Study guide

4.1 ACCA Manual D Airflow Fundamentals & External Static Pressure

Arkansas HVAC/R Contractor License Exam

Track your progress as you read

Finished sections get a check mark.

1 Arkansas HVAC/R Licensing Law, Board Rules & Administration

1.1 Arkansas HVAC/R Board Authority, Statutes & Definitions 1.2 License Classifications & Capacity Limitations 1.3 Registrant Requirements, Apprenticeship & Experience Verification 1.4 License Renewal, Continuing Education & Disciplinary Actions

2 HVAC Thermodynamics, Psychrometrics & Gas Laws

2.1 Principles of Heat Transfer & Thermodynamic Fundamentals 2.2 Psychrometric Chart Dynamics & Air Properties 2.3 Psychrometric Processes & Air Mixture Calculations 2.4 Gas Laws Applied to HVAC/R Systems

3 Heating and Cooling Load Calculations (Manual J & S)

3.1 ACCA Manual J Design Conditions & Thermal Envelopes 3.2 Peak Cooling Load Calculations: Sensible vs. Latent Heat Gain 3.3 Heating Load Calculations & Infiltration Rates 3.4 ACCA Manual S Equipment Selection & Verification

4 Ductwork Design, Sizing & SMACNA Standards (Manual D)

4.1 ACCA Manual D Airflow Fundamentals & External Static Pressure 4.2 Equal Friction & Static Regain Duct Sizing Methods 4.3 Duct Fittings, Equivalent Length & Dynamic Losses 4.4 SMACNA Duct Construction Standards & Joint Sealing

5 Air Distribution, Balancing & Ventilation Codes

5.1 Supply & Return Air Distribution Hardware (Grilles, Registers, Diffusers) 5.2 System Airflow Testing, Adjusting & Balancing (TAB) 5.3 Ventilation Standards: ASHRAE 62.1, 62.2 & 2021 IMC Ventilation Air

6 Mechanical Refrigeration Cycle & Components

6.1 The Vapor-Compression Refrigeration Cycle 6.2 Compressors & Operating Characteristics 6.3 Condensers & Evaporators 6.4 Metering Devices & Refrigerant Flow Controls 6.5 Refrigerant Line Sizing, Oil Return & Field Piping Practices

7 Refrigerants, Oils & EPA Section 608 Regulations

7.1 Refrigerant Chemistry, ASHRAE Standard 34 & A2L Transition 7.2 Lubricating Oils & System Compatibility 7.3 EPA Section 608 Regulatory Mandates & Recovery Standards 7.4 System Evacuation, Dehydration & Leak Detection

8 Air Conditioning & Heat Pump Systems

8.1 Residential & Commercial Split Systems and Package RTUs 8.2 Air-Source Heat Pumps & The Reversing Valve 8.3 Supplemental & Emergency Heating Systems 8.4 Dual-Fuel & Geothermal (Ground-Source) Heat Pump Systems

9 Gas Furnaces, Combustion Air & Venting (IFGC / IMC)

9.1 Gas Furnace Types, AFUE Ratings & Sequence of Operation 9.2 Gas Burners, Ignition Systems & Flame Safeguard Controls 9.3 Combustion Air Requirements (IFGC Chapter 3 / IMC Chapter 7) 9.4 Flue Gas Venting & Category I-IV Venting Systems

10 Boilers, Hydronics & Fuel Gas Piping

10.1 Hydronic Heating Systems, Low-Pressure Boilers & ASME Code 10.2 Hydronic Distribution, Circulator Pumps & Piping Loops 10.3 Fuel Gas Piping Materials, Sizing & Pressure Testing (IFGC Chapter 4) 10.4 Gas Regulators, Manifold Pressure & Gas Meter Sizing 10.5 Condensate Disposal, Piping Support & Mechanical Insulation

11 Electrical Fundamentals, Motors & Control Circuits

11.1 HVAC Electrical Fundamentals, Ohm's Law & Power Calculations 11.2 Single-Phase & Three-Phase Electric Motors in HVAC 11.3 Low-Voltage Control Circuits & Thermostats

12 National Electrical Code (NEC) for HVAC Equipment

12.1 NEC Article 440: Hermetic Refrigerant Motor-Compressors & Branch Circuits 12.2 Equipment Disconnecting Means & Overcurrent Protective Devices (OCPD) 12.3 Motor Branch Circuit Sizing & Conductor Ampacity (NEC Article 430 & Tables)

