Study guide
8.4 Dual-Fuel & Geothermal (Ground-Source) Heat Pump Systems
Arkansas HVAC/R Contractor License Exam
Track your progress as you read
Finished sections get a check mark.
1 Arkansas HVAC/R Licensing Law, Board Rules & Administration
1.1 Arkansas HVAC/R Board Authority, Statutes & Definitions 1.2 License Classifications & Capacity Limitations 1.3 Registrant Requirements, Apprenticeship & Experience Verification 1.4 License Renewal, Continuing Education & Disciplinary Actions
2 HVAC Thermodynamics, Psychrometrics & Gas Laws
2.1 Principles of Heat Transfer & Thermodynamic Fundamentals 2.2 Psychrometric Chart Dynamics & Air Properties 2.3 Psychrometric Processes & Air Mixture Calculations 2.4 Gas Laws Applied to HVAC/R Systems
3 Heating and Cooling Load Calculations (Manual J & S)
3.1 ACCA Manual J Design Conditions & Thermal Envelopes 3.2 Peak Cooling Load Calculations: Sensible vs. Latent Heat Gain 3.3 Heating Load Calculations & Infiltration Rates 3.4 ACCA Manual S Equipment Selection & Verification
4 Ductwork Design, Sizing & SMACNA Standards (Manual D)
4.1 ACCA Manual D Airflow Fundamentals & External Static Pressure 4.2 Equal Friction & Static Regain Duct Sizing Methods 4.3 Duct Fittings, Equivalent Length & Dynamic Losses 4.4 SMACNA Duct Construction Standards & Joint Sealing
5 Air Distribution, Balancing & Ventilation Codes
5.1 Supply & Return Air Distribution Hardware (Grilles, Registers, Diffusers) 5.2 System Airflow Testing, Adjusting & Balancing (TAB) 5.3 Ventilation Standards: ASHRAE 62.1, 62.2 & 2021 IMC Ventilation Air
6 Mechanical Refrigeration Cycle & Components
6.1 The Vapor-Compression Refrigeration Cycle 6.2 Compressors & Operating Characteristics 6.3 Condensers & Evaporators 6.4 Metering Devices & Refrigerant Flow Controls 6.5 Refrigerant Line Sizing, Oil Return & Field Piping Practices
7 Refrigerants, Oils & EPA Section 608 Regulations
7.1 Refrigerant Chemistry, ASHRAE Standard 34 & A2L Transition 7.2 Lubricating Oils & System Compatibility 7.3 EPA Section 608 Regulatory Mandates & Recovery Standards 7.4 System Evacuation, Dehydration & Leak Detection
8 Air Conditioning & Heat Pump Systems
8.1 Residential & Commercial Split Systems and Package RTUs 8.2 Air-Source Heat Pumps & The Reversing Valve 8.3 Supplemental & Emergency Heating Systems 8.4 Dual-Fuel & Geothermal (Ground-Source) Heat Pump Systems
9 Gas Furnaces, Combustion Air & Venting (IFGC / IMC)
9.1 Gas Furnace Types, AFUE Ratings & Sequence of Operation 9.2 Gas Burners, Ignition Systems & Flame Safeguard Controls 9.3 Combustion Air Requirements (IFGC Chapter 3 / IMC Chapter 7) 9.4 Flue Gas Venting & Category I-IV Venting Systems
10 Boilers, Hydronics & Fuel Gas Piping
10.1 Hydronic Heating Systems, Low-Pressure Boilers & ASME Code 10.2 Hydronic Distribution, Circulator Pumps & Piping Loops 10.3 Fuel Gas Piping Materials, Sizing & Pressure Testing (IFGC Chapter 4) 10.4 Gas Regulators, Manifold Pressure & Gas Meter Sizing 10.5 Condensate Disposal, Piping Support & Mechanical Insulation
11 Electrical Fundamentals, Motors & Control Circuits
11.1 HVAC Electrical Fundamentals, Ohm's Law & Power Calculations 11.2 Single-Phase & Three-Phase Electric Motors in HVAC 11.3 Low-Voltage Control Circuits & Thermostats
12 National Electrical Code (NEC) for HVAC Equipment
12.1 NEC Article 440: Hermetic Refrigerant Motor-Compressors & Branch Circuits 12.2 Equipment Disconnecting Means & Overcurrent Protective Devices (OCPD) 12.3 Motor Branch Circuit Sizing & Conductor Ampacity (NEC Article 430 & Tables)
13 System Maintenance, Troubleshooting & Safety Standards
13.1 Systematic Mechanical & Electrical Troubleshooting 13.2 Airflow & Refrigerant Charge Diagnostics 13.3 Jobsite Safety, OSHA Standards & Personal Protective Equipment
14 Plan Reading, Estimating & HVAC/R Trade Math
14.1 Mechanical Plan Symbols, Schedules & Abbreviations 14.2 Architectural Scales, Dimensions & Quantity Takeoff 14.3 Material, Labor & Bid Estimating 14.4 Applied HVAC/R Trade Math & Unit Conversions
8.4 Dual-Fuel & Geothermal (Ground-Source) Heat Pump Systems
Key Takeaways Explain This Topic AI
Dual-fuel (hybrid) systems combine an electric air-source heat pump with a natural gas or propane furnace, maximizing seasonal efficiency by switching heating modes at an outdoor thermostat balance point.
