Study guide
2.2 Series, Parallel, and Combination Circuits
Arkansas Journeyman Electrician Exam Study Guide 2026
Track your progress as you read
Finished sections get a check mark.
1 Introduction & Arkansas Exam Overview
1.1 Current Exam Facts 1.2 Arkansas Licensing Pathway & Board Process 1.3 Open-Book Rules & Allowed References 1.4 NEC 2023 Navigation & Lookup Strategy
2 Electrical Theory & Trade Calculations
2.1 Ohm's Law, Power, and Basic Circuits 2.2 Series, Parallel, and Combination Circuits 2.3 Voltage Drop Calculations 2.4 Box Fill Calculations (314.16)
3 Load Calculations (Article 220)
3.1 Standard Dwelling Unit Load Calculations 3.2 Optional Dwelling & Multifamily Demand 3.3 Commercial / Non-Dwelling Demand Factors 3.4 Ampacity Adjustment & Correction (310.15)
4 Grounding Electrode Systems
4.1 Grounding Electrode Types & Installation 4.2 Grounding Electrode Conductor Sizing (250.66) 4.3 Main Bonding Jumper & Service Bonding
5 Equipment Grounding & Bonding
5.1 Equipment Grounding Conductors (250.122) 5.2 Bonding Raceways, Enclosures & Equipment 5.3 Separately Derived Systems Grounding
6 Services & Service Equipment
6.1 Service Entrance Conductors & Clearances 6.2 Service Disconnecting Means 6.3 Service Equipment & Working Space 6.4 Grounding Connections at the Service
7 Feeders & Overcurrent Protection
7.1 Feeder Conductor Sizing 7.2 Overcurrent Device Selection (Art 240) 7.3 Feeder and Branch-Circuit Tap Rules 7.4 Continuous Loads & OCPD Sizing
8 Branch Circuits, GFCI & AFCI
8.1 Branch-Circuit Ratings & Required Circuits 8.2 Dwelling Receptacle Placement & Kitchen/Bath Circuits 8.3 GFCI Protection Requirements 8.4 AFCI Protection Requirements
9 Metal Raceways
9.1 EMT Installation & Supports 9.2 RMC and IMC 9.3 Flexible Metal & Liquidtight Flexible Metal Conduit
10 Nonmetallic Raceways & Enclosures
10.1 PVC and ENT 10.2 Conduit Fill (Chapter 9 Tables) 10.3 Boxes, Conduit Bodies & Fill 10.4 Cabinets, Cutout Boxes & Meter Enclosures
11 Conductor Ampacity & Selection
11.1 Ampacity Table 310.16 Application 11.2 Termination Temperature Limitations 11.3 Conductor Insulation Types & Uses 11.4 Parallel Conductors
12 Cable Assemblies & Terminations
12.1 NM, MC, and AC Cable Assemblies 12.2 Conductor Identification & Color Coding 12.3 Splices, Taps & Terminations
13 Motors (Article 430)
13.1 Motor Nameplate Data & FLC Tables 13.2 Motor Branch-Circuit Conductors 13.3 Motor Overload Protection 13.4 Motor Short-Circuit / Ground-Fault Protection
14 Motor Controls & Transformers
14.1 Motor Disconnects & Controllers 14.2 Motor Control Circuits 14.3 Transformers (Article 450) for Journeymen
15 Utilization & General-Use Equipment
15.1 Luminaires & Lighting (Art 410) 15.2 Receptacles & Switches (Arts 406/404) 15.3 Appliances & Fixed Electric Space-Heating 15.4 Panelboards (Art 408)
16 Special Occupancies
16.1 Hazardous (Classified) Locations Overview 16.2 Health Care, Assembly & Temporary Installations 16.3 Swimming Pools, Spas & Similar Installations
17 Special Equipment Highlights
17.1 Signs & Outline Lighting 17.2 Elevators & Electric Vehicle Power Transfer 17.3 Emergency & Standby Systems Basics
18 Low-Voltage, Alarms & Communications
18.1 Class 1, 2, and 3 Circuits (Art 725) 18.2 Fire Alarm Systems (Art 760) 18.3 Communications Circuits Overview (Art 800+)
19 Electrical Safety
19.1 Working Space & Dedicated Equipment Space (110.26) 19.2 Lockout/Tagout & Safe Work Practices 19.3 Arc-Flash Awareness for the Exam
20 Exam Strategy & Test Day
20.1 Mixed Calculation Lab 20.2 Timed Code Lookup Drills 20.3 Test-Day Checklist, Scoring & Retakes
2.2 Series, Parallel, and Combination Circuits
Key Takeaways Explain This Topic AI
Series circuits: same current through every component; voltages add; total resistance is the sum of individual resistances
Parallel circuits: same voltage across every branch; currents add; total resistance is always less than the smallest branch resistance
Two equal parallel resistors: RT = R / 2; product-over-sum for two unequal resistors: RT = (R1 × R2) / (R1 + R2)
Combination circuits: reduce parallel groups first, then add series portions — or vice versa depending on the diagram
Arkansas JW theory items often ask for total resistance, branch current, or voltage across one resistor in a simple series or parallel string
Last updated: August 2026
After Ohm's law, the next General Knowledge skill is recognizing how loads connect. Arkansas Journeyman items may show a simple schematic or describe "three 60 Ω resistors in parallel" and ask for total resistance or total current from a stated supply voltage. Getting series versus parallel rules backward is one of the fastest ways to miss an otherwise easy calculation point.
