2.4 Gas Laws Applied to HVAC/R Systems

Arkansas HVAC/R Contractor License Exam

Track your progress as you read

Finished sections get a check mark.

1 Arkansas HVAC/R Licensing Law, Board Rules & Administration

1.1 Arkansas HVAC/R Board Authority, Statutes & Definitions 1.2 License Classifications & Capacity Limitations 1.3 Registrant Requirements, Apprenticeship & Experience Verification 1.4 License Renewal, Continuing Education & Disciplinary Actions

2 HVAC Thermodynamics, Psychrometrics & Gas Laws

2.1 Principles of Heat Transfer & Thermodynamic Fundamentals 2.2 Psychrometric Chart Dynamics & Air Properties 2.3 Psychrometric Processes & Air Mixture Calculations 2.4 Gas Laws Applied to HVAC/R Systems

3 Heating and Cooling Load Calculations (Manual J & S)

3.1 ACCA Manual J Design Conditions & Thermal Envelopes 3.2 Peak Cooling Load Calculations: Sensible vs. Latent Heat Gain 3.3 Heating Load Calculations & Infiltration Rates 3.4 ACCA Manual S Equipment Selection & Verification

4 Ductwork Design, Sizing & SMACNA Standards (Manual D)

4.1 ACCA Manual D Airflow Fundamentals & External Static Pressure 4.2 Equal Friction & Static Regain Duct Sizing Methods 4.3 Duct Fittings, Equivalent Length & Dynamic Losses 4.4 SMACNA Duct Construction Standards & Joint Sealing

5 Air Distribution, Balancing & Ventilation Codes

5.1 Supply & Return Air Distribution Hardware (Grilles, Registers, Diffusers) 5.2 System Airflow Testing, Adjusting & Balancing (TAB) 5.3 Ventilation Standards: ASHRAE 62.1, 62.2 & 2021 IMC Ventilation Air

6 Mechanical Refrigeration Cycle & Components

6.1 The Vapor-Compression Refrigeration Cycle 6.2 Compressors & Operating Characteristics 6.3 Condensers & Evaporators 6.4 Metering Devices & Refrigerant Flow Controls 6.5 Refrigerant Line Sizing, Oil Return & Field Piping Practices

7 Refrigerants, Oils & EPA Section 608 Regulations

7.1 Refrigerant Chemistry, ASHRAE Standard 34 & A2L Transition 7.2 Lubricating Oils & System Compatibility 7.3 EPA Section 608 Regulatory Mandates & Recovery Standards 7.4 System Evacuation, Dehydration & Leak Detection

8 Air Conditioning & Heat Pump Systems

8.1 Residential & Commercial Split Systems and Package RTUs 8.2 Air-Source Heat Pumps & The Reversing Valve 8.3 Supplemental & Emergency Heating Systems 8.4 Dual-Fuel & Geothermal (Ground-Source) Heat Pump Systems

9 Gas Furnaces, Combustion Air & Venting (IFGC / IMC)

9.1 Gas Furnace Types, AFUE Ratings & Sequence of Operation 9.2 Gas Burners, Ignition Systems & Flame Safeguard Controls 9.3 Combustion Air Requirements (IFGC Chapter 3 / IMC Chapter 7) 9.4 Flue Gas Venting & Category I-IV Venting Systems

10 Boilers, Hydronics & Fuel Gas Piping

10.1 Hydronic Heating Systems, Low-Pressure Boilers & ASME Code 10.2 Hydronic Distribution, Circulator Pumps & Piping Loops 10.3 Fuel Gas Piping Materials, Sizing & Pressure Testing (IFGC Chapter 4) 10.4 Gas Regulators, Manifold Pressure & Gas Meter Sizing 10.5 Condensate Disposal, Piping Support & Mechanical Insulation

11 Electrical Fundamentals, Motors & Control Circuits

11.1 HVAC Electrical Fundamentals, Ohm's Law & Power Calculations 11.2 Single-Phase & Three-Phase Electric Motors in HVAC 11.3 Low-Voltage Control Circuits & Thermostats

12 National Electrical Code (NEC) for HVAC Equipment

12.1 NEC Article 440: Hermetic Refrigerant Motor-Compressors & Branch Circuits 12.2 Equipment Disconnecting Means & Overcurrent Protective Devices (OCPD) 12.3 Motor Branch Circuit Sizing & Conductor Ampacity (NEC Article 430 & Tables)

