Study guide

5.2 System Airflow Testing, Adjusting & Balancing (TAB)

Arkansas HVAC/R Contractor License Exam

Track your progress as you read

Finished sections get a check mark.

1 Arkansas HVAC/R Licensing Law, Board Rules & Administration

1.1 Arkansas HVAC/R Board Authority, Statutes & Definitions 1.2 License Classifications & Capacity Limitations 1.3 Registrant Requirements, Apprenticeship & Experience Verification 1.4 License Renewal, Continuing Education & Disciplinary Actions

2 HVAC Thermodynamics, Psychrometrics & Gas Laws

2.1 Principles of Heat Transfer & Thermodynamic Fundamentals 2.2 Psychrometric Chart Dynamics & Air Properties 2.3 Psychrometric Processes & Air Mixture Calculations 2.4 Gas Laws Applied to HVAC/R Systems

3 Heating and Cooling Load Calculations (Manual J & S)

3.1 ACCA Manual J Design Conditions & Thermal Envelopes 3.2 Peak Cooling Load Calculations: Sensible vs. Latent Heat Gain 3.3 Heating Load Calculations & Infiltration Rates 3.4 ACCA Manual S Equipment Selection & Verification

4 Ductwork Design, Sizing & SMACNA Standards (Manual D)

4.1 ACCA Manual D Airflow Fundamentals & External Static Pressure 4.2 Equal Friction & Static Regain Duct Sizing Methods 4.3 Duct Fittings, Equivalent Length & Dynamic Losses 4.4 SMACNA Duct Construction Standards & Joint Sealing

5 Air Distribution, Balancing & Ventilation Codes

5.1 Supply & Return Air Distribution Hardware (Grilles, Registers, Diffusers) 5.2 System Airflow Testing, Adjusting & Balancing (TAB) 5.3 Ventilation Standards: ASHRAE 62.1, 62.2 & 2021 IMC Ventilation Air

6 Mechanical Refrigeration Cycle & Components

6.1 The Vapor-Compression Refrigeration Cycle 6.2 Compressors & Operating Characteristics 6.3 Condensers & Evaporators 6.4 Metering Devices & Refrigerant Flow Controls 6.5 Refrigerant Line Sizing, Oil Return & Field Piping Practices

7 Refrigerants, Oils & EPA Section 608 Regulations

7.1 Refrigerant Chemistry, ASHRAE Standard 34 & A2L Transition 7.2 Lubricating Oils & System Compatibility 7.3 EPA Section 608 Regulatory Mandates & Recovery Standards 7.4 System Evacuation, Dehydration & Leak Detection

8 Air Conditioning & Heat Pump Systems

8.1 Residential & Commercial Split Systems and Package RTUs 8.2 Air-Source Heat Pumps & The Reversing Valve 8.3 Supplemental & Emergency Heating Systems 8.4 Dual-Fuel & Geothermal (Ground-Source) Heat Pump Systems

9 Gas Furnaces, Combustion Air & Venting (IFGC / IMC)

9.1 Gas Furnace Types, AFUE Ratings & Sequence of Operation 9.2 Gas Burners, Ignition Systems & Flame Safeguard Controls 9.3 Combustion Air Requirements (IFGC Chapter 3 / IMC Chapter 7) 9.4 Flue Gas Venting & Category I-IV Venting Systems

10 Boilers, Hydronics & Fuel Gas Piping

10.1 Hydronic Heating Systems, Low-Pressure Boilers & ASME Code 10.2 Hydronic Distribution, Circulator Pumps & Piping Loops 10.3 Fuel Gas Piping Materials, Sizing & Pressure Testing (IFGC Chapter 4) 10.4 Gas Regulators, Manifold Pressure & Gas Meter Sizing 10.5 Condensate Disposal, Piping Support & Mechanical Insulation

11 Electrical Fundamentals, Motors & Control Circuits

11.1 HVAC Electrical Fundamentals, Ohm's Law & Power Calculations 11.2 Single-Phase & Three-Phase Electric Motors in HVAC 11.3 Low-Voltage Control Circuits & Thermostats

12 National Electrical Code (NEC) for HVAC Equipment

12.1 NEC Article 440: Hermetic Refrigerant Motor-Compressors & Branch Circuits 12.2 Equipment Disconnecting Means & Overcurrent Protective Devices (OCPD) 12.3 Motor Branch Circuit Sizing & Conductor Ampacity (NEC Article 430 & Tables)

13 System Maintenance, Troubleshooting & Safety Standards

13.1 Systematic Mechanical & Electrical Troubleshooting 13.2 Airflow & Refrigerant Charge Diagnostics 13.3 Jobsite Safety, OSHA Standards & Personal Protective Equipment

