Study guide
17.2 Elevators & Electric Vehicle Power Transfer
Arkansas Journeyman Electrician Exam Study Guide 2026
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Arkansas Exam Overview
1.1 Current Exam Facts 1.2 Arkansas Licensing Pathway & Board Process 1.3 Open-Book Rules & Allowed References 1.4 NEC 2023 Navigation & Lookup Strategy
2 Electrical Theory & Trade Calculations
2.1 Ohm's Law, Power, and Basic Circuits 2.2 Series, Parallel, and Combination Circuits 2.3 Voltage Drop Calculations 2.4 Box Fill Calculations (314.16)
3 Load Calculations (Article 220)
3.1 Standard Dwelling Unit Load Calculations 3.2 Optional Dwelling & Multifamily Demand 3.3 Commercial / Non-Dwelling Demand Factors 3.4 Ampacity Adjustment & Correction (310.15)
4 Grounding Electrode Systems
4.1 Grounding Electrode Types & Installation 4.2 Grounding Electrode Conductor Sizing (250.66) 4.3 Main Bonding Jumper & Service Bonding
5 Equipment Grounding & Bonding
5.1 Equipment Grounding Conductors (250.122) 5.2 Bonding Raceways, Enclosures & Equipment 5.3 Separately Derived Systems Grounding
6 Services & Service Equipment
6.1 Service Entrance Conductors & Clearances 6.2 Service Disconnecting Means 6.3 Service Equipment & Working Space 6.4 Grounding Connections at the Service
7 Feeders & Overcurrent Protection
7.1 Feeder Conductor Sizing 7.2 Overcurrent Device Selection (Art 240) 7.3 Feeder and Branch-Circuit Tap Rules 7.4 Continuous Loads & OCPD Sizing
8 Branch Circuits, GFCI & AFCI
8.1 Branch-Circuit Ratings & Required Circuits 8.2 Dwelling Receptacle Placement & Kitchen/Bath Circuits 8.3 GFCI Protection Requirements 8.4 AFCI Protection Requirements
9 Metal Raceways
9.1 EMT Installation & Supports 9.2 RMC and IMC 9.3 Flexible Metal & Liquidtight Flexible Metal Conduit
10 Nonmetallic Raceways & Enclosures
10.1 PVC and ENT 10.2 Conduit Fill (Chapter 9 Tables) 10.3 Boxes, Conduit Bodies & Fill 10.4 Cabinets, Cutout Boxes & Meter Enclosures
11 Conductor Ampacity & Selection
11.1 Ampacity Table 310.16 Application 11.2 Termination Temperature Limitations 11.3 Conductor Insulation Types & Uses 11.4 Parallel Conductors
12 Cable Assemblies & Terminations
12.1 NM, MC, and AC Cable Assemblies 12.2 Conductor Identification & Color Coding 12.3 Splices, Taps & Terminations
13 Motors (Article 430)
13.1 Motor Nameplate Data & FLC Tables 13.2 Motor Branch-Circuit Conductors 13.3 Motor Overload Protection 13.4 Motor Short-Circuit / Ground-Fault Protection
14 Motor Controls & Transformers
14.1 Motor Disconnects & Controllers 14.2 Motor Control Circuits 14.3 Transformers (Article 450) for Journeymen
15 Utilization & General-Use Equipment
15.1 Luminaires & Lighting (Art 410) 15.2 Receptacles & Switches (Arts 406/404) 15.3 Appliances & Fixed Electric Space-Heating 15.4 Panelboards (Art 408)
16 Special Occupancies
16.1 Hazardous (Classified) Locations Overview 16.2 Health Care, Assembly & Temporary Installations 16.3 Swimming Pools, Spas & Similar Installations
17 Special Equipment Highlights
17.1 Signs & Outline Lighting 17.2 Elevators & Electric Vehicle Power Transfer 17.3 Emergency & Standby Systems Basics
18 Low-Voltage, Alarms & Communications
18.1 Class 1, 2, and 3 Circuits (Art 725) 18.2 Fire Alarm Systems (Art 760) 18.3 Communications Circuits Overview (Art 800+)
19 Electrical Safety
19.1 Working Space & Dedicated Equipment Space (110.26) 19.2 Lockout/Tagout & Safe Work Practices 19.3 Arc-Flash Awareness for the Exam
20 Exam Strategy & Test Day
20.1 Mixed Calculation Lab 20.2 Timed Code Lookup Drills 20.3 Test-Day Checklist, Scoring & Retakes
17.2 Elevators & Electric Vehicle Power Transfer
Key Takeaways Explain This Topic AI
Article 620 covers elevators, escalators, moving walks, dumbwaiters, and platform lifts; Article 625 covers electric vehicle power transfer systems (EVSE) under NEC 2023.