13 System Maintenance, Troubleshooting & Safety Standards

13.1 Systematic Mechanical & Electrical Troubleshooting 13.2 Airflow & Refrigerant Charge Diagnostics 13.3 Jobsite Safety, OSHA Standards & Personal Protective Equipment

14 Plan Reading, Estimating & HVAC/R Trade Math

14.1 Mechanical Plan Symbols, Schedules & Abbreviations 14.2 Architectural Scales, Dimensions & Quantity Takeoff 14.3 Material, Labor & Bid Estimating 14.4 Applied HVAC/R Trade Math & Unit Conversions

2.4 Gas Laws Applied to HVAC/R Systems

Key Takeaways Explain This Topic AI

Thermodynamic gas laws strictly require absolute temperature measured in Rankine (°R = °F + 459.67) or Kelvin (K = °C + 273.15); calculating with customary Fahrenheit yields invalid answers.

Absolute pressure (psia) equals gauge pressure (psig) plus atmospheric barometric pressure (14.7 psi at sea level); deep vacuum is quantified in microns of mercury (25,400 microns = 1 in. Hg).

Boyle's Law (P1 · V1 = P2 · V2) governs compressor displacement and compression ratios, establishing that halving vapor volume doubles its absolute pressure at constant temperature.

Charles's Law (V1 / T1 = V2 / T2) and Gay-Lussac's Law (P1 / T1 = P2 / T2) explain nitrogen holding pressure variations during ambient temperature swings and refrigerant cylinder thermal expansion.

Dalton's Law of Partial Pressures dictates that total pressure is the sum of all individual gas partial pressures; non-condensable air trapped in a refrigeration circuit directly increases head pressure, reduces subcooling accuracy, and elevates compressor power consumption.

Last updated: September 2026

2.4 Gas Laws Applied to HVAC/R Systems

Note

Gas Law Foundations in HVAC/R Systems : All vapor-compression refrigeration circuits, fuel gas combustion systems, pneumatic controls, and nitrogen testing procedures are governed by physical gas laws. Gaseous refrigerants, natural gas, propane, air, and nitrogen expand, contract, exert pressure, and absorb energy according to predictable mathematical relationships between pressure, volume, temperature, and molecular density. Understanding these principles is essential for field diagnostics and passing the Arkansas licensing exam.

Absolute Temperature and Pressure Scales

A critical requirement for solving any thermodynamic gas law equation is that all calculations must be performed using absolute temperature and absolute pressure scales . Utilizing standard gauge pressure (psig) or customary Fahrenheit temperatures (°F) directly in gas equations yields mathematically incorrect results.

Absolute Temperature Scales: Rankine and Kelvin

Ordinary temperature scales (Fahrenheit and Celsius) are referenced to the freezing and boiling points of water. However, thermal molecular motion does not cease at 0°F or 0°C. Molecular motion ceases entirely only at Absolute Zero ( − 459.67 ∘ F -459.67^\circ\text{F} − 459.6 7 ∘ F or − 273.15 ∘ C -273.15^\circ\text{C} − 273.1 5 ∘ C ).

The Rankine Scale ( ∘ R ^\circ\text{R} ∘ R ) : The absolute thermodynamic temperature scale corresponding to the Fahrenheit system: ∘ R = ∘ F + 459.67 ≈ ∘ F + 460 ^\circ\text{R} = ^\circ\text{F} + 459.67 \approx ^\circ\text{F} + 460 ∘ R = ∘ F + 459.67 ≈ ∘ F + 460

The Kelvin Scale ( K K K ) : The absolute thermodynamic temperature scale corresponding to the Celsius system: K = ∘ C + 273.15 K = ^\circ\text{C} + 273.15 K = ∘ C + 273.15

Rule of Practice : If an exam problem states that gas inside a cylinder is heated from 40°F to 80°F, the temperature has not doubled. In absolute terms, the temperature has only increased from 500 R 500\text{ R} 500 R ( 40 + 460 40 + 460 40 + 460 ) to 540 R 540\text{ R} 540 R ( 80 + 460 80 + 460 80 + 460 ), a modest increase of 8% .

Absolute Pressure vs. Gauge Pressure

Pressure is defined as force applied perpendicular to a surface per unit area ( P = F / A P = F / A P = F / A ). In the U.S. Customary system, pressure is measured in pounds per square inch (psi).

