.26 limits the total of all bends between pull points (boxes, conduit bodies, cabinets) to 360 degrees . Four neat 90° bends fill the budget; a fifth 90° means you need another pull point. On timed exams, “how many 90s between boxes?” is really a 358.26 question.

Common Prov traps

  • Trap Correct move
  • Supporting EMT every 4½ ft like FMC EMT max interval is 10 ft ( 358.30 )
  • Fastening only within 12 in of the box EMT termination fastening is 3 ft , not 12 in
  • Using EMT in a forklift aisle unprotected Check 358.12 severe physical damage
  • Dry-location setscrew outdoors in rain Wet location needs suitable fittings
  • Confusing EMT with RMC unsupported-span tables Those tables belong to 344 , not 358
  • Timed open-book tips

Tab 358.10 , 358.12 , 358.26 , and 358.30 . On every EMT stem, ask in order: (1) Is the use permitted? (2) Are fittings suitable for wet/corrosive conditions? (3) Is fastening within 3 ft and support ≤ 10 ft? (4) Is bend total ≤ 360°? That four-step filter clears most of Prov’s metal-raceway EMT items under the eight Raceways and Enclosures questions.