13 System Maintenance, Troubleshooting & Safety Standards

13.1 Systematic Mechanical & Electrical Troubleshooting 13.2 Airflow & Refrigerant Charge Diagnostics 13.3 Jobsite Safety, OSHA Standards & Personal Protective Equipment

14 Plan Reading, Estimating & HVAC/R Trade Math

14.1 Mechanical Plan Symbols, Schedules & Abbreviations 14.2 Architectural Scales, Dimensions & Quantity Takeoff 14.3 Material, Labor & Bid Estimating 14.4 Applied HVAC/R Trade Math & Unit Conversions

4.1 ACCA Manual D Airflow Fundamentals & External Static Pressure

Key Takeaways Explain This Topic AI

ACCA Manual D establishes the nationwide engineering standard for sizing residential and light-commercial duct systems to deliver designated room-by-room CFM without excessive noise, velocity turbulence, or parasitic static pressure.

Total External Static Pressure (TESP) represents the net resistance that the air handler or furnace blower must overcome outside of its internal cabinet, calculated as the absolute sum of supply static pressure and return static pressure (|SP_supply| + |SP_return|).

Available Static Pressure (ASP) is the remaining pressure head dedicated solely to duct friction and fittings, calculated by subtracting all external component pressure drops (cased evaporator coil, air filters, heat strips, registers, grilles, and balancing dampers) from the rated TESP.

Forward-curved centrifugal blowers with permanent split capacitor (PSC) motors suffer severe airflow decay as static pressure rises, whereas electronically commutated motors (ECM) ramp up motor speed and power consumption to maintain constant CFM, generating higher duct pressures and acoustic noise if undersized.

Standard residential systems are engineered for approximately 400 CFM per nominal ton of cooling (ranging from 350 CFM/ton in humid Arkansas conditions for enhanced dehumidification up to 450 CFM/ton for high-sensible heat applications).

Last updated: September 2026

4.1 ACCA Manual D Airflow Fundamentals & External Static Pressure

Note

Code Mandate & Regulatory Foundation : Under the 2021 International Mechanical Code (IMC Section 603), the 2021 International Residential Code (IRC Section M1601), and Arkansas Mechanical Rules, all residential duct distribution systems must be designed, sized, and installed in strict compliance with ACCA Manual D (Residential Duct Systems). Installing arbitrary duct sizes based on "rules of thumb" (such as assuming a 6-inch flex runout always supplies 100 CFM) violates state building codes and frequently leads to chronic airflow starvation, excessive blower energy consumption, equipment limit tripping, and severe comfort complaints.

Ductwork functions as the vascular distribution network of any forced-air heating and cooling system. The finest high-efficiency variable-speed heat pump or condensing gas furnace cannot achieve its rated SEER2, HSPF2, or AFUE efficiency if the connected air distribution system is restricted, imbalanced, or poorly routed. ACCA Manual D provides the rigorous fluid dynamic equations required to ensure that the exact room-by-room CFM determined in ACCA Manual J is delivered to each conditioned space against the real-world pressure limitations of the selected air mover.

Fluid Dynamics of Duct Airstreams: Total, Static, and Velocity Pressures

Air flowing through an enclosed duct system possesses energy in two distinct physical states: potential energy (manifested as outward compressive pressure against the duct walls) and kinetic energy (manifested as forward directional momentum). In HVAC aerodynamics, these pressures are universally measured in inches of water column (in. w.g.) , where 1.0 inch of water column equals approximately 0.0361 pounds per square inch (psi) or 249.1 Pascals (Pa) . +-------------------------------------------------------------------------+

  • | BERNOULLI'S EQUATION IN HVAC AIRFLOW |
  • +-------------------------------------------------------------------------+
  • | |
  • | TOTAL PRESSURE (TP) = STATIC PRESSURE (SP) + VELOCITY PRESSURE (VP) |
  • | |
  • | * Static Pressure (SP): Potential energy pushing equally in all |
  • | directions against the internal duct walls (positive or negative). |
  • | |
  • | * Velocity Pressure (VP): Kinetic energy created by the speed and mass |
  • | of moving air in the direction of flow (always positive). |
  • | |
  • | * Total Pressure (TP): The algebraic sum of static and velocity |
  • | pressures; always decreases in the direction of airflow due to |
  • | frictional and dynamic turbulence losses. |
  • +-------------------------------------------------------------------------+
  • 1. Static Pressure (SP)

Static pressure is the compressive or bursting force exerted uniformly perpendicular to the duct walls. In a forced-air system:

Supply Ductwork : Operates under positive static pressure relative to the surrounding atmospheric room pressure because the blower pushes air outward through the supply plenum and branch runouts.