Atmospheric Pressure ( P atm P_{\text{atm}} P atm ​ ) : The weight of the Earth's atmosphere exerting force on the Earth's surface. At sea level under standard temperature conditions (59°F), atmospheric pressure equals 14.696 psia ≈ 14.7 psia 14.696\text{ psia} \approx 14.7\text{ psia} 14.696 psia ≈ 14.7 psia (or 29.921 inches of mercury 29.921\text{ inches of mercury} 29.921 inches of mercury ). Atmospheric pressure decreases with increasing altitude.

Gauge Pressure (psig) : Pressure measured relative to local atmospheric pressure. A standard manifold gauge reads 0 psig 0\text{ psig} 0 psig when open to the atmosphere.

Absolute Pressure (psia) : Pressure measured relative to a perfect, complete vacuum (0 psia): P psia = P psig + P atm = P psig + 14.7 P_{\text{psia}} = P_{\text{psig}} + P_{\text{atm}} = P_{\text{psig}} + 14.7 P psia ​ = P psig ​ + P atm ​ = P psig ​ + 14.7 +-------------------------------------------------------------+ 114.7 psia (100 psig)

  • | |
  • | GAUGE PRESSURE (psig) |
  • | |
  • +=============================================================+ 14.7 psia (0 psig - Atmospheric Baseline)
  • | VACUUM RANGE (in. Hg) |

+-------------------------------------------------------------+ 0 psia (-29.92 in. Hg / 0 Microns / Absolute Zero)

Vacuum Measurement: Inches of Mercury and Microns

Pressures below atmospheric pressure fall into the vacuum range :

Inches of Mercury Vacuum (in. Hg vac) : Standard Bourdon tube manifold gauges measure vacuum from 0 in. Hg 0\text{ in. Hg} 0 in. Hg (atmospheric) down to − 29.92 in. Hg -29.92\text{ in. Hg} − 29.92 in. Hg (perfect vacuum).

The Micron : Mechanical dial gauges lack the sensitivity needed to verify deep evacuation. Technicians use electronic digital vacuum gauges calibrated in microns (one millionth of a meter of mercury column height, or 0.001 mm Hg 0.001\text{ mm Hg} 0.001 mm Hg ): 1 inch of mercury = 25 , 400 microns 1\text{ inch of mercury} = 25,400\text{ microns} 1 inch of mercury = 25 , 400 microns 29.92 inches of mercury (Atmospheric Pressure) = 760 , 000 microns 29.92\text{ inches of mercury (Atmospheric Pressure)} = 760,000\text{ microns} 29.92 inches of mercury (Atmospheric Pressure) = 760 , 000 microns Industry Deep Evacuation Standard (EPA / Manufacturers) = 500 microns or below \text{Industry Deep Evacuation Standard (EPA / Manufacturers)} = \mathbf{500\text{ microns or below}} Industry Deep Evacuation Standard (EPA / Manufacturers) = 500 microns or below

  • The Classical Gas Laws in HVAC/R Systems
  • 1. Boyle's Law: Pressure-Volume Relationship (Constant Temperature)

Formulated by Robert Boyle in 1662, Boyle's Law states that the absolute pressure of a given mass of gas is inversely proportional to its volume, provided the temperature remains constant within a closed system. P 1 × V 1 = P 2 × V 2 or P × V = Constant P_1 \times V_1 = P_2 \times V_2 \quad \text{or} \quad P \times V = \text{Constant} P 1 ​ × V 1 ​ = P 2 ​ × V 2 ​ or P × V = Constant

If the volume occupied by a gas is halved, its absolute pressure doubles; conversely, expanding the volume to twice its size cuts the absolute pressure in half.

Application: Positive-Displacement Compressors and Compression Ratio

Reciprocating, scroll, rotary, and screw compressors operate on Boyle's Law. A reciprocating compressor draws in a large volume of low-pressure suction gas during the downward piston stroke. On the upward compression stroke, the piston reduces cylinder volume, forcing refrigerant vapor into a tiny clearance volume, raising its pressure until it forces the discharge reed valve open.