14 Plan Reading, Estimating & HVAC/R Trade Math

14.1 Mechanical Plan Symbols, Schedules & Abbreviations 14.2 Architectural Scales, Dimensions & Quantity Takeoff 14.3 Material, Labor & Bid Estimating 14.4 Applied HVAC/R Trade Math & Unit Conversions

5.2 System Airflow Testing, Adjusting & Balancing (TAB)

Key Takeaways Explain This Topic AI

Testing, Adjusting, and Balancing (TAB) is the standardized engineering discipline (governed by NEBB, AABC, and SMACNA) of measuring, adjusting, and documenting fluid distribution systems to achieve design airflow within an industry standard tolerance of ±10% per branch and terminal.

Total duct pressure (P_t) is the algebraic sum of static pressure (P_s, outward radial force) and velocity pressure (P_v, directional kinetic force): P_t = P_s + P_v, where velocity pressure is calculated using standard air density as V = 4005 · √(P_v).

Primary TAB instruments include the pitot tube paired with an inclined or digital differential manometer for duct traverse measurements, rotating vane and thermal hot-wire anemometers for coil and face velocity readings, and direct-reading capture hoods (flow hoods) with backpressure compensation for terminal diffusers.

The Fan Affinity Laws govern centrifugal and axial fan performance when adjusting rotational speed (RPM): airflow varies directly (CFM ∝ RPM), static pressure varies with the square (SP ∝ RPM²), and brake horsepower varies with the cube (BHP ∝ RPM³).

Proportional balancing requires identifying the system's 'index terminal' (the branch or diffuser delivering the lowest percentage of design airflow), proportionally trimming all other branches relative to this index terminal without throttling the index damper, and subsequently adjusting total fan RPM to bring the entire system to 100% capacity.

Last updated: September 2026

5.2 System Airflow Testing, Adjusting & Balancing (TAB)

Important

Code Mandates for System Balancing : Modern energy conservation codes, including the 2021 International Energy Conservation Code (IECC Section C408) and the 2021 International Mechanical Code (IMC Section 603.18) , require mechanical systems to be tested, adjusted, and balanced prior to final code sign-off and occupancy certificate issuance. An unbalanced system wastes immense fan energy, starves critical zones of fresh ventilation air, causes room-to-room pressure imbalances that drive building infiltration, and produces severe occupant thermal discomfort.

Fluid Pressure Dynamics in Duct Systems: Static, Velocity & Total Pressure

Air flowing through a duct system possesses mechanical energy that manifests in two distinct fluid pressure states: static pressure and velocity pressure . Understanding how these pressures interact is the cornerstone of all aerodynamic measurement and balancing. Air Flow Direction ───►

═══════════════════════════════════════════ Top Duct Wall

  • Static Tap (Ps)
  • │ (Perpendicular to Flow)
  • ▼
  • ┌─────┐
  • │ │ Total Pressure Tube (Pt)
  • │ │ ┌──────────────────────┐
  • │ │ │ (Impact Tip Faces │◄─── Air Flow
  • │ │ │ Directly Into Flow)│
  • │ │ └───────────┬──────────┘
  • ▼ ▼ ▼
  • ┌───────────┐ ┌───────────┐
  • │ Manometer │ │ Manometer │
  • │ Low Port │ │ High Port │
  • └─────┬─────┘ └─────┬─────┘
  • │ │
  • └──────────────┬───────────────┘
  • ▼

Differential Reading:

  • Pv = Pt - Ps
  • 1. Static Pressure ( P s P_s P s ​ )

Static pressure ( P s P_s P s ​ ) is the potential energy stored within the air stream. It is the outward radial force exerted equally in all directions against the interior duct walls, independent of air velocity or direction. Static pressure can be thought of as the "bursting pressure" that inflates a balloon or expands a flexible duct.

Supply Ductwork : Static pressure is positive ( P s > 0 P_s > 0 P s ​ > 0 ) relative to atmospheric room pressure because the blower pushes air forward against friction and component resistance.

Return Ductwork : Static pressure is negative ( P s < 0 P_s < 0 P s ​ < 0 ) relative to atmospheric room pressure because the suction side of the blower draws air inward toward the fan inlet.

2. Velocity Pressure ( P v P_v P v ​ )

Velocity pressure ( P v P_v P v ​ ) is the kinetic energy of moving air molecules. It is exerted solely in the exact direction of fluid flow. Unlike static pressure, velocity pressure cannot be measured directly with a single wall tap; it must be derived by subtracting static pressure from total pressure ( P v = P t − P s P_v = P_t - P_s P v ​ = P t ​ − P s ​ ).