In a dual-fuel system, the heat pump indoor coil must always be installed downstream (on the discharge supply air side) of the gas furnace, and controls must strictly prevent simultaneous furnace and heat pump operation during normal heating.
Simultaneous operation of a fossil fuel furnace and heat pump compressor subjects the indoor coil (acting as a condenser) to extreme 130°F–140°F air temperatures, causing catastrophic refrigerant head pressure spikes that trip high-pressure safety switches.
Geothermal ground-source heat pumps (GSHPs) leverage constant subsurface earth temperatures (~55°F–60°F in Arkansas) to deliver industry-leading efficiencies, achieving cooling EERs of 20 to 35+ and heating COPs exceeding 4.0 to 5.2.
Closed-loop vertical geothermal installations require high-density polyethylene (HDPE) piping with heat-fused joints encased in high-solids thermally enhanced bentonite grout to maximize borehole heat transfer and safeguard groundwater aquifers.
Last updated: September 2026
8.4 Dual-Fuel & Geothermal (Ground-Source) Heat Pump Systems
Note
Advanced Heat Pumping Frontiers : While conventional air-source heat pumps provide clean, efficient comfort conditioning across moderate climates, extreme winter temperature drops and peak summer heat waves present severe efficiency penalties. To overcome the limitations of ambient air as a heat source and heat sink, advanced HVAC engineering utilizes two sophisticated alternatives: dual-fuel (hybrid) systems , which combine the high seasonal COP of an electric heat pump with the high-temperature capacity of a fossil fuel furnace, and geothermal (ground-source) heat pumps (GSHPs) , which reject and extract thermal energy from the earth's stable subterranean thermal mass. Mastery of both technologies is essential for modern mechanical contractors seeking advanced licensure.
Dual-Fuel (Hybrid) System Architecture & Thermodynamics
A dual-fuel system (frequently termed a hybrid heat pump ) pairs an outdoor electric air-source heat pump with an indoor fossil fuel (natural gas or LP/propane) furnace acting as the air distribution system and auxiliary heat source. [OUTDOOR HEAT PUMP]
- |
- Refrigerant Lines (Vapor & Liquid)
- |
- v
- +-------------------------------------------------------------------------+
- | INDOOR AIR HANDLER TRAIN |
- | |
- | [SUPPLY AIR PLENUM] |
- | ^ |
- | | |
- | [INDOOR CASED COIL] <----- MUST BE DOWNSTREAM (DISCHARGE SIDE) |
- | ^ |
- | | |
- | [FOSSIL FUEL FURNACE] <--- Upstream Gas Burners & Heat Exchanger |
- | ^ |
- | | |
- | [RETURN AIR / BLOWER] <--- Return Air Inflow |
- +-------------------------------------------------------------------------+
- The Operational Changeover Strategy
Dual-fuel systems exploit the economic and physical strengths of both heating platforms:
Mild Winter Temperatures (Above Balance Point, e.g., > 35°F) :
The outdoor heat pump operates at high efficiency (COP 3.0 to 4.2). Delivering heat via the vapor-compression cycle is substantially less expensive than burning fossil fuel.
The furnace gas burners remain OFF; the furnace ECM blower operates to distribute heat pump comfort.
Severe Winter Temperatures (Below Balance Point, e.g., < 30°F–35°F) :
As outdoor temperatures drop, heat pump capacity falls and defrost cycles multiply.
An outdoor ambient thermostat or electronic dual-fuel logic board de-energizes the heat pump compressor entirely and ignites the gas furnace burners.
The furnace delivers high-temperature (120°F to 140°F) supply air, satisfying space heating demands regardless of sub-freezing outdoor weather.