The Compression Ratio (CR) measures the degree of mechanical compression: Compression Ratio (CR) = P discharge (psia) P suction (psia) = P head (psig) + 14.7 P suction (psig) + 14.7 \text{Compression Ratio (CR)} = \frac{P_{\text{discharge (psia)}}}{P_{\text{suction (psia)}}} = \frac{P_{\text{head (psig)}} + 14.7}{P_{\text{suction (psig)}} + 14.7} Compression Ratio (CR) = P suction (psia) ​ P discharge (psia) ​ ​ = P suction (psig) ​ + 14.7 P head (psig) ​ + 14.7 ​

Caution

Compression Ratio Exam Trap : Never calculate compression ratio using gauge pressures (psig)! If an R-410A system operates at 118 psig 118\text{ psig} 118 psig suction and 385 psig 385\text{ psig} 385 psig discharge, calculating 385 / 118 = 3.26 385 / 118 = 3.26 385/118 = 3.26 is completely wrong. You must add 14.7 14.7 14.7 to both values: CR = ( 385 + 14.7 ) / ( 118 + 14.7 ) = 399.7 / 132.7 = 3.01 : 1 \text{CR} = (385 + 14.7) / (118 + 14.7) = 399.7 / 132.7 = \mathbf{3.01:1} CR = ( 385 + 14.7 ) / ( 118 + 14.7 ) = 399.7/132.7 = 3.01 : 1 .

2. Charles's Law: Volume-Temperature Relationship (Constant Pressure)

Formulated by Jacques Charles in 1787, Charles's Law states that the volume of a given mass of gas is directly proportional to its absolute temperature, provided the pressure remains constant. V 1 T 1 = V 2 T 2 \frac{V_1}{T_1} = \frac{V_2}{T_2} T 1 ​ V 1 ​ ​ = T 2 ​ V 2 ​ ​

Where T 1 T_1 T 1 ​ and T 2 T_2 T 2 ​ are in degrees Rankine ( ∘ F + 460 ^\circ\text{F} + 460 ∘ F + 460 ).

Application: Combustion Flue Gas Buoyancy

Charles's Law governs Category I natural draft combustion venting (gas furnaces and water heaters). When fuel gas burns, combustion products heat to 350°F–450°F. According to Charles's Law, heating gas causes it to expand significantly. Because the mass of gas now occupies a larger volume, its density decreases. The surrounding cooler, denser atmospheric air exerts a buoyant upward force, causing flue gases to rise naturally up the chimney flue pipe and vent safely outdoors.

3. Gay-Lussac's Law: Pressure-Temperature Relationship (Constant Volume)

Formulated by Joseph Louis Gay-Lussac in 1802, Gay-Lussac's Law (often termed the Pressure Law) states that the absolute pressure of a given mass of gas is directly proportional to its absolute temperature, provided the volume of the container remains fixed. P 1 T 1 = P 2 T 2 \frac{P_1}{T_1} = \frac{P_2}{T_2} T 1 ​ P 1 ​ ​ = T 2 ​ P 2 ​ ​

Where P P P is in psia and T T T is in degrees Rankine ( ∘ F + 460 ^\circ\text{F} + 460 ∘ F + 460 ).

Application: Nitrogen Pressure Testing & Cylinder Safety

When an HVAC technician pressurizes copper linesets with dry nitrogen to test for leaks, the piping represents a rigid, fixed-volume container ( V 1 = V 2 V_1 = V_2 V 1 ​ = V 2 ​ ). If nitrogen is charged to 300 psig 300\text{ psig} 300 psig during a hot afternoon at 95°F ( 555 R 555\text{ R} 555 R ), and the technician returns the next morning when the temperature has dropped to 55°F ( 515 R 515\text{ R} 515 R ), Gay-Lussac's Law dictates that the pressure must fall: P 2 = P 1 × ( T 2 T 1 ) = ( 300 + 14.7 ) × ( 515 555 ) = 314.7 × 0.9279 = 292.0 psia = 277.3 psig P_2 = P_1 \times \left(\frac{T_2}{T_1}\right) = (300 + 14.7) \times \left(\frac{515}{555}\right) = 314.7 \times 0.9279 = 292.0\text{ psia} = \mathbf{277.3\text{ psig}} P 2 ​ = P 1 ​ × ( T 1 ​ T 2 ​ ​ ) = ( 300 + 14.7 ) × ( 555 515 ​ ) = 314.7 × 0.9279 = 292.0 psia = 277.3 psig

A pressure drop from 300 psig 300\text{ psig} 300 psig to 277 psig 277\text{ psig} 277 psig under these conditions is purely the result of thermal contraction, not a physical piping leak.