NEC 620.51 requires a lockable disconnecting means within sight of the elevator controller, accessible to qualified persons, that opens all ungrounded conductors.
Elevator machine rooms, control rooms/spaces, and pits typically need dedicated lighting and GFCI-protected receptacles — do not feed car lighting from the same circuit as the hoist motor.
Article 625 treats EVSE as continuous loads for branch-circuit sizing (generally 125% of the maximum load) and requires personnel protection and suitable disconnecting means.
On Arkansas Prov stems, identify equipment first: elevator controller disconnect → 620; EV charger ampacity/GF protection → 625 — do not apply motor Article 430 alone when 620/625 govern.
Last updated: August 2026
Two Articles, One Special-Equipment Cluster
On the Arkansas Prov JW exam (NEC 2023 , 60Q / 3 hr / 70% ), elevators and electric vehicle power transfer both land in Special Occupancies and Equipment thinking, but they live in different articles:
Equipment Article Typical Prov ask
Elevators, escalators, moving walks, dumbwaiters, platform lifts 620 Disconnect within sight of controller; separate lighting/receptacle circuits; pit GFCI
EV charging / power transfer equipment (EVSE) 625 Continuous-load 125% sizing; disconnect; personnel protection
Tab 620.22–620.25 , 620.51 , 620.85 , and 625.40–625.42 (and nearby sizing/protection sections). Article 430 still matters for motor FLC background, but 620 modifies and organizes elevator wiring as a system.
- Article 620 — Elevators and Related Equipment
- Scope and Voltage
Article 620 covers the installation of electrical equipment and wiring used in connection with elevators, dumbwaiters, escalators, moving walks, platform lifts, and stairway chairlifts. Voltage limitations appear in 620.3 and related sections — know that different parts of the elevator system (power, lighting, control, traveling cable) have distinct wiring method and voltage contexts. For exam day, identity beats memorizing every millivolt: if the stem says “elevator machine room controller,” open 620 , not 430 alone.
Motor Controllers and Disconnects — 620.51
620.51 requires a disconnecting means for the elevator drive/controller power:
- Located where it is readily accessible to qualified persons
- Within sight of the controller (Article 100: visible and ≤ 50 ft )
- Capable of being locked in the open position
- Opens all ungrounded conductors
No other loads on the load side of that disconnect (elevator power disconnect is dedicated to that elevator equipment as the section describes)
Multiple elevators may each need their own disconnect. A single building main breaker that is not within sight of the controller — and not arranged as the required lockable elevator disconnect — fails the 620.51 test even if it can de-energize the feeder.
Exam trap: Using the motor disconnect rules from 430.102 without checking the elevator-specific within sight of the controller and lockable language in 620.51.
Separate Circuits — Car, Machine Room, and Pit
Article 620 requires separate branch circuits for several elevator-related loads. Typical Prov recognition points:
Car lights , receptacles, ventilation, and heating/air-conditioning on the car generally need their own circuit(s), not the hoist-motor feeder.
Machine room / control room / control space lighting and receptacles are supplied so that loss of the elevator power circuit does not plunge the room into darkness or remove the only receptacle — follow 620.22 / 620.23 style separation rules in the 2023 text.