Physical Coil Placement: Downstream Discharge Mandate
In dual-fuel installations, the cased indoor refrigerant coil must always be installed on the downstream (discharge / supply air) side of the gas furnace :
Why Downstream? : If the coil were placed on the upstream return air side of the furnace, cold supply air (45°F to 55°F) during summer cooling would blow directly across the furnace's primary steel heat exchanger. The resulting moisture condensation on the cold steel would cause rapid rust perforation, cracking, and lethal carbon monoxide leakage into the airstream.
The Interlock Mandate: The Fossil Fuel Kit
A fundamental engineering principle governing dual-fuel systems is that the gas furnace burners and the heat pump compressor must NEVER operate simultaneously during normal heating :
In heating mode, the indoor coil acts as the refrigerant condenser , releasing heat from high-pressure discharge gas into the air stream.
If the gas furnace burners were allowed to fire while the heat pump compressor is running, 130°F to 140°F air from the furnace combustion heat exchanger would blow directly across the indoor refrigerant coil.
This blistering air eliminates the temperature difference required to condense the refrigerant. Liquid refrigerant cannot condense; condensing pressure skyrockets immediately past 550 to 600 psig (on R-410A systems).
Within seconds, the high-pressure safety cutout switch trips, causing violent mechanical cycling, compressor motor overheating, and potential rupture of compressor discharge valves.
To prevent this disaster, older systems utilize an electromechanical fossil fuel kit (a relay interlock package), while modern systems utilize dual-fuel thermostats or integrated furnace control boards that electronically lock out the compressor whenever the gas valve receives 24V power.
Warning
Defrost Changeover in Dual-Fuel Systems : During an outdoor defrost cycle, the heat pump temporarily shifts into cooling mode (the indoor coil becomes an evaporator). In some dual-fuel systems, the control board energizes the gas furnace burners during defrost to temper the indoor air. However, because the indoor coil is cold (absorbing heat), simultaneous operation during defrost does not cause high head pressure. Once defrost terminates and the heat pump returns to heating, the furnace burners must instantly de-energize.
Geothermal (Ground-Source) Heat Pump (GSHP) Fundamentals
While air temperatures fluctuate wildly between summer extremes (95°F to 105°F) and winter freezes (0°F to 15°F), the temperature of the earth below a depth of 10 to 20 feet remains remarkably stable year-round. In Arkansas, this subsurface earth temperature remains virtually constant at 55°F to 62°F . SEASONAL HEAT EXCHANGER COMPARISON
- +---------------------------------------------------------------------------------------+
- | MEDIUM | SUMMER REJECTION SINK | WINTER EXTRACTION SOURCE | EFFICIENCY RANGE |
- |----------------+------------------------+--------------------------+------------------|
- | Ambient Air | 95°F to 105°F (Hot) | 10°F to 30°F (Cold) | EER 13-18 / COP 2.5-3.5|
- | Earth Subsoil | 55°F to 60°F (Cool) | 55°F to 60°F (Warm) | EER 20-35+ / COP 4.0-5.2+|
- +---------------------------------------------------------------------------------------+
A geothermal ground-source heat pump (GSHP) rejects heat into this cool earth sink during summer and extracts heat from this warm earth source during winter. Because the heat pump operates against a vastly narrower temperature difference (lift), compressor work is drastically reduced, delivering industry-leading energy efficiencies:
Cooling EER : 20.0 to 35.0+ BTU/Watt-hr (compared to 12–16 for standard air-source units).
Heating COP : 4.0 to 5.2 (delivering over 4 to 5 units of heat energy per unit of electric power consumed).
Ground Heat Exchanger (GHEX) Loop Configurations
Geothermal systems are broadly categorized into two thermodynamic categories: closed-loop systems and open-loop systems . GEOTHERMAL LOOP CONFIGURATIONS
- |
- +----------------------+----------------------+
- | |
- CLOSED-LOOP SYSTEMS OPEN-LOOP SYSTEMS
- (Continuous Sealed Circulation) (Groundwater Well Extraction)
- | | |
- v v v
- Vertical Boreholes Horizontal Trenches Extraction Well
- (150-400 ft deep) (4-6 ft deep / Slinky) ("Pump & Dump" / Return Well)
- Small footprint - Large land area - Highest efficiency
- Thermally grouted - Seasonal moisture drift - Cupronickel coil required
- 1. Closed-Loop Vertical Boreholes
Engineering Design : The most common commercial and residential configuration where land area is restricted. Vertical boreholes (typically 4 to 6 inches in diameter) are drilled to depths of 150 to 400 feet .
