Study guide
2.1 Ohm's Law, Power, and Basic Circuits
Arkansas Journeyman Electrician Exam Study Guide 2026
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Arkansas Exam Overview
1.1 Current Exam Facts 1.2 Arkansas Licensing Pathway & Board Process 1.3 Open-Book Rules & Allowed References 1.4 NEC 2023 Navigation & Lookup Strategy
2 Electrical Theory & Trade Calculations
2.1 Ohm's Law, Power, and Basic Circuits 2.2 Series, Parallel, and Combination Circuits 2.3 Voltage Drop Calculations 2.4 Box Fill Calculations (314.16)
3 Load Calculations (Article 220)
3.1 Standard Dwelling Unit Load Calculations 3.2 Optional Dwelling & Multifamily Demand 3.3 Commercial / Non-Dwelling Demand Factors 3.4 Ampacity Adjustment & Correction (310.15)
4 Grounding Electrode Systems
4.1 Grounding Electrode Types & Installation 4.2 Grounding Electrode Conductor Sizing (250.66) 4.3 Main Bonding Jumper & Service Bonding
5 Equipment Grounding & Bonding
5.1 Equipment Grounding Conductors (250.122) 5.2 Bonding Raceways, Enclosures & Equipment 5.3 Separately Derived Systems Grounding
6 Services & Service Equipment
6.1 Service Entrance Conductors & Clearances 6.2 Service Disconnecting Means 6.3 Service Equipment & Working Space 6.4 Grounding Connections at the Service
7 Feeders & Overcurrent Protection
7.1 Feeder Conductor Sizing 7.2 Overcurrent Device Selection (Art 240) 7.3 Feeder and Branch-Circuit Tap Rules 7.4 Continuous Loads & OCPD Sizing
8 Branch Circuits, GFCI & AFCI
8.1 Branch-Circuit Ratings & Required Circuits 8.2 Dwelling Receptacle Placement & Kitchen/Bath Circuits 8.3 GFCI Protection Requirements 8.4 AFCI Protection Requirements
9 Metal Raceways
9.1 EMT Installation & Supports 9.2 RMC and IMC 9.3 Flexible Metal & Liquidtight Flexible Metal Conduit
10 Nonmetallic Raceways & Enclosures
10.1 PVC and ENT 10.2 Conduit Fill (Chapter 9 Tables) 10.3 Boxes, Conduit Bodies & Fill 10.4 Cabinets, Cutout Boxes & Meter Enclosures
11 Conductor Ampacity & Selection
11.1 Ampacity Table 310.16 Application 11.2 Termination Temperature Limitations 11.3 Conductor Insulation Types & Uses 11.4 Parallel Conductors
12 Cable Assemblies & Terminations
12.1 NM, MC, and AC Cable Assemblies 12.2 Conductor Identification & Color Coding 12.3 Splices, Taps & Terminations
13 Motors (Article 430)
13.1 Motor Nameplate Data & FLC Tables 13.2 Motor Branch-Circuit Conductors 13.3 Motor Overload Protection 13.4 Motor Short-Circuit / Ground-Fault Protection
14 Motor Controls & Transformers
14.1 Motor Disconnects & Controllers 14.2 Motor Control Circuits 14.3 Transformers (Article 450) for Journeymen
15 Utilization & General-Use Equipment
15.1 Luminaires & Lighting (Art 410) 15.2 Receptacles & Switches (Arts 406/404) 15.3 Appliances & Fixed Electric Space-Heating 15.4 Panelboards (Art 408)
16 Special Occupancies
16.1 Hazardous (Classified) Locations Overview 16.2 Health Care, Assembly & Temporary Installations 16.3 Swimming Pools, Spas & Similar Installations
17 Special Equipment Highlights
17.1 Signs & Outline Lighting 17.2 Elevators & Electric Vehicle Power Transfer 17.3 Emergency & Standby Systems Basics
18 Low-Voltage, Alarms & Communications
18.1 Class 1, 2, and 3 Circuits (Art 725) 18.2 Fire Alarm Systems (Art 760) 18.3 Communications Circuits Overview (Art 800+)
19 Electrical Safety
19.1 Working Space & Dedicated Equipment Space (110.26) 19.2 Lockout/Tagout & Safe Work Practices 19.3 Arc-Flash Awareness for the Exam
20 Exam Strategy & Test Day
20.1 Mixed Calculation Lab 20.2 Timed Code Lookup Drills 20.3 Test-Day Checklist, Scoring & Retakes
2.1 Ohm's Law, Power, and Basic Circuits
Key Takeaways Explain This Topic AI
Ohm's law relates voltage (E or V), current (I), and resistance (R): E = I × R, I = E / R, and R = E / I
Power formulas every Arkansas JW candidate must know: P = I × E, P = I²R, and P = E² / R (watts)
On a 120 V or 240 V branch circuit, solving for missing current or load watts is a common General Knowledge item on the Prov 60-question exam
Convert kW to amperes with I = (kW × 1000) / E for DC or single-phase; use I = (kW × 1000) / (E × 1.732 × PF) for three-phase when power factor is given
Keep units consistent: ohms, volts, amperes, and watts — convert milliamps and kilowatts before applying formulas
Last updated: August 2026
The Arkansas Journeyman Electrician exam administered by Prov includes nine General Knowledge of the Electrical Trade and Calculations items. Several of those questions test pure electrical theory — Ohm's law, power relationships, and basic circuit math — rather than Code lookup. You still bring NEC 2023 into the room, but these problems are solved with formulas and careful unit handling, not Article hunting.