Return Ductwork : Operates under negative static pressure (suction/vacuum) relative to the ambient space because the blower fan inlet draws air inward from return grilles toward the equipment cabinet.

2. Velocity Pressure (VP)

Velocity pressure is the directional dynamic pressure generated by the motion of the air molecules. Unlike static pressure, velocity pressure cannot be measured perpendicularly; it must be measured facing directly into the oncoming airstream using an impact tube or the total-pressure port of a pitot tube. Velocity pressure is always positive and is mathematically coupled to air velocity ( V V V , in feet per minute) under standard air density conditions ( 0.075 lb/ft 3 0.075 \text{ lb/ft}^3 0.075 lb/ft 3 at 70°F and 29.92 in. Hg): V = 4 , 005 × V P V = 4,005 \times \sqrt{VP} V = 4 , 005 × V P ​ V P = ( V 4 , 005 ) 2 VP = \left(\frac{V}{4,005}\right)^2 V P = ( 4 , 005 V ​ ) 2

Where:

  • V V V = Air velocity in feet per minute (FPM)
  • V P VP V P = Velocity pressure in inches of water column (in. w.g.)
  • 4 , 005 4,005 4 , 005 = Aerodynamic constant for standard dry air

For example, air traveling through a main supply trunk at 800 FPM generates a velocity pressure of: V P = ( 800 4 , 005 ) 2 = ( 0.1997 ) 2 ≈ 0.040 in. w.g. VP = \left(\frac{800}{4,005}\right)^2 = (0.1997)^2 \approx 0.040 \text{ in. w.g.} V P = ( 4 , 005 800 ​ ) 2 = ( 0.1997 ) 2 ≈ 0.040 in. w.g.

If the velocity increases to 1,200 FPM , velocity pressure more than doubles to: V P = ( 1 , 200 4 , 005 ) 2 = ( 0.2996 ) 2 ≈ 0.090 in. w.g. VP = \left(\frac{1,200}{4,005}\right)^2 = (0.2996)^2 \approx 0.090 \text{ in. w.g.} V P = ( 4 , 005 1 , 200 ​ ) 2 = ( 0.2996 ) 2 ≈ 0.090 in. w.g.

3. Total Pressure (TP)

Total pressure represents the total fluid energy content of the airstream ( T P = S P + V P TP = SP + VP TP = SP + V P ). According to the Second Law of Thermodynamics, energy dissipates as air encounters wall friction, elbows, tees, and transitions. Therefore, Total Pressure strictly decreases in the direction of airflow from the blower discharge to the terminal diffuser , and from the return intake to the blower inlet.

The Continuity Equation and Airflow Rate

The fundamental law of conservation of mass dictates that for incompressible fluid flow (subsonic air below 2,000 FPM), the volumetric flow rate ( Q Q Q , in CFM) must remain constant across any cross-section of an unbranched, sealed duct: Q = A × V Q = A \times V Q = A × V

Where:

  • Q Q Q = Volumetric airflow rate in cubic feet per minute (CFM)
  • A A A = Cross-sectional interior area of the duct in square feet (ft²)
  • V V V = Average air velocity across the cross-section in feet per minute (FPM)
  • Rectangular and Round Area Formulations

For a rectangular duct with width W W W (inches) and height H H H (inches): A = W × H 144 (ft 2 ) A = \frac{W \times H}{144} \quad \text{(ft}^2\text{)} A = 144 W × H ​ (ft 2 )

For a round spiral or rigid duct with inside diameter D D D (inches): A = π × D 2 4 × 144 = π × D 2 576 ≈ D 2 183.35 (ft 2 ) A = \frac{\pi \times D^2}{4 \times 144} = \frac{\pi \times D^2}{576} \approx \frac{D^2}{183.35} \quad \text{(ft}^2\text{)} A = 4 × 144 π × D 2 ​ = 576 π × D 2 ​ ≈ 183.35 D 2 ​ (ft 2 )