Pit lighting and receptacles have their own requirements; receptacles in pits, machine rooms, and similar spaces generally require GFCI protection ( 620.85 and related).
Think life-safety and maintenance: a mechanic in the pit needs light and a GFCI receptacle even if the elevator main is locked out.
Traveling Cables and Wiring Methods
Traveling cables between the car and the hoistway raceway are a hallmark of Article 620. They must be listed for the purpose, supported, and limited in what circuits they may carry. Hoistway wiring methods are restricted; you do not freely run ordinary NM cable through the hoistway as if it were a dwelling basement. On open-book items, if the stem mentions traveling cable conductor count or permitted circuits, stay inside Article 620 Parts covering wiring.
Working Space and Guarding
Controllers and disconnects still need working space per 110.26 unless Article 620 provides a specific modification. Guarding of live parts and motor rooms as restricted spaces matters for AHJ practice; Prov stems usually stick to disconnect location, circuit separation, and GFCI.
- Article 625 — Electric Vehicle Power Transfer Systems
- Scope
Article 625 covers the electrical conductors and equipment connecting an electric vehicle to premises wiring for charging (and, where covered, power export / bidirectional systems). The utilization equipment is commonly called EVSE (Electric Vehicle Supply Equipment). Cord-and-plug EVSE and permanently connected EVSE both appear in stems.
Branch-Circuit Sizing — Continuous Load
EV charging is treated as a continuous load for branch-circuit and feeder calculations unless a specific exception applies. The usual Prov math path:
Read the EVSE maximum load / nameplate current (or the adjustable setting if the listing and 625 rules allow a supervised setting).
Size branch-circuit conductors and overcurrent protection at not less than 125% of that continuous current ( 625.40 / continuous-load rules as applied in Article 625).
Example pattern: An EVSE nameplate maximum of 32 A continuous → conductors and OCPD based on 40 A (32 × 1.25). Verify conductor ampacity after temperature and bundling adjustments from Article 310 / 210 , but the 125% continuous factor is the Article 625 gate.
Exam trap: Sizing a 32 A EVSE on a 30 A breaker “because the car never draws that much” — Code uses the EVSE rating and continuous-load multiplier, not informal diversity.
Disconnecting Means and Personnel Protection
Article 625 requires a disconnecting means for permanently connected EVSE, located and identified per the section (often within sight or lockable/remote as allowed). Personnel protection against shock — GFCI or a listed personnel protection system integral to the EVSE — is a core requirement for AC Level systems. Do not omit GFCI/personnel protection because “it’s outdoors and WR.” Outdoor listing and personnel protection are separate issues.
Location, Cable Management, and Ventilation
Outdoor EVSE needs wet-location suitability. Cable connectors and interactive cable management must not create trip hazards or damaged cords. Older Code editions emphasized ventilation for certain non-conductive charging methods; modern conductive Level 2 EVSE stems usually focus on ampacity, disconnect, and personnel protection rather than garage CFM calculations — read the stem for which hazard is being tested.
Interactive / bidirectional power transfer (vehicle-to-grid or vehicle-to-home) adds interconnection and islanding concerns that may cross into Articles 705 / 710 territory. If the stem is only “Level 2 wall charger for a dwelling garage,” stay in 625 .
How Prov Mixes 620, 625, and 430
- Question angle Open first
- Elevator controller disconnect location 620.51
- Elevator pit receptacle protection 620.85
- Separate car lighting circuit 620.22 area
- EVSE conductor/OCPD size 625 continuous 125%
- Motor FLC table for a non-elevator shop motor 430.6 / Tables
- Arkansas Prov Takeaway
For elevators: lockable disconnect within sight of the controller , separate lighting/receptacle circuits, and GFCI where 620 requires it. For EVSE: treat the load as continuous (125%) , provide the proper disconnect , and ensure personnel protection . Identity the equipment before you reach for Article 430 general motor rules.