Fundamental Fluid Rule : Velocity pressure is always a positive value ( P v > 0 P_v > 0 P v ​ > 0 ) whenever air is in motion. It can never be negative or zero in an active duct.

3. Total Pressure ( P t P_t P t ​ )

Total pressure ( P t P_t P t ​ ) is the algebraic sum of static pressure and velocity pressure: P t = P s + P v P_t = P_s + P_v P t ​ = P s ​ + P v ​

As air travels through ductwork, friction against duct walls and dynamic losses across fittings (elbows, transitions) dissipate energy. Consequently, total pressure always drops continuously in the direction of airflow . However, static and velocity pressure can convert back and forth into one another:

When a duct expands into a larger cross-sectional area, air velocity decreases. As velocity pressure drops, a portion of that kinetic energy converts into increased static pressure—a phenomenon termed static regain .

When a duct transitions into a narrower duct, air accelerates. Static pressure drops to generate the increased velocity pressure required to accelerate the mass of air.

Mathematical Derivation of Air Velocity from Velocity Pressure

Under standard atmospheric conditions (sea level barometric pressure of 29.92 in. Hg 29.92\text{ in. Hg} 29.92 in. Hg , 70 ∘ F 70^\circ\text{F} 7 0 ∘ F dry-bulb temperature, and standard air density ρ = 0.075 lb/ft 3 \rho = 0.075\text{ lb/ft}^3 ρ = 0.075 lb/ft 3 ), fluid velocity is directly calculated from velocity pressure using Bernoulli's equation: V = 4005 × P v V = 4005 \times \sqrt{P_v} V = 4005 × P v ​ ​

Where:

  • V V V = Fluid air velocity in feet per minute (FPM)
  • P v P_v P v ​ = Velocity pressure measured in inches of water gauge (in. w.g.)

4005 4005 4005 = Standard conversion constant incorporating gravitational acceleration ( g = 32.174 ft/s 2 g = 32.174\text{ ft/s}^2 g = 32.174 ft/s 2 ), standard air density ( 0.075 lb/ft 3 0.075\text{ lb/ft}^3 0.075 lb/ft 3 ), and unit conversions ( 12 in/ft 12\text{ in/ft} 12 in/ft , 60 s/min 60\text{ s/min} 60 s/min , and water density 62.37 lb/ft 3 62.37\text{ lb/ft}^3 62.37 lb/ft 3 at 68 ∘ F 68^\circ\text{F} 6 8 ∘ F )

Once velocity is determined, the volumetric airflow rate (CFM) passing through the duct cross-section is calculated using the continuity equation: CFM = V × A \text{CFM} = V \times A CFM = V × A

Where A A A is the internal cross-sectional area of the duct in square feet ( ft 2 \text{ft}^2 ft 2 ).

Air Density Correction : At high elevations (such as mountainous regions) or high airstream temperatures, air density drops below 0.075 lb/ft 3 0.075\text{ lb/ft}^3 0.075 lb/ft 3 . In such environments, technicians must apply an air density correction factor ( K d = 0.075 / ρ actual K_d = 0.075 / \rho_{\text{actual}} K d ​ = 0.075/ ρ actual ​ ) so that V = 4005 × P v × K d V = 4005 \times \sqrt{P_v \times K_d} V = 4005 × P v ​ × K d ​ ​ .

TAB Instrumentation and Measurement Protocols

Accurate field balancing requires matching the correct instrument to the specific fluid dynamics of the measurement location.

Instrument Operating Principle Ideal Applications Limitations & Precautions

Pitot-Static Tube Concentric dual-tube sensing total pressure at open tip and static pressure through radial side ports Duct traverses in rigid ductwork to measure velocity pressure ( P v P_v P v ​ ) Unreliable below 600 − 800 FPM 600 - 800\text{ FPM} 600 − 800 FPM ; requires straight, non-turbulent duct runs

Digital Differential Manometer Electronic piezoresistive pressure transducer sensing differential pressure Paired with pitot tubes, flow hoods, or static probes; reads down to 0.001 in. w.g. 0.001\text{ in. w.g.} 0.001 in. w.g. Must be zero-calibrated (auto-zeroed) prior to each traverse reading

Rotating Vane Anemometer Mechanical rotating impeller whose rotational speed is calibrated to air velocity Coil face velocity, large filter banks, kitchen hood face openings ( 200 − 3 , 000 FPM 200-3,000\text{ FPM} 200 − 3 , 000 FPM ) Large physical head (3" or 4" diameter) averages velocity; cannot fit into small duct taps