Sizing Rule of Thumb : Approximately 150 to 250 bore feet per ton of cooling capacity , depending on soil thermal conductivity and drilling formations.
Piping Specifications : High-Density Polyethylene (HDPE 3408, 3608, or 4710) pipe with factory-molded U-bend fittings installed at the bottom. All subterranean pipe joints must be joined exclusively by thermal heat fusion (butt fusion, socket fusion, or electrofusion). Threaded, glued, or mechanical compression joints are strictly prohibited underground under IGSHPA (International Ground Source Heat Pump Association) standards.
Borehole Grouting : Under the Arkansas Water Well Construction Commission rules and environmental regulations, boreholes must be pressure-grouted from the bottom up through a tremie pipe using thermally enhanced bentonite grout (bentonite clay mixed with silica sand to achieve a thermal conductivity k k k of 0.85 to 1.20 BTU/hr·ft·°F ). High-solids grout seals the borehole, eliminates insulating air gaps, and prevents surface contaminants from migrating into subterranean drinking water aquifers.
2. Closed-Loop Horizontal Trenches & Slinky Coils
Horizontal Trenches : HDPE pipes are buried in trenches excavated 4 to 6 feet deep . Configurations include two-pipe, four-pipe, or six-pipe layouts per trench. Requires approximately 400 to 600 trench feet per ton .
Slinky / Spiral Loops : Overlapping, circular spirals of continuous HDPE pipe rolled out flat into wide trenches (3 to 6 feet wide). Slinky loops pack up to 800 to 1,000 feet of pipe per ton into substantially shorter trench lengths (typically 100 to 150 trench feet per ton).
Limitation : Requires expansive unobstructed land acreage. Shallow soil temperatures (4–6 feet) are influenced by surface weather, drought, and winter freezes, resulting in wider loop temperature swings than vertical systems.
3. Closed-Loop Surface Water / Pond Loops
Submerged bundles or slinky coils of HDPE pipe anchored at the bottom of a nearby lake, farm pond, or retention basin.
Criteria : Water body must maintain a minimum depth of 8 to 10 feet at the loop location and have a minimum surface area of 0.5 to 1.0 acre with sufficient water volume to prevent freezing solid in winter.
Advantage : Lowest excavation and installation cost; exceptional convective heat transfer between circulating pipe and pond water.
4. Open-Loop Groundwater Systems ("Pump and Dump")
Operational Principle : Groundwater is pumped directly from a water supply well (at a steady 55°F to 60°F) directly through the heat pump's internal water-to-refrigerant coaxial heat exchanger.
Discharge Options : Water exits the unit and is discharged into a second injection / return well (recharging the aquifer), a surface drainage pond, or a stream, subject to Arkansas Department of Energy and Environment (ADEE / ADEQ) permitting.
Water Flow Requirements : Typically requires 1.5 to 3.0 Gallons Per Minute (GPM) per ton of capacity.
Water Quality Vulnerabilities : Untreated groundwater can cause severe mineral scaling (calcium carbonate), iron bacteria fouling, particulate abrasion, and acid corrosion. Open-loop systems strictly mandate cupronickel heat exchangers (a 70/30 or 90/10 copper-nickel alloy) rather than standard copper to prevent tube erosion and pitting.
Equipment Architecture: Water-to-Air vs. Water-to-Water
Geothermal machinery utilizes the vapor-compression cycle with specialized fluid-to-refrigerant heat exchangers: +---------------------------------------+
- | GEOTHERMAL REFRIGERATION CABINET |
- | |
- Earth Loop In --->| [WATER-TO-REFRIGERANT HEAT EXCHANGER] |<--- Coaxial Tube-in-Tube
- Earth Loop Out <---| (Refrigerant Condenser / Evaporator) |
- | |
- | [COMPRESSOR] <==> [REVERSING VALVE] |
- | |
- | [SECONDARY LOAD HEAT EXCHANGER] |
- +-------------------+-------------------+
- |
- +--------------------+--------------------+
- | |
- WATER-TO-AIR UNIT WATER-TO-WATER UNIT
- Refrigerant-to-Air Fin Coil - Second Water-to-Refrig Exchanger
- ECM Supply Blower Fan - Hydronic Circulator Pumps
- Delivers ducted conditioned air - Radiant floor heating / Hydronic FCUs
- 1. Water-to-Air Systems
The geothermal cabinet contains a coaxial tube-in-tube water-to-refrigerant heat exchanger, a hermetic scroll compressor, a 4-way reversing valve, and an indoor refrigerant-to-air finned coil with an ECM blower .