Tip

Field Conversion Example : If an 8-inch diameter round branch duct carries 180 CFM of conditioned air, its cross-sectional area is A = π × ( 8 ) 2 / 576 = 201.06 / 576 = 0.349 ft 2 A = \pi \times (8)^2 / 576 = 201.06 / 576 = 0.349 \text{ ft}^2 A = π × ( 8 ) 2 /576 = 201.06/576 = 0.349 ft 2 . The resulting air velocity is V = Q / A = 180 / 0.349 = 516 FPM V = Q / A = 180 / 0.349 = 516 \text{ FPM} V = Q / A = 180/0.349 = 516 FPM , which satisfies residential comfort noise thresholds.

Total External Static Pressure (TESP)

Total External Static Pressure (TESP) is the benchmark metric of fan capacity and ductwork resistance. It represents the total pressure differential that the supply air fan must overcome to move the design airflow through the external air distribution circuit. +-------------------------------------------------------------------------+

  • | TOTAL EXTERNAL STATIC PRESSURE (TESP) TEST HOLE LOCATIONS |
  • +-------------------------------------------------------------------------+
  • | |
  • | [RETURN DUCT] ---> [FILTER] ---> [BLOWER / FURNACE] ---> [SUPPLY PLENUM]
  • | | | | |
  • | | P1 (Before Filter) P3 (Between Blower & Coil) |
  • | | | |
  • | v v v
  • | P0 (Return Boot) P2 (Entering Cabinet) P4 (True Supply)
  • | |
  • | * Gas Furnace / Modular Blower (External Cased Coil): |
  • | TESP = |P2 (Cabinet Return Inlet)| + |P3 (Before Evaporator Coil)| |
  • | |
  • | * Integrated Air Handler (Internal Factory Coil & Filter Rack): |
  • | TESP = |P1 (Entering Filter/Cabinet)| + |P4 (Leaving Supply Plenum)||
  • +-------------------------------------------------------------------------+
  • Measuring TESP in the Field

When testing static pressure using a digital dual-port manometer with static pressure probes (pointed against the direction of airflow):

Return Static Pressure probe ( S P return SP_{\text{return}} S P return ​ ) is inserted into the return air duct directly where it attaches to the furnace or air handler cabinet (downstream of the air filter if the filter is external to the equipment).

Supply Static Pressure probe ( S P supply SP_{\text{supply}} S P supply ​ ) is inserted into the supply plenum:

On a furnace with an add-on cased evaporator coil , the probe is placed in the transition duct between the furnace discharge and the bottom of the cooling coil . This isolates the furnace blower's external static pressure rating, treating the cased coil as an external accessory device.

On a factory air handler (where the fan, electric heat, and cooling coil are integrated inside a single factory-sealed casing), the probe is placed in the supply plenum after the coil and electric heat elements , approximately 6 to 12 inches above the cabinet collar.

Mathematical Formulation

Because return static pressure is negative and supply static pressure is positive, TESP is the absolute sum of the two static pressure magnitudes: TESP = ∣ S P supply ∣ + ∣ S P return ∣ \text{TESP} = |SP_{\text{supply}}| + |SP_{\text{return}}| TESP = ∣ S P supply ​ ∣ + ∣ S P return ​ ∣

For example, if a digital manometer registers a supply static pressure of +0.28 in. w.g. and a return static pressure of -0.24 in. w.g. : TESP = ∣ + 0.28 ∣ + ∣ − 0.24 ∣ = 0.28 + 0.24 = 0.52 in. w.g. \text{TESP} = |+0.28| + |-0.24| = 0.28 + 0.24 = 0.52 \text{ in. w.g.} TESP = ∣ + 0.28∣ + ∣ − 0.24∣ = 0.28 + 0.24 = 0.52 in. w.g.

If the technician inadvertently subtracts the two values without considering sign, they arrive at an erroneous 0.04 in. w.g. 0.04 \text{ in. w.g.} 0.04 in. w.g. , masking a potentially severe restriction.

Fan Performance Curves: PSC vs. ECM Blowers

Equipment manufacturers publish blower performance tables in their technical specification sheets, illustrating the volume of air (CFM) delivered across various speed taps at specific external static pressures.