Thermal (Hot-Wire) Anemometer Micro-heated wire or bead element cooled by air convection; electrical resistance correlates to speed Extremely accurate at low velocities ( 20 − 1 , 000 FPM 20 - 1,000\text{ FPM} 20 − 1 , 000 FPM ); VAV box minimum stops Fragile sensor; highly susceptible to physical breakage or calibration drift from airborne dust

Direct-Reading Capture Hood Fabric capture skirt channeling terminal airflow across an averaging flow manifold Rapid, non-destructive volumetric (CFM) measurement of supply diffusers and return grilles Creates backpressure resistance on high-velocity diffusers; requires backpressure correction

Pitot Tube Duct Traverse Standards (Log-Tchebycheff vs. Equal Area)

Because air velocity is not uniform across a duct profile—boundary layer friction causes air to drag against duct walls while traveling fastest in the center—measuring a single centerline point will overestimate airflow by 10 % to 20 % 10\%\text{ to }20\% 10% to 20% . To determine true average velocity, technicians must perform a multi-point duct traverse in accordance with ASHRAE Standard 111 and SMACNA TAB procedural standards.

Straight-Run Clearance Rules : To ensure a laminar, non-turbulent velocity profile, the traverse must be performed in a straight section of duct located at least 7.5 duct diameters 7.5\text{ duct diameters} 7.5 duct diameters downstream from any upstream disturbance (elbow, fan discharge, transition, or damper) and at least 2.5 duct diameters 2.5\text{ duct diameters} 2.5 duct diameters upstream from any downstream obstruction.

Traverse Methodology : In rectangular ducts, the cross-section is divided into an array of identical rectangular sub-areas (minimum 16 to 25 test points ). In round ducts, measurements are taken across two perpendicular diameters using either the Log-Tchebycheff rule (which concentrates measurement points closer to duct walls where velocity gradients are steepest) or the Equal Area method (minimum 10 points along each of two diameters , totaling 20 readings).

Warning

The Averaging Trap in TAB Calculations : When calculating average velocity from a multi-point pitot tube traverse, technicians must calculate the velocity for each individual test point first , and then average the resulting velocities! You must NEVER average the velocity pressures ( P v P_v P v ​ ) directly and take the square root of that average. Because velocity is proportional to the square root of velocity pressure ( V ∝ P v V \propto \sqrt{P_v} V ∝ P v ​ ​ ), averaging pressures directly introduces significant mathematical error: Correct: V avg = V 1 + V 2 + V 3 + ⋯ + V n n = 4005 P v 1 + 4005 P v 2 + ⋯ + 4005 P v n n \text{Correct: } V_{\text{avg}} = \frac{V_1 + V_2 + V_3 + \dots + V_n}{n} = \frac{4005\sqrt{P_{v1}} + 4005\sqrt{P_{v2}} + \dots + 4005\sqrt{P_{vn}}}{n} Correct: V avg ​ = n V 1 ​ + V 2 ​ + V 3 ​ + ⋯ + V n ​ ​ = n 4005 P v 1 ​ ​ + 4005 P v 2 ​ ​ + ⋯ + 4005 P v n ​ ​ ​ INCORRECT: V avg ≠ 4005 × P v 1 + P v 2 + ⋯ + P v n n \text{INCORRECT: } V_{\text{avg}} \neq 4005 \times \sqrt{\frac{P_{v1} + P_{v2} + \dots + P_{vn}}{n}} INCORRECT: V avg ​  = 4005 × n P v 1 ​ + P v 2 ​ + ⋯ + P v n ​ ​ ​

The Fan Affinity Laws

The Fan Affinity Laws (governed by AMCA Standard 210) describe the exact physical relationships between fan rotational speed ( R P M RPM RPM ), volumetric airflow rate ( C F M CFM CFM ), static pressure ( S P SP SP ), and brake horsepower ( B H P BHP B H P ). In field balancing, these laws allow technicians to predict the exact operational consequences of changing fan motor sheaves, pulley pitch diameters, or Variable Frequency Drive (VFD) inverter speeds.

