2.4 Box Fill Calculations (314.16)

Arkansas Journeyman Electrician Exam Study Guide 2026

Track your progress as you read

Finished sections get a check mark.

1 Introduction & Arkansas Exam Overview

1.1 Current Exam Facts 1.2 Arkansas Licensing Pathway & Board Process 1.3 Open-Book Rules & Allowed References 1.4 NEC 2023 Navigation & Lookup Strategy

2 Electrical Theory & Trade Calculations

2.1 Ohm's Law, Power, and Basic Circuits 2.2 Series, Parallel, and Combination Circuits 2.3 Voltage Drop Calculations 2.4 Box Fill Calculations (314.16)

3 Load Calculations (Article 220)

3.1 Standard Dwelling Unit Load Calculations 3.2 Optional Dwelling & Multifamily Demand 3.3 Commercial / Non-Dwelling Demand Factors 3.4 Ampacity Adjustment & Correction (310.15)

4 Grounding Electrode Systems

4.1 Grounding Electrode Types & Installation 4.2 Grounding Electrode Conductor Sizing (250.66) 4.3 Main Bonding Jumper & Service Bonding

5 Equipment Grounding & Bonding

5.1 Equipment Grounding Conductors (250.122) 5.2 Bonding Raceways, Enclosures & Equipment 5.3 Separately Derived Systems Grounding

6 Services & Service Equipment

6.1 Service Entrance Conductors & Clearances 6.2 Service Disconnecting Means 6.3 Service Equipment & Working Space 6.4 Grounding Connections at the Service

7 Feeders & Overcurrent Protection

7.1 Feeder Conductor Sizing 7.2 Overcurrent Device Selection (Art 240) 7.3 Feeder and Branch-Circuit Tap Rules 7.4 Continuous Loads & OCPD Sizing

8 Branch Circuits, GFCI & AFCI

8.1 Branch-Circuit Ratings & Required Circuits 8.2 Dwelling Receptacle Placement & Kitchen/Bath Circuits 8.3 GFCI Protection Requirements 8.4 AFCI Protection Requirements

9 Metal Raceways

9.1 EMT Installation & Supports 9.2 RMC and IMC 9.3 Flexible Metal & Liquidtight Flexible Metal Conduit

10 Nonmetallic Raceways & Enclosures

10.1 PVC and ENT 10.2 Conduit Fill (Chapter 9 Tables) 10.3 Boxes, Conduit Bodies & Fill 10.4 Cabinets, Cutout Boxes & Meter Enclosures

11 Conductor Ampacity & Selection

11.1 Ampacity Table 310.16 Application 11.2 Termination Temperature Limitations 11.3 Conductor Insulation Types & Uses 11.4 Parallel Conductors

12 Cable Assemblies & Terminations

12.1 NM, MC, and AC Cable Assemblies 12.2 Conductor Identification & Color Coding 12.3 Splices, Taps & Terminations

13 Motors (Article 430)

13.1 Motor Nameplate Data & FLC Tables 13.2 Motor Branch-Circuit Conductors 13.3 Motor Overload Protection 13.4 Motor Short-Circuit / Ground-Fault Protection

14 Motor Controls & Transformers

14.1 Motor Disconnects & Controllers 14.2 Motor Control Circuits 14.3 Transformers (Article 450) for Journeymen

15 Utilization & General-Use Equipment

15.1 Luminaires & Lighting (Art 410) 15.2 Receptacles & Switches (Arts 406/404) 15.3 Appliances & Fixed Electric Space-Heating 15.4 Panelboards (Art 408)

16 Special Occupancies

16.1 Hazardous (Classified) Locations Overview 16.2 Health Care, Assembly & Temporary Installations 16.3 Swimming Pools, Spas & Similar Installations

17 Special Equipment Highlights

17.1 Signs & Outline Lighting 17.2 Elevators & Electric Vehicle Power Transfer 17.3 Emergency & Standby Systems Basics

18 Low-Voltage, Alarms & Communications

18.1 Class 1, 2, and 3 Circuits (Art 725) 18.2 Fire Alarm Systems (Art 760) 18.3 Communications Circuits Overview (Art 800+)

19 Electrical Safety

19.1 Working Space & Dedicated Equipment Space (110.26) 19.2 Lockout/Tagout & Safe Work Practices 19.3 Arc-Flash Awareness for the Exam

20 Exam Strategy & Test Day

20.1 Mixed Calculation Lab 20.2 Timed Code Lookup Drills 20.3 Test-Day Checklist, Scoring & Retakes

2.4 Box Fill Calculations (314.16)

Key Takeaways Explain This Topic AI

NEC 2023 Section 314.16 limits the number of conductors in boxes based on box volume (Table 314.16(A)) and volume allowances per conductor size (Table 314.16(B))

Each insulated conductor entering a box and terminating or splicing counts as one volume allowance of its size; unbroken pass-through conductors also count as one each

All equipment grounding conductors together count as a single volume allowance based on the largest EGC in the box (additional EGCs for isolated grounds have special counting rules)

Each yoke-mounted device (switch or receptacle) counts as two volume allowances based on the largest conductor connected to that device

One or more internal cable clamps count as a single volume allowance of the largest conductor present; external clamps or connectors do not consume box fill

Last updated: August 2026

Box fill is a classic General Knowledge / Code hybrid item on the Arkansas Journeyman Electrician exam. You open NEC 2023 to Article 314 , specifically 314.16 , and apply counting rules — not Ohm's law. Prov expects you to know what counts, what does not, and how device and clamp allowances work.