Blower Motor Technology Reaction to Elevated Static Pressure Airflow (CFM) Impact Electrical Power (Watts) Impact Acoustic Profile

PSC (Permanent Split Capacitor) Fan slips; blades cannot bite into dense air Drops drastically (e.g., drops from 1,200 CFM at 0.5" to 850 CFM at 0.8") Decreases slightly (motor unloads as mass flow drops) Blower runs quieter as CFM drops, but heat exchanger overheats

Constant-Torque ECM (X13 / Endura) Pre-programmed torque curves Drops moderately at elevated static Increases moderately Increases moderately

Constant-CFM ECM (Variable-Speed) Microprocessor senses static rise and increases motor RPM Maintains constant CFM up to rated static cutoff (~0.80" to 1.00" w.g.) Spikes significantly (power can double from 250W to 600W+) Sharp increase in objectionable air velocity hiss and duct vibration

Manufacturer Blower Performance Curve (3-Ton Residential Air Handler)

Consider the certified fan performance table below for a nominal 3-ton (1,200 design CFM) high-efficiency blower unit:

External Static Pressure (in. w.g.) Low Tap (CFM) Med-Low Tap (CFM) Med-High Tap (CFM) High Tap (CFM) Blower Motor Power (Watts)

  • 0.10 980 1,120 1,310 1,480 185 W
  • 0.20 940 1,080 1,270 1,440 220 W
  • 0.30 890 1,040 1,230 1,390 265 W
  • 0.40 840 990 1,180 1,340 315 W
  • 0.50 (AHRI Rated Baseline) 780 940 1,120 1,280 370 W
  • 0.60 710 880 1,060 1,210 430 W
  • 0.70 630 810 980 1,130 490 W
  • 0.80 540 720 890 1,030 560 W
  • 0.90 430 610 780 910 635 W

Notice that if an installation is designed for 1,200 CFM on the High speed tap, but undersized ductwork drives the actual field TESP from the AHRI baseline of 0.50 in. w.g. up to 0.80 in. w.g. , the delivered airflow on a standard PSC motor drops from 1,280 CFM down to 1,030 CFM (a 20% loss). In cooling mode, this causes evaporator coil frosting and liquid refrigerant slugging back to the compressor; in heating mode, it triggers furnace high-temperature limit safety switch lockouts.

Available Static Pressure (ASP)

One of the most critical engineering steps in ACCA Manual D is computing the Available Static Pressure (ASP) . While the equipment blower provides the total external static pressure head (TESP), the ductwork itself does not get to consume all of that pressure. Before air ever enters a supply duct runout or returns through a return grille, a substantial portion of the TESP is consumed by necessary external ancillary components.

Pressure Drops of Component Accessories ( Δ P device {\Delta}P_{\text{device}} Δ P device ​ )

Evaporator Coil (Wet vs. Dry) :

For gas furnaces with external cooling coils, the coil pressure drop must be accounted for.

A clean cooling coil operating dry in heating mode creates approximately 0.12 to 0.18 in. w.g. of resistance.

During cooling operation in Arkansas's humid summers, condensed water clings between the aluminum fins, significantly restricting free air passage. A wet cooling coil exhibits a pressure drop of 0.20 to 0.32 in. w.g. ACCA Manual D mandates sizing for the wet coil condition .

Air Filtration Media :

Standard 1-inch disposable fiberglass filter: 0.05 to 0.10 in. w.g.

1-inch high-efficiency pleated filter (MERV 8 to 11): 0.15 to 0.28 in. w.g.

1-inch ultra-dense allergen filter (MERV 13): 0.30 to 0.45 in. w.g. (Often consumes 60% to 90% of the entire blower capacity by itself!).

4-inch to 5-inch deep-pleated media air cleaner (MERV 11 to 13): 0.10 to 0.15 in. w.g. due to vastly expanded surface media area.

Electric Resistance Supplemental Heat Strip Bank :

Adds 0.04 to 0.10 in. w.g. depending on kilowatt capacity (5 kW to 20 kW) and coil arrangement.

Supply Air Diffusers and Registers :

Engineered supply grilles and registers require 0.03 to 0.05 in. w.g. of static head behind the damper louvers to create the necessary throw velocity and room air mixing pattern.

Return Air Grilles :

Standard stamped face return grilles require 0.02 to 0.04 in. w.g. across the face louvers.

Balancing Dampers and Backdraft Dampers :

Typically contribute 0.02 to 0.05 in. w.g.