Law 1: Airflow vs. Rotational Speed (Linear Relationship)

Volumetric airflow capacity varies directly and linearly with fan rotational speed: CFM 2 CFM 1 = RPM 2 RPM 1 ⟹ CFM 2 = CFM 1 × ( RPM 2 RPM 1 ) \frac{\text{CFM}_2}{\text{CFM}_1} = \frac{\text{RPM}_2}{\text{RPM}_1} \quad \implies \quad \text{CFM}_2 = \text{CFM}_1 \times \left( \frac{\text{RPM}_2}{\text{RPM}_1} \right) CFM 1 ​ CFM 2 ​ ​ = RPM 1 ​ RPM 2 ​ ​ ⟹ CFM 2 ​ = CFM 1 ​ × ( RPM 1 ​ RPM 2 ​ ​ )

Practical Example : If an air handler operates at 800 RPM 800\text{ RPM} 800 RPM and delivers 4 , 000 CFM 4,000\text{ CFM} 4 , 000 CFM , increasing the fan speed by 10 % 10\% 10% to 880 RPM 880\text{ RPM} 880 RPM increases airflow by exactly 10 % 10\% 10% to 4 , 400 CFM 4,400\text{ CFM} 4 , 400 CFM .

Law 2: Static Pressure vs. Rotational Speed (Square Relationship)

System static pressure (or total pressure) varies directly with the square of fan rotational speed: SP 2 SP 1 = ( RPM 2 RPM 1 ) 2 ⟹ SP 2 = SP 1 × ( RPM 2 RPM 1 ) 2 \frac{\text{SP}_2}{\text{SP}_1} = \left( \frac{\text{RPM}_2}{\text{RPM}_1} \right)^2 \quad \implies \quad \text{SP}_2 = \text{SP}_1 \times \left( \frac{\text{RPM}_2}{\text{RPM}_1} \right)^2 SP 1 ​ SP 2 ​ ​ = ( RPM 1 ​ RPM 2 ​ ​ ) 2 ⟹ SP 2 ​ = SP 1 ​ × ( RPM 1 ​ RPM 2 ​ ​ ) 2

Practical Example : Using the same fan, if the initial static pressure is 1.0 in. w.g. 1.0\text{ in. w.g.} 1.0 in. w.g. at 800 RPM 800\text{ RPM} 800 RPM , increasing the speed to 880 RPM 880\text{ RPM} 880 RPM ( 1.10 × 1.10\times 1.10 × speed) increases static pressure by 1.10 2 = 1.21 × 1.10^2 = 1.21\times 1.1 0 2 = 1.21 × , raising system static pressure to 1.21 in. w.g. 1.21\text{ in. w.g.} 1.21 in. w.g.

Law 3: Brake Horsepower vs. Rotational Speed (Cubic Relationship)

The mechanical power required to drive the fan impeller (brake horsepower, B H P BHP B H P ) varies directly with the cube of fan rotational speed: BHP 2 BHP 1 = ( RPM 2 RPM 1 ) 3 ⟹ BHP 2 = BHP 1 × ( RPM 2 RPM 1 ) 3 \frac{\text{BHP}_2}{\text{BHP}_1} = \left( \frac{\text{RPM}_2}{\text{RPM}_1} \right)^3 \quad \implies \quad \text{BHP}_2 = \text{BHP}_1 \times \left( \frac{\text{RPM}_2}{\text{RPM}_1} \right)^3 BHP 1 ​ BHP 2 ​ ​ = ( RPM 1 ​ RPM 2 ​ ​ ) 3 ⟹ BHP 2 ​ = BHP 1 ​ × ( RPM 1 ​ RPM 2 ​ ​ ) 3

Caution

The Motor Overload Hazard (Affinity Law 3) : Because power demand increases with the cube of speed ( R P M 3 RPM^3 RP M 3 ), small adjustments in fan speed require massive increases in motor power! If a technician speeds up a fan by 25 % 25\% 25% ( R P M 2 / R P M 1 = 1.25 RPM_2 / RPM_1 = 1.25 RP M 2 ​ / RP M 1 ​ = 1.25 ) to overcome an airflow shortfall, the motor power requirement increases by: 1.25 3 = 1.953 ( a 95.3 % increase in power! ) 1.25^3 = 1.953 \quad (\text{a } 95.3\% \text{ increase in power!}) 1.2 5 3 = 1.953 ( a 95.3% increase in power! ) A 5-horsepower motor will suddenly be subjected to a 9.77 BHP load, causing thermal overload trips, nuisance breaker clearing, and burned stator windings. Technicians must always check motor running amperage with a clamp-on ammeter against the motor nameplate Full Load Amps (FLA) whenever speeding up a blower.