Series Circuits — One Path
In a series circuit there is only one current path. Every ampere that leaves the source returns through every component.
Rules:
- Quantity Series behavior
- Current (I) Same through all parts: I_total = I1 = I2 = I3
- Voltage (E) Voltages add: E_total = E1 + E2 + E3
- Resistance (R) Resistances add: RT = R1 + R2 + R3
Voltage divider: The voltage across one series resistor is proportional to its share of total resistance:
- E_x = E_total × (R_x / RT)
- Worked Example — Series Resistances
Three resistors — 10 Ω, 20 Ω, and 30 Ω — are connected in series across 120 V .
- RT = 10 + 20 + 30 = 60 Ω
- I = 120 / 60 = 2 A (same through each)
Voltage across the 30 Ω resistor:
E30 = 2 × 30 = 60 V
Or by divider: E30 = 120 × (30/60) = 60 V. Check: 20 + 40 + 60 = 120 V across the three parts.
Parallel Circuits — Shared Voltage
In a parallel circuit each branch sees the full source voltage. Currents split among branches and recombine at the return.
Rules:
- Quantity Parallel behavior
- Voltage (E) Same across all branches: E_total = E1 = E2 = E3
- Current (I) Currents add: I_total = I1 + I2 + I3
- Resistance (R) Reciprocal sum: 1/RT = 1/R1 + 1/R2 + 1/R3
Important check: Parallel RT is always smaller than the smallest individual branch resistance. If your answer is larger than the smallest R, you added instead of paralleling.
Two-Resistor Parallel Shortcut
For exactly two resistors:
RT = (R1 × R2) / (R1 + R2)
Equal resistors: two 40 Ω in parallel → RT = 20 Ω. Three equal resistors → RT = R / 3.
Worked Example — Parallel Branches
Two loads on a 120 V circuit: 40 Ω and 60 Ω in parallel.
- RT = (40 × 60) / (40 + 60) = 2,400 / 100 = 24 Ω
- I_total = 120 / 24 = 5 A
Branch currents:
- I40 = 120 / 40 = 3 A
- I60 = 120 / 60 = 2 A
3 + 2 = 5 A — confirms Kirchhoff's current law.
Three Unequal Parallel Resistors
Find RT for 10 Ω, 15 Ω, and 30 Ω in parallel:
- 1/RT = 1/10 + 1/15 + 1/30 = 0.100 + 0.067 + 0.033 = 0.200
- RT = 1 / 0.200 = 5 Ω
Note 5 Ω < 10 Ω (smallest branch) — the sanity check passes.
On 120 V , I_total = 120 / 5 = 24 A . Individual branches: 12 A, 8 A, and 4 A respectively.
Combination Circuits
Real exam diagrams often mix series and parallel. Strategy:
Identify pure parallel groups and reduce each group to a single equivalent resistance.
Redraw: those equivalents now sit in series (or another parallel group).
Continue until one RT remains, then apply Ohm's law for total current.
Work backward: use series current or parallel voltage to find individual branch values asked in the stem.
Worked Example — Combination
A 10 Ω resistor is in series with a parallel combination of 20 Ω and 30 Ω . Supply is 120 V .
Step 1 — Parallel pair:
R_par = (20 × 30) / (20 + 30) = 600 / 50 = 12 Ω
Step 2 — Series with 10 Ω:
RT = 10 + 12 = 22 Ω
Step 3 — Total current:
I_total = 120 / 22 ≈ 5.45 A
Voltage across the parallel pair:
- E_par = 5.45 × 12 ≈ 65.5 V
- (The 10 Ω series resistor drops about 54.5 V; 54.5 + 65.5 = 120 V.)
Current through the 20 Ω branch:
I20 = 65.5 / 20 ≈ 3.28 A
Current through the 30 Ω branch:
I30 = 65.5 / 30 ≈ 2.18 A
3.28 + 2.18 ≈ 5.46 A ≈ I_total through the series 10 Ω — consistent.
Open and Short Concepts (Theory Wording)
Open in a series string stops all current (I = 0). An open in one parallel branch kills only that branch; other branches still see source voltage.
Short across a resistor forces nearly zero voltage across that path and can dump large current limited only by remaining circuit resistance and source capacity — overcurrent devices exist for this reason.
Exam Timing Tip
On the Prov Arkansas JW exam you have about three minutes per question on average. Series/parallel items should take under a minute if you:
Label whether the unknown is RT, I, or E_x.
Write the one-line formula before punching the calculator.
Run the "RT < smallest R?" check on every parallel answer.
Power in Series vs Parallel
Because power is additive for separate loads, total watts equal the sum of each resistor's dissipation. In series at 2 A through 10 Ω, 20 Ω, and 30 Ω: P = I²R gives 40 W + 80 W + 120 W = 240 W , which matches P = E × I = 120 × 2. In parallel at 120 V across 40 Ω and 60 Ω: P40 = E²/R = 360 W and P60 = 240 W for 600 W total — matching 120 V × 5 A. If your power totals disagree with E × I_total, revisit the resistance reduction.
Lighting strings marketed as "series holiday lights" behave like series filaments: one open extinguishes the string. Building receptacles and most utilization equipment are parallel on the branch so each device receives full circuit voltage — that mental model helps you reject series answers on dwelling wiring theory items.
These habits protect the nine General Knowledge points and free clock time for Article 250 and Article 430 lookups later in the session.