The Available Static Pressure (ASP) Formula A S P = TESP − ∑ Δ P components ASP = \text{TESP} - \sum \Delta P_{\text{components}} A SP = TESP − ∑ Δ P components ​ A S P = TESP − ( Δ P coil + Δ P filter + Δ P heat + Δ P supply register + Δ P return grille + Δ P accessories ) ASP = \text{TESP} - (\Delta P_{\text{coil}} + \Delta P_{\text{filter}} + \Delta P_{\text{heat}} + \Delta P_{\text{supply register}} + \Delta P_{\text{return grille}} + \Delta P_{\text{accessories}}) A SP = TESP − ( Δ P coil ​ + Δ P filter ​ + Δ P heat ​ + Δ P supply register ​ + Δ P return grille ​ + Δ P accessories ​ )

Where:

  • A S P ASP A SP = Available Static Pressure for the entire duct system (in. w.g.)
  • TESP \text{TESP} TESP = Total External Static Pressure rating of the blower at design CFM (in. w.g.)

∑ Δ P components \sum \Delta P_{\text{components}} ∑ Δ P components ​ = Sum of all component and accessory static pressure drops

Important

The Available Static Pressure governs both sides : The resulting A S P ASP A SP is the total pressure remaining to push air through the entire supply duct network plus pull air through the entire return duct network. It is not allocated to the supply side alone.

Step-by-Step ASP Calculation Example

An HVAC contractor in Little Rock is designing a 3.5-ton heat pump system for a two-story home. The engineering parameters are established as follows:

Design Airflow : 3.5 tons × 400 CFM/ton = 1 , 400 CFM 3.5 \text{ tons} \times 400 \text{ CFM/ton} = 1,400 \text{ CFM} 3.5 tons × 400 CFM/ton = 1 , 400 CFM

Selected Air Handler : Manufacturer blower rating table indicates the fan can deliver 1,400 CFM at a rated maximum TESP of 0.50 in. w.g.

System Accessories & Component Losses :

Internal factory wet evaporator coil: Already accounted for in manufacturer air handler cabinet rating ( 0.00 in. w.g. 0.00 \text{ in. w.g.} 0.00 in. w.g. external penalty).

External 1-inch MERV 11 pleated filter: Δ P filter = 0.18 in. w.g. \Delta P_{\text{filter}} = 0.18 \text{ in. w.g.} Δ P filter ​ = 0.18 in. w.g.

10 kW supplemental electric resistance heat pack: Δ P heat = 0.06 in. w.g. \Delta P_{\text{heat}} = 0.06 \text{ in. w.g.} Δ P heat ​ = 0.06 in. w.g.

Supply registers (worst-case bedroom outlet): Δ P supply register = 0.03 in. w.g. \Delta P_{\text{supply register}} = 0.03 \text{ in. w.g.} Δ P supply register ​ = 0.03 in. w.g.

Return air filter grilles: Δ P return grille = 0.03 in. w.g. \Delta P_{\text{return grille}} = 0.03 \text{ in. w.g.} Δ P return grille ​ = 0.03 in. w.g.

Balancing volume dampers: Δ P damper = 0.02 in. w.g. \Delta P_{\text{damper}} = 0.02 \text{ in. w.g.} Δ P damper ​ = 0.02 in. w.g.

Calculation Procedure:

Calculate total component pressure drop: ∑ Δ P = 0.18 + 0.06 + 0.03 + 0.03 + 0.02 = 0.32 in. w.g. \sum \Delta P = 0.18 + 0.06 + 0.03 + 0.03 + 0.02 = 0.32 \text{ in. w.g.} ∑ Δ P = 0.18 + 0.06 + 0.03 + 0.03 + 0.02 = 0.32 in. w.g.

Compute Available Static Pressure: A S P = 0.50 − 0.32 = 0.18 in. w.g. ASP = 0.50 - 0.32 = 0.18 \text{ in. w.g.} A SP = 0.50 − 0.32 = 0.18 in. w.g.

Engineering Analysis : A total of 0.18 in. w.g. of static pressure head remains available to overcome friction and dynamic fitting turbulence across both the supply ductwork runs and the return ductwork runs. If the designer had neglected to deduct the filter, heat strips, and registers, they would have mistakenly assumed 0.50 in. w.g. was available—designing a constricted duct system that would fail to deliver the mandatory 1,400 CFM.

Loading diagram... Airflow Energy & Static Pressure Budget Breakdown