Distributes conditioned air directly through traditional ductwork, identical to a standard split air handler.
Domestic Hot Water Desuperheater : Most residential water-to-air units incorporate a factory-installed desuperheater —a small circulating water pump and double-wall heat exchanger that captures high-temperature discharge gas directly from the compressor. During summer cooling and winter heating, it preheats domestic potable water to 120°F–140°F for free, depositing it into the home's water heater tank.
2. Water-to-Water Systems
The geothermal cabinet contains two fluid heat exchangers : a source heat exchanger connected to the ground loop, and a load heat exchanger connected to a building hydronic loop.
Produces chilled water (45°F to 50°F) during cooling to feed hydronic fan coil units, and hot water (105°F to 130°F) during heating to feed in-slab radiant hydronic floor loops or domestic hot water storage tanks.
3. Antifreeze Solutions in Closed Loops
In closed-loop systems in northern regions and mixed climates, ground loop fluid temperatures can drop to 25°F to 30°F during peak winter operation. To prevent the water-to-refrigerant heat exchanger from freezing and rupturing, the closed loop must be charged with clean water mixed with an approved non-toxic antifreeze:
Propylene Glycol : Environmentally safe and non-toxic; requires higher pumping horsepower due to elevated fluid viscosity at low temperatures.
Denatured Ethanol or Methanol : Low viscosity and exceptional heat transfer properties; highly flammable in concentrated form, requiring strict safety protocols during site mixing and charging.
Realistic Trade Scenario: Dual-Fuel Coil Inversion Disaster
A mechanical contractor in Springdale, Arkansas, installs a dual-fuel system consisting of an 80% AFUE natural gas furnace and a 3-ton 16-SEER air-source heat pump. During initial start-up in June, the cooling system performs flawlessly. However, during the first freezing cold snap in December, the homeowner calls reporting that the outdoor heat pump makes a loud grinding noise and trips the main electrical breaker whenever the furnace ignites.
An ADLL licensed contractor investigates the installation. Upon removing the furnace closet access panels, the contractor discovers two catastrophic installation errors:
The installing crew placed the cased evaporator coil beneath the furnace on the return air side, rather than above the furnace on the supply discharge side.
The low-voltage wiring was connected with a standard single-stage heat thermostat without an outdoor balance sensor, fossil fuel kit, or compressor lockout interlock.
Failure Mechanism Forensics :
When the thermostat called for heating, it energized the heat pump compressor (Y) and simultaneously fired the gas furnace burners (W). Because the coil was improperly placed, cold supply air was condensing on the heat exchanger. Worse, when the homeowner selected emergency heat, the furnace fired, but the heat pump continued to run. If the heat pump had operated in heating mode with the coil on top, 140°F air would have driven condensing pressure past 600 psig, blowing the compressor terminal plug.
Corrective Reconstruction :
The contractor completely re-engineers the mechanical closet, installing the gas furnace at the base and mounting the cased coil on the discharge supply plenum above the furnace.
Installs an outdoor temperature sensor and a smart dual-fuel thermostat , programming a hard compressor lockout balance point at 32°F .
Verifies that whenever the furnace gas valve receives 24V, the compressor contactor is physically locked out, protecting the compressor and ensuring code compliance.
Common Exam Traps & Key Distinctions
Exam Trap: Dual-Fuel Coil Location : Licensing exams frequently ask whether the cased coil goes upstream or downstream of a fossil fuel furnace. It must always be installed downstream (on the discharge / supply air side) of the furnace.
Exam Trap: Simultaneous Operation of Dual-Fuel : Remember the golden rule: A heat pump compressor and a fossil fuel furnace must NEVER run at the same time in normal heating mode . Doing so causes runaway head pressure.
Exam Trap: Underground Geothermal Pipe Joining : Watch out for questions asking about acceptable pipe joints for underground HDPE geothermal loops. Threaded, compression, and solvent-cemented PVC joints are strictly prohibited ; all underground joints must be thermally heat-fused .
Exam Trap: Open-Loop Coil Materials : Open-loop groundwater systems pumping well water require cupronickel heat exchangers to withstand mineral erosion and pitting, not standard copper.
Exam Trap: Borehole Grouting Requirements : In vertical geothermal installations, boreholes must be pressure-grouted from the bottom up with thermally enhanced bentonite grout to safeguard groundwater aquifers from surface contamination.