Sheave and Pulley Sizing Equation

In belt-driven air handling systems, fan rotational speed is modified by adjusting the pitch diameter of variable-pitch motor sheaves or replacing fixed pulleys according to the inverse diameter ratio: RPM fan × D fan = RPM motor × D motor \text{RPM}_{\text{fan}} \times D_{\text{fan}} = \text{RPM}_{\text{motor}} \times D_{\text{motor}} RPM fan ​ × D fan ​ = RPM motor ​ × D motor ​

Where:

RPM fan \text{RPM}_{\text{fan}} RPM fan ​ and RPM motor \text{RPM}_{\text{motor}} RPM motor ​ = Rotational speeds of fan shaft and motor shaft

  • D fan D_{\text{fan}} D fan ​ = Pitch diameter of the fan pulley (inches)
  • D motor D_{\text{motor}} D motor ​ = Pitch diameter of the motor drive sheave (inches)
  • Proportional Balancing Methodology

Balancing an air distribution system is an orderly, systematic engineering sequence. Attempting to balance terminal outlets randomly by adjusting dampers back and forth results in "hunting" and infinite loops, because throttling a damper at one outlet immediately diverts air to downstream branches. Main Air Handler

  • │
  • ▼
  • Main Supply Duct (VFD / Total System Trimming)
  • │
  • ├───────────────────────────────┬───────────────────────────────┐
  • ▼ ▼ ▼
  • Branch Damper A Branch Damper B Branch Damper C
  • │ │ │
  • ┌──┴──┐ ┌──┴──┐ ┌──┴──┐
  • ▼ ▼ ▼ ▼ ▼ ▼
  • Diff 1 Diff 2 Diff 3 Diff 4 Diff 5 Diff 6
  • (115%) (110%) (105%) (98%) (92%) (78%)
  • ▲
  • │
  • INDEX TERMINAL
  • (Lowest % Flow)
  • LEAVE DAMPER 100% OPEN
  • Step 1: Pre-Balancing System Audit

Prior to placing any instrument on a terminal diffuser, the TAB technician must verify mechanical operating readiness:

Verify all construction debris has been vacuumed from ductwork.

Ensure clean, specified air filters are installed in all filter racks.

Verify that all fire dampers, smoke dampers, and manual balancing dampers are locked in the 100 % 100\% 100% wide-open position .

Confirm correct motor rotation (centrifugal forward-curved blowers will still move roughly 50 % 50\% 50% of design airflow when spinning backward, while drawing low motor amps).

Inspect drive belt tension, pulley alignment, and bearing lubrication.

Step 2: Initial System Scan and Index Terminal Identification

Measure total airflow across the main supply fan using a pitot tube traverse.

Conduct an initial pass across every supply diffuser using a calibrated flow hood, recording the initial measured CFM against the design CFM.

Calculate the Percentage of Design Flow for every terminal: % Design Flow = ( Measured CFM Design CFM ) × 100 % \% \text{ Design Flow} = \left( \frac{\text{Measured CFM}}{\text{Design CFM}} \right) \times 100\% % Design Flow = ( Design CFM Measured CFM ​ ) × 100%

Identify the Index Terminal : The index terminal is the terminal or branch that exhibits the lowest percentage of design flow in the entire system. Typically, this is the hydraulically most remote outlet located at the end of the longest, most restrictive duct run.

Step 3: Proportional Trimming

The damper on the Index Terminal must remain 100 % 100\% 100% wide open throughout the balancing procedure. It must never be throttled.

Work upstream toward the fan, beginning with the terminal adjacent to the index outlet. Measure the ratio of airflow between that terminal and the index terminal.

Slowly throttle the upstream damper until its percentage of design flow matches the percentage of design flow at the index terminal. As you choke down the upstream damper, air is forced backward through the system into the index branch, increasing the index terminal's flow.

Repeat this proportional procedure for every terminal on the branch, then balance branch dampers against each other, always maintaining the most restricted branch damper wide open.

Step 4: Final Fan Trimming to 100 % 100\% 100%

Once all terminal outlets are balanced proportionally to one another (e.g., all outlets deliver between 78 % 78\% 78% and 82 % 82\% 82% of their design flow), the entire system is in hydraulic proportion. The technician completes the process by:

Speeding up the supply fan motor via the Variable Frequency Drive (VFD) or adjusting the motor drive sheave to bring total system airflow up to 100 % of design CFM 100\%\text{ of design CFM} 100% of design CFM .

Because all dampers were balanced proportionally, increasing the main fan speed lifts every terminal outlet simultaneously to 100 % of design CFM ( ± 10 % ) 100\%\text{ of design CFM} (\pm 10\%) 100% of design CFM ( ± 10% ) without requiring further terminal damper adjustments.