The Governing Rule — 314.16

Boxes must be large enough so that the total volume of conductors, devices, clamps, and fittings does not exceed the box's marked or tabulated volume. Two tables do the heavy lifting:

  • Table Purpose
  • 314.16(A) Metal box trade sizes and minimum volumes (in.³)
  • 314.16(B) Volume allowance (in.³) for each free conductor by AWG

Common 314.16(B) allowances (verify on exam):

  • Conductor size Free conductor volume
  • 18 AWG 1.50 in.³
  • 16 AWG 1.75 in.³
  • 14 AWG 2.00 in.³
  • 12 AWG 2.25 in.³
  • 10 AWG 2.50 in.³
  • 8 AWG 3.00 in.³
  • 6 AWG 5.00 in.³

What Counts as a Volume Allowance?

314.16(B)(1) — Conductor fill: Each conductor that originates outside the box and terminates or is spliced inside counts as one of its size. A conductor that passes through unbroken also counts as one. Fixture wires covered by exception and equipment grounding conductors are handled separately.

Does not count: Pigtails that stay entirely inside the box (they originate and terminate inside). Conductors that never leave the box do not add fill.

314.16(B)(2) — Clamp fill: One or more internal cable clamps count as a single volume allowance based on the largest conductor present in the box. Locknuts and bushings do not count. Clamps outside the box (external connectors) do not count.

314.16(B)(3) — Support fittings: Luminaire studs or hickeys can add allowances — read the stem; many device-box questions omit them.

314.16(B)(4) — Device or equipment fill: Each yoke or strap containing a device (duplex receptacle, switch, etc.) counts as two volume allowances based on the largest conductor connected to that device. A single switch = 2; two devices on separate yokes = 4 allowances.

314.16(B)(5) — Equipment grounding fill: All equipment grounding conductors count together as one volume allowance of the largest EGC in the box. An additional isolated/insulated EGC requirement can add one more allowance — watch for that wording.

Worked Example 1 — Device Box with NM Cable

A 4 in. square × 2⅛ in. deep metal box (Table 314.16(A) lists 30.3 in.³ for the 4 × 2⅛ square row; confirm the exact row on exam day) will contain:

  • Two 12/2 NM cables with grounds (supply and load) to one duplex receptacle
  • Internal cable clamps

Count for 12 AWG (2.25 in.³ each):

  • Item Allowances Volume
  • Circuit conductors (4): hot and neutral from each cable 4 × 1 4 × 2.25 = 9.00
  • All EGCs (2 grounds) 1 × 1 1 × 2.25 = 2.25
  • Internal clamps 1 × 1 1 × 2.25 = 2.25
  • Duplex receptacle (one yoke) 2 × 1 2 × 2.25 = 4.50
  • Total 18.00 in.³

18.00 < 30.3 → box is adequate . The four insulated circuit conductors each count; the two grounds collapse to one allowance; clamps collapse to one; the receptacle uses two.

Worked Example 2 — Too Many Conductors

Same 30.3 in.³ box, but now three 12/2 NM cables (six circuit conductors + three EGCs), internal clamps, and one receptacle:

  • Item Volume
  • 6 circuit conductors × 2.25 13.50
  • EGCs → 1 × 2.25 2.25
  • Clamps → 1 × 2.25 2.25
  • Device → 2 × 2.25 4.50
  • Total 22.50 in.³

Still under 30.3. Add a second device yoke (another switch) on the same box:

Extra device = +4.50 → 27.00 in.³ — still OK. A third device yoke (+4.50) would reach 31.50 in.³ and fail 314.16 for this box volume.

Worked Example 3 — Mixed Sizes

When conductor sizes differ, each insulated conductor uses the volume for its own size from Table 314.16(B). Device and clamp allowances use the largest conductor connected to the device or present in the box, respectively. EGC allowance uses the largest EGC.

Example: Box contains four 14 AWG circuit conductors (2.00 in.³ each), two 12 AWG circuit conductors (2.25 each), EGCs of 14 AWG, internal clamps, one receptacle fed by the 12 AWG conductors:

  • Item Calculation in.³
  • 14 AWG conductors 4 × 2.00 8.00
  • 12 AWG conductors 2 × 2.25 4.50
  • EGC (largest EGC 14 → 2.00) 1 × 2.00 2.00
  • Clamps (largest conductor in box = 12 → 2.25) 1 × 2.25 2.25
  • Device (largest connected = 12 → 2.25) 2 × 2.25 4.50
  • Total 21.25

Row-reading trap: Table 314.16(A) separates square , round/octagonal , and device boxes. A 4 × 2⅛ square box is 30.3 in.³ , but a 4 × 2⅛ × 2⅛ device (handy) box is only 14.5 in.³ and a 4 × 2⅛ round/octagonal box is 21.5 in.³ . The 18.00 in.³ fill above passes in the 30.3 in.³ square box and would fail in the 14.5 in.³ device box. Read the box shape in the stem before you read a volume.

Plastic Boxes and Marked Volume

Nonmetallic boxes are often marked with cubic inch capacity. Use the marked volume rather than guessing from dimensions. Metal boxes use Table 314.16(A) unless a larger volume is marked.

Domed Covers and Extensions

Domed covers or plaster rings with marked volume may add usable cubic inches — only if the question states a marked additional volume. Do not invent extra volume.

Arkansas Exam Lookup Habit

Open to 314.16 and Tables 314.16(A) and (B) .

List every cable/conductor entering the box on scratch paper.

Apply the five fill categories in order: conductors, clamps, support fittings, devices, EGCs.

Multiply allowances by the correct in.³ from Table 314.16(B).

Compare total to box volume.

Box fill rewards methodical counting. On a timed Prov exam, write the tally table — it prevents double-counting grounds or forgetting that a device costs two allowances.