9.2 RMC and IMC
Arkansas Journeyman Electrician Exam Study Guide 2026
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Arkansas Exam Overview
1.1 Current Exam Facts 1.2 Arkansas Licensing Pathway & Board Process 1.3 Open-Book Rules & Allowed References 1.4 NEC 2023 Navigation & Lookup Strategy
2 Electrical Theory & Trade Calculations
2.1 Ohm's Law, Power, and Basic Circuits 2.2 Series, Parallel, and Combination Circuits 2.3 Voltage Drop Calculations 2.4 Box Fill Calculations (314.16)
3 Load Calculations (Article 220)
3.1 Standard Dwelling Unit Load Calculations 3.2 Optional Dwelling & Multifamily Demand 3.3 Commercial / Non-Dwelling Demand Factors 3.4 Ampacity Adjustment & Correction (310.15)
4 Grounding Electrode Systems
4.1 Grounding Electrode Types & Installation 4.2 Grounding Electrode Conductor Sizing (250.66) 4.3 Main Bonding Jumper & Service Bonding
5 Equipment Grounding & Bonding
5.1 Equipment Grounding Conductors (250.122) 5.2 Bonding Raceways, Enclosures & Equipment 5.3 Separately Derived Systems Grounding
6 Services & Service Equipment
6.1 Service Entrance Conductors & Clearances 6.2 Service Disconnecting Means 6.3 Service Equipment & Working Space 6.4 Grounding Connections at the Service
7 Feeders & Overcurrent Protection
7.1 Feeder Conductor Sizing 7.2 Overcurrent Device Selection (Art 240) 7.3 Feeder and Branch-Circuit Tap Rules 7.4 Continuous Loads & OCPD Sizing
8 Branch Circuits, GFCI & AFCI
8.1 Branch-Circuit Ratings & Required Circuits 8.2 Dwelling Receptacle Placement & Kitchen/Bath Circuits 8.3 GFCI Protection Requirements 8.4 AFCI Protection Requirements
9 Metal Raceways
9.1 EMT Installation & Supports 9.2 RMC and IMC 9.3 Flexible Metal & Liquidtight Flexible Metal Conduit
10 Nonmetallic Raceways & Enclosures
10.1 PVC and ENT 10.2 Conduit Fill (Chapter 9 Tables) 10.3 Boxes, Conduit Bodies & Fill 10.4 Cabinets, Cutout Boxes & Meter Enclosures
11 Conductor Ampacity & Selection
11.1 Ampacity Table 310.16 Application 11.2 Termination Temperature Limitations 11.3 Conductor Insulation Types & Uses 11.4 Parallel Conductors
12 Cable Assemblies & Terminations
12.1 NM, MC, and AC Cable Assemblies 12.2 Conductor Identification & Color Coding 12.3 Splices, Taps & Terminations
13 Motors (Article 430)
13.1 Motor Nameplate Data & FLC Tables 13.2 Motor Branch-Circuit Conductors 13.3 Motor Overload Protection 13.4 Motor Short-Circuit / Ground-Fault Protection
14 Motor Controls & Transformers
14.1 Motor Disconnects & Controllers 14.2 Motor Control Circuits 14.3 Transformers (Article 450) for Journeymen
15 Utilization & General-Use Equipment
15.1 Luminaires & Lighting (Art 410) 15.2 Receptacles & Switches (Arts 406/404) 15.3 Appliances & Fixed Electric Space-Heating 15.4 Panelboards (Art 408)
16 Special Occupancies
16.1 Hazardous (Classified) Locations Overview 16.2 Health Care, Assembly & Temporary Installations 16.3 Swimming Pools, Spas & Similar Installations
17 Special Equipment Highlights
17.1 Signs & Outline Lighting 17.2 Elevators & Electric Vehicle Power Transfer 17.3 Emergency & Standby Systems Basics
18 Low-Voltage, Alarms & Communications
18.1 Class 1, 2, and 3 Circuits (Art 725) 18.2 Fire Alarm Systems (Art 760) 18.3 Communications Circuits Overview (Art 800+)
19 Electrical Safety
19.1 Working Space & Dedicated Equipment Space (110.26) 19.2 Lockout/Tagout & Safe Work Practices 19.3 Arc-Flash Awareness for the Exam
20 Exam Strategy & Test Day
20.1 Mixed Calculation Lab 20.2 Timed Code Lookup Drills 20.3 Test-Day Checklist, Scoring & Retakes
9.2 RMC and IMC
Key Takeaways Explain This Topic AI