Ohm's Law Triangle
Ohm's law states that voltage across a resistive load equals current through the load times resistance:
E = I × R
Rearranged forms you must recall instantly:
- Solve for Formula When you use it
- Voltage (E or V) E = I × R Known amps and ohms; find expected voltage drop across a resistor or heater element
- Current (I) I = E / R Known supply voltage and load resistance; find amperes drawn
- Resistance (R) R = E / I Known voltage and measured or given current; find ohms
Electricians often write V for voltage; exam questions may use E (electromotive force). Treat them as the same quantity in volts.
Worked Example — Find Current
A resistive heating element measures 24 Ω and is connected across a 120 V branch circuit. What is the current?
I = E / R = 120 / 24 = 5 A
That 5 A load on a 15 A or 20 A branch is within rating before continuous-load factors; the theory question usually stops at finding 5 A.
Worked Example — Find Resistance
A luminaire draws 0.83 A at 120 V . Approximate filament resistance equivalent:
R = E / I = 120 / 0.83 ≈ 144.6 Ω
On multiple-choice items, expect rounded options such as 145 Ω or 144 Ω.
The Power Family
Power in watts (W) is the rate of energy use. Three equivalent formulas cover nearly every JW theory item:
- Formula Best when you know…
- P = I × E Current and voltage
- P = I²R Current and resistance
- P = E² / R Voltage and resistance
Kilowatts: 1 kW = 1,000 W. Always convert before mixing with amperes and volts unless the question already works in kW with a matching formula.
Worked Example — Power from Current and Voltage
A water heater element draws 18.8 A on a 240 V circuit:
- P = I × E = 18.8 × 240 = 4,512 W ≈ 4.5 kW
- Worked Example — Power from Voltage and Resistance
Same heater, resistance 12.8 Ω at operating temperature on 240 V:
P = E² / R = (240)² / 12.8 = 57,600 / 12.8 = 4,500 W
Slight differences come from rounding of measured current versus nameplate ohms — exam problems give clean numbers so answers match exactly.
Single-Phase kW to Amperes
For DC or single-phase AC with unity power factor (resistive loads):
I = (kW × 1,000) / E
Example: A 3 kW baseboard heater on 240 V :
I = (3 × 1,000) / 240 = 3,000 / 240 = 12.5 A
Continuous heating loads are later sized at 125% for branch-circuit and OCPD selection (Article 210/424 concepts), but the pure calculation question often asks only for the load current: 12.5 A.
Three-Phase Power (When PF Appears)
If the Prov item gives three-phase voltage and power factor:
- P = E × I × 1.732 × PF (watts, line-to-line E)
- I = P / (E × 1.732 × PF)
Example: A three-phase load of 15 kW at 208 V , PF 0.85 :
I = 15,000 / (208 × 1.732 × 0.85) ≈ 15,000 / 306.3 ≈ 49 A
If PF is omitted and the load is described as resistive, treat PF as 1.0.
Horsepower Shortcuts (Nameplate Context)
Motors are covered heavily elsewhere on the outline, but theory items sometimes convert hp to watts: 1 hp ≈ 746 W . A 1 hp motor input is higher than 746 W because of efficiency and power factor — if the question says "output" use 746 W; if it gives efficiency, divide output by efficiency to get input watts, then find current.
Example: 1 hp motor, 85% efficient, 240 V single-phase, PF 0.9:
- Input W = 746 / 0.85 ≈ 878 W
- I = 878 / (240 × 0.9) ≈ 4.1 A
- Unit Discipline
Common traps on open-book calculation days:
- Leaving current in mA (divide by 1,000 to get amperes before Ohm's law)
- Mixing kW with a formula that expects watts
- Using 208 V when the stem says 240 V (or vice versa)
- Forgetting that P = I²R uses amperes squared — a 10 A load on 2 Ω dissipates 200 W, not 20 W
- Quick Reference Card for Exam Day
- Need Use
- Amps from volts and ohms I = E / R
- Volts from amps and ohms E = I × R
- Ohms from volts and amps R = E / I
- Watts from amps and volts P = I × E
- Watts from amps and ohms P = I²R
- Watts from volts and ohms P = E² / R
- Amps from kW (1φ) I = (kW × 1000) / E
- Relating Power Formulas Without a Calculator Panic
If you know any two of P, I, E, or R (with a consistent set), you can find the others. Suppose a question gives only P = 1,440 W and E = 120 V . Current is I = P / E = 1,440 / 120 = 12 A , then R = E / I = 120 / 12 = 10 Ω . Checking with P = I²R: 12² × 10 = 1,440 W. Building that habit catches wrong answer choices that swapped watts and amperes.
For multiwire branch circuits and shared neutrals, theory questions still treat each ungrounded conductor's load with Ohm's law separately unless the stem clearly combines loads. Do not invent three-phase math on a single-phase 120/240 V dwelling stem.
Practice these until you can pick the correct rearrangement in under ten seconds. On a 60-question, 3-hour Arkansas JW exam, theory items should be quick wins that bank time for Code lookups in grounding, services, and special occupancies.