  • Step-by-Step Worked Engineering Calculations
  • Calculation 1: Pitot Tube Duct Traverse Average Velocity and Airflow

Problem : A balancing technician performs a 4-point sample pitot tube traverse in an 18 " × 12 " 18" \times 12" 18" × 12" rectangular supply trunk. The differential manometer records the following velocity pressures ( P v P_v P v ​ ):

Point 1: P v 1 = 0.16 in. w.g. P_{v1} = 0.16\text{ in. w.g.} P v 1 ​ = 0.16 in. w.g.

Point 2: P v 2 = 0.25 in. w.g. P_{v2} = 0.25\text{ in. w.g.} P v 2 ​ = 0.25 in. w.g.

Point 3: P v 3 = 0.36 in. w.g. P_{v3} = 0.36\text{ in. w.g.} P v 3 ​ = 0.36 in. w.g.

Point 4: P v 4 = 0.09 in. w.g. P_{v4} = 0.09\text{ in. w.g.} P v 4 ​ = 0.09 in. w.g.

Calculate the true average duct velocity in FPM and the total volumetric airflow rate in CFM.

Step 1: Calculate velocity at each individual traverse point ( V = 4005 P v V = 4005 \sqrt{P_v} V = 4005 P v ​ ​ )

V 1 = 4005 × 0.16 = 4005 × 0.40 = 1 , 602 FPM V_1 = 4005 \times \sqrt{0.16} = 4005 \times 0.40 = 1,602\text{ FPM} V 1 ​ = 4005 × 0.16 ​ = 4005 × 0.40 = 1 , 602 FPM

V 2 = 4005 × 0.25 = 4005 × 0.50 = 2 , 002.5 FPM V_2 = 4005 \times \sqrt{0.25} = 4005 \times 0.50 = 2,002.5\text{ FPM} V 2 ​ = 4005 × 0.25 ​ = 4005 × 0.50 = 2 , 002.5 FPM

V 3 = 4005 × 0.36 = 4005 × 0.60 = 2 , 403 FPM V_3 = 4005 \times \sqrt{0.36} = 4005 \times 0.60 = 2,403\text{ FPM} V 3 ​ = 4005 × 0.36 ​ = 4005 × 0.60 = 2 , 403 FPM

V 4 = 4005 × 0.09 = 4005 × 0.30 = 1 , 201.5 FPM V_4 = 4005 \times \sqrt{0.09} = 4005 \times 0.30 = 1,201.5\text{ FPM} V 4 ​ = 4005 × 0.09 ​ = 4005 × 0.30 = 1 , 201.5 FPM

Step 2: Calculate the true average air velocity ( V avg V_{\text{avg}} V avg ​ ) V avg = 1 , 602 + 2 , 002.5 + 2 , 403 + 1 , 201.5 4 = 7 , 209 4 = 1 , 802.25 FPM V_{\text{avg}} = \frac{1,602 + 2,002.5 + 2,403 + 1,201.5}{4} = \frac{7,209}{4} = 1,802.25\text{ FPM} V avg ​ = 4 1 , 602 + 2 , 002.5 + 2 , 403 + 1 , 201.5 ​ = 4 7 , 209 ​ = 1 , 802.25 FPM

Step 3: Calculate duct cross-sectional area in square feet Area = 18 " × 12 " 144 in. 2 / ft 2 = 216 144 = 1.50 ft 2 \text{Area} = \frac{18" \times 12"}{144\text{ in.}^2/\text{ft}^2} = \frac{216}{144} = 1.50\text{ ft}^2 Area = 144 in. 2 / ft 2 18" × 12" ​ = 144 216 ​ = 1.50 ft 2

Step 4: Calculate volumetric airflow (CFM = Area × Average Velocity) CFM = 1.50 ft 2 × 1 , 802.25 FPM = 2 , 703.4 CFM \text{CFM} = 1.50\text{ ft}^2 \times 1,802.25\text{ FPM} = 2,703.4\text{ CFM} CFM = 1.50 ft 2 × 1 , 802.25 FPM = 2 , 703.4 CFM

Result : The duct airflow is 2 , 703 CFM 2,703\text{ CFM} 2 , 703 CFM at an average velocity of 1 , 802 FPM 1,802\text{ FPM} 1 , 802 FPM .

Calculation 2: Applying Fan Affinity Laws to Correct an Airflow Deficit

Problem : A rooftop packaged air handling unit operates at 900 RPM 900\text{ RPM} 900 RPM , delivering 3 , 600 CFM 3,600\text{ CFM} 3 , 600 CFM against an external static pressure of 1.20 in. w.g. 1.20\text{ in. w.g.} 1.20 in. w.g. The fan motor currently draws 4.2 BHP 4.2\text{ BHP} 4.2 BHP (on a 5.0 HP motor). Design specifications call for 4 , 200 CFM 4,200\text{ CFM} 4 , 200 CFM . Calculate the required fan RPM, the new static pressure, and the new motor brake horsepower.