Article 344 covers Rigid Metal Conduit (RMC); Article 342 covers Intermediate Metal Conduit (IMC)—both are threaded heavy-duty metal raceways
Secure RMC/IMC within 3 ft of terminations (5 ft where structural spacing makes 3 ft impracticable per the article text) and support at intervals not exceeding 10 ft
Threaded couplings and listed fittings maintain mechanical strength and EGC continuity; RMC and IMC are premier equipment grounding paths under 250.118
Uses permitted include wet locations, concrete, and many areas subject to physical damage where EMT would be rejected
Table 344.30(B)(2) allows greater support spacing on straight threaded RMC runs of larger trade sizes—open the table; do not memorize every row
Last updated: August 2026
9.2 RMC and IMC
Quick Answer: Rigid Metal Conduit (RMC) is Article 344 ; Intermediate Metal Conduit (IMC) is Article 342 . Both are threaded steel (or other permitted metals) raceways built for strength. Fasten within 3 ft of boxes/cabinets (with article-specific relief to 5 ft when structural members make 3 ft impracticable), and support at intervals not exceeding 10 ft . Use them where physical protection, wet locations, or classified-location Chapter 5 wiring methods demand more than EMT can give.
Arkansas Prov’s Raceways and Enclosures items often contrast thin-wall EMT with rigid/intermediate conduit. If the stem mentions exposed warehouse columns, service masts, corrosive industrial areas, or Class I threaded conduit systems, you are usually in 342/344 , not 358 .
RMC vs IMC — what the exam expects
- Feature RMC (Art. 344) IMC (Art. 342)
- Wall / weight Heaviest traditional rigid Lighter than RMC, still threaded
- Joints Threaded couplings / listed fittings Threaded couplings / listed fittings
- Typical use Services, masts, severe exposure, industrial Same family of heavy-duty uses at less weight
- Max trade size Through trade size 6 Through trade size 6 (2023)
- As EGC Yes when continuous ( 344.60 / 250.118 ) Yes when continuous ( 342.60 / 250.118 )
IMC is not “flexible” and not EMT. Treat IMC like RMC for most journeyman lookups: threaded, robust, and Code-recognized as a wiring method and grounding path.
Uses permitted — where rigid wins
344.10 and 342.10 permit RMC/IMC in a wide range of conditions:
Exposed and concealed work.
Dry, damp, and wet locations.
Concrete embedment and direct burial (with corrosion protection as required by 300.6 and the listing).
Locations subject to severe physical damage —this is the strategic contrast with EMT’s 358.12 ban.
Many hazardous-location Chapter 5 methods that specify threaded rigid or intermediate metal conduit.
Service masts and outdoor risers commonly use RMC (sometimes IMC where accepted) because of mechanical strength and weather exposure. When a Prov stem asks for the raceway on a building service mast, think RMC first unless the problem states another listed method.
Corrosive atmospheres still require suitable materials or protective coatings—stainless, PVC-coated RMC, or other listed systems—not bare steel left to rust through.
Uses not permitted / practical limits
RMC and IMC have fewer “never” lists than EMT, but they are still constrained by:
Material suitability (dissimilar metals, aluminum in concrete, corrosive chemicals).
Chapter 5 special occupancy rules that may demand explosionproof fittings, sealing, or other methods beyond ordinary threaded conduit.
Support and coupling rules—threaded joints must be made up wrench-tight for mechanical and grounding integrity.
Fill, bend, and pull-point rules shared with other raceways (total bends ≤ 360° between pull points under 344.26 / 342.26 ).
Do not assume “RMC can go anywhere.” Assume “RMC can go where physical protection is required and the environment matches the material.”
- Securing and supporting — 344.30 / 342.30
- Baseline rule (same numbers as EMT, different article)
Securely fasten within 3 ft of each outlet box, junction box, device box, cabinet, conduit body, or other termination.
Support at intervals not exceeding 10 ft .
The 5 ft fastening relief
Where structural members are spaced so that fastening within 3 ft is impracticable , 342.30 / 344.30 language commonly allows fastening within 5 ft of the termination. Read the exact subsection in your 2023 NEC—Prov may quote the condition. This is not a free pass to skip supports on an open bay with plenty of steel to strap to.
Straight-run support tables (RMC)
Table 344.30(B)(2) permits increased distances between supports for straight runs of RMC with threaded couplings, based on trade size. Larger conduit can span farther when the installation meets the table’s conditions. Exam strategy:
Confirm the run is straight and uses threaded couplings as the table requires.
Open Table 344.30(B)(2) for the trade size.
Still fasten near terminations per 344.30(A) .
Do not apply this table to EMT or to zig-zag flex runs.
Vertical risers
Both articles address vertical support. Under stated conditions (threaded couplings, fastened at top and bottom, no intermediate structural support available), supports may be farther apart—commonly discussed as up to 20 ft for qualified risers. Always verify the exact Exception text rather than treating 20 ft as universal.
Worked examples
Example A — Exposed column run: 1½ in RMC up a warehouse column, 40 ft. Fasten within 3 ft of the enclosure at the bottom and top; place intermediate supports ≤ 10 ft apart unless a straight-run table or riser Exception clearly applies.
Example B — IMC feeder in a wet process room: Use fittings and conduit suitable for the wet/corrosive location; support on the 3 ft / 10 ft pattern; maintain threaded continuity for the EGC path.
Example C — Trade size 4 RMC across an open plant bay: Check Table 344.30(B)(2) for a longer support interval on a straight threaded run; still hit termination fastening rules.
Fittings, threads, and the EGC path
Field threads on RMC/IMC must be cut clean and tapered per standard conduit threading practice so couplings engage fully. Running threads that defeat the coupling’s tapered seal are a workmanship failure and can impair bonding. Listed threadless fittings exist for specific applications; follow the listing—do not mix EMT setscrew fittings onto rigid pipe as a general practice.
342.60 and 344.60 recognize IMC and RMC as equipment grounding conductors. With wrench-tight threaded joints, these raceways are among the most reliable metallic EGC paths in the Code. Expansion fittings, flexible sections, or impaired joints may need bonding jumpers—tie back to Article 250 when continuity is broken.
Where conductors leave the conduit into an enclosure, bushings protect insulation. Locknuts and bonding locknuts must be tight; concentric knockouts on the supply side of service equipment may still need bonding bushings even when the conduit is rigid.
Bends, cutting, and reaming
Field bends must not reduce the internal diameter. Factory elbows are common on large trade sizes. Ream cut ends to remove burrs ( 344.28 / 342.28 ). The 360° total bend limit between pull points applies just as it does for EMT—add a conduit body or box when the run would otherwise exceed the budget.
Choosing RMC/IMC vs EMT on exam stems
- Stem cue Likely method
- Severe physical damage / vehicle traffic RMC or IMC
- Ordinary dry commercial interior Often EMT
- Threaded Class I Division 1 raceway language RMC/IMC (per Chapter 5)
- Lightweight thin-wall / setscrew EMT
- Service mast subject to ice/wind Usually RMC
- Timed open-book tips
Tab 342.30 , 344.30 , Table 344.30(B)(2) , 344.10 , and 344.60 . First decide which article (342 vs 344 vs 358). Then apply termination fastening (3 ft / possible 5 ft), then interval (10 ft or table). Finally ask whether the raceway is also answering an EGC question under 250.118 . That sequence keeps rigid-conduit items fast on a 3-hour, 60-question Arkansas Prov exam.