Step 1: Calculate new fan speed using Affinity Law 1 RPM 2 = RPM 1 × ( CFM 2 CFM 1 ) = 900 × ( 4 , 200 3 , 600 ) = 900 × 1.1667 = 1 , 050 RPM \text{RPM}_2 = \text{RPM}_1 \times \left( \frac{\text{CFM}_2}{\text{CFM}_1} \right) = 900 \times \left( \frac{4,200}{3,600} \right) = 900 \times 1.1667 = 1,050\text{ RPM} RPM 2 ​ = RPM 1 ​ × ( CFM 1 ​ CFM 2 ​ ​ ) = 900 × ( 3 , 600 4 , 200 ​ ) = 900 × 1.1667 = 1 , 050 RPM

Step 2: Calculate new static pressure using Affinity Law 2 SP 2 = SP 1 × ( RPM 2 RPM 1 ) 2 = 1.20 × ( 1.1667 ) 2 = 1.20 × 1.3611 = 1.633 in. w.g. \text{SP}_2 = \text{SP}_1 \times \left( \frac{\text{RPM}_2}{\text{RPM}_1} \right)^2 = 1.20 \times (1.1667)^2 = 1.20 \times 1.3611 = 1.633\text{ in. w.g.} SP 2 ​ = SP 1 ​ × ( RPM 1 ​ RPM 2 ​ ​ ) 2 = 1.20 × ( 1.1667 ) 2 = 1.20 × 1.3611 = 1.633 in. w.g.

Step 3: Calculate new brake horsepower using Affinity Law 3 BHP 2 = BHP 1 × ( RPM 2 RPM 1 ) 3 = 4.2 × ( 1.1667 ) 3 = 4.2 × 1.5879 = 6.67 BHP \text{BHP}_2 = \text{BHP}_1 \times \left( \frac{\text{RPM}_2}{\text{RPM}_1} \right)^3 = 4.2 \times (1.1667)^3 = 4.2 \times 1.5879 = 6.67\text{ BHP} BHP 2 ​ = BHP 1 ​ × ( RPM 1 ​ RPM 2 ​ ​ ) 3 = 4.2 × ( 1.1667 ) 3 = 4.2 × 1.5879 = 6.67 BHP

Critical Engineering Evaluation : While the fan can physically reach 1 , 050 RPM 1,050\text{ RPM} 1 , 050 RPM to deliver 4 , 200 CFM 4,200\text{ CFM} 4 , 200 CFM , the new power requirement is 6.67 BHP 6.67\text{ BHP} 6.67 BHP . Because the installed motor is rated at only 5.0 HP 5.0\text{ HP} 5.0 HP , operating at this speed will overload and burn out the motor. The contractor cannot simply change sheaves—they must upgrade the motor to a 7.5 HP 7.5\text{ HP} 7.5 HP model and resize branch electrical conductors and OCPDs.

Common Exam Traps & Regulatory Distinctions

Exam Trap: Static Pressure Sign Conventions : Supply static pressure is positive; return static pressure is negative. However, velocity pressure is always positive ( P v > 0 P_v > 0 P v ​ > 0 ). If a test question displays a negative velocity pressure, it indicates a reversed hose connection on the manometer.

Exam Trap: Straight Duct Run Traverse Distances : The licensing exam frequently asks for the minimum upstream and downstream distances required for an accurate pitot tube traverse. Memorize the ratio: 7.5 duct diameters 7.5\text{ duct diameters} 7.5 duct diameters upstream and 2.5 duct diameters 2.5\text{ duct diameters} 2.5 duct diameters downstream from any disturbance.

Exam Trap: The Cubic Exponent on Fan Power : Questions asking for new motor horsepower when fan speed increases are common. Remember that horsepower scales with the cube of speed ratio: ( R P M 2 / R P M 1 ) 3 (RPM_2 / RPM_1)^3 ( RP M 2 ​ / RP M 1 ​ ) 3 , not linearly or squared.

Exam Trap: Index Terminal Damper Position : During proportional balancing, what is the correct damper setting for the index terminal? It is always 100 % 100\% 100% wide open . Throttling the index terminal damper invalidates the entire proportional balance.

Loading diagram... Pitot-Static Tube Pressure Sensing and Log-Tchebycheff Duct Traverse Grid