4. The Combined Gas Law

Combining Boyle's, Charles's, and Gay-Lussac's Laws yields the Combined Gas Law , which correlates simultaneous variations in pressure, volume, and temperature for a fixed mass of gas: P 1 × V 1 T 1 = P 2 × V 2 T 2 \frac{P_1 \times V_1}{T_1} = \frac{P_2 \times V_2}{T_2} T 1 ​ P 1 ​ × V 1 ​ ​ = T 2 ​ P 2 ​ × V 2 ​ ​

5. The Ideal Gas Law

The Ideal Gas Law introduces the quantity of gas molecules, expressed in moles ( n n n ): P × V = n × R × T P \times V = n \times R \times T P × V = n × R × T

Where:

  • P P P = Absolute pressure ( lb / ft 2 \text{lb}/\text{ft}^2 lb / ft 2 or psia)
  • V V V = Volume ( ft 3 \text{ft}^3 ft 3 )
  • n n n = Number of moles of gas ( m / M m / M m / M )

R R R = Universal gas constant ( 10.73 psia ⋅ ft 3 / [ lbmol ⋅ ∘ R ] 10.73\text{ psia}\cdot\text{ft}^3/[\text{lbmol}\cdot^\circ\text{R}] 10.73 psia ⋅ ft 3 / [ lbmol ⋅ ∘ R ] ) or individual gas constant ( R air = 53.35 ft ⋅ lb / [ lb ⋅ ∘ R ] R_{\text{air}} = 53.35\text{ ft}\cdot\text{lb}/[\text{lb}\cdot^\circ\text{R}] R air ​ = 53.35 ft ⋅ lb / [ lb ⋅ ∘ R ] )

  • T T T = Absolute temperature in Rankine ( ∘ R ^\circ\text{R} ∘ R )
  • Dalton's Law of Partial Pressures: Non-Condensable Refrigerant Contamination

Formulated by John Dalton in 1801, Dalton's Law of Partial Pressures states that the total pressure exerted by a mixture of non-reacting gases is equal to the sum of the partial pressures that each individual gas would exert if it alone occupied the entire volume at the same temperature: P total = P 1 + P 2 + P 3 + ⋯ + P n P_{\text{total}} = P_1 + P_2 + P_3 + \dots + P_n P total ​ = P 1 ​ + P 2 ​ + P 3 ​ + ⋯ + P n ​

Atmospheric Partial Pressures

In sea-level atmospheric air at 14.7 psia 14.7\text{ psia} 14.7 psia :

Nitrogen ( 78.08 % 78.08\% 78.08% ): P N 2 = 0.7808 × 14.7 = 11.48 psia P_{N_2} = 0.7808 \times 14.7 = 11.48\text{ psia} P N 2 ​ ​ = 0.7808 × 14.7 = 11.48 psia

Oxygen ( 20.95 % 20.95\% 20.95% ): P O 2 = 0.2095 × 14.7 = 3.08 psia P_{O_2} = 0.2095 \times 14.7 = 3.08\text{ psia} P O 2 ​ ​ = 0.2095 × 14.7 = 3.08 psia

Argon & Water Vapor ( 0.97 % 0.97\% 0.97% ): P other = 0.0097 × 14.7 = 0.14 psia P_{\text{other}} = 0.0097 \times 14.7 = 0.14\text{ psia} P other ​ = 0.0097 × 14.7 = 0.14 psia

Total Pressure: 11.48 + 3.08 + 0.14 = 14.70 psia 11.48 + 3.08 + 0.14 = \mathbf{14.70\text{ psia}} 11.48 + 3.08 + 0.14 = 14.70 psia

Dalton's Law in Refrigeration Diagnostics: Non-Condensable Gases

Dalton's Law is the diagnostic key to identifying non-condensable gas contamination in refrigeration circuits. Non-condensables consist of atmospheric air, nitrogen, or carbon dioxide inadvertently introduced due to improper evacuation, leaking suction lines, or contaminated charging hoses.

Inside an operational condenser, refrigerant vapor desuperheats and condenses into liquid at its saturation pressure corresponding to the condensing temperature. However, atmospheric air and nitrogen have critical temperatures well below − 150 ∘ F -150^\circ\text{F} − 15 0 ∘ F and cannot condense at normal operating temperatures. Consequently, non-condensables collect as trapped gas pockets in the upper coils of the condenser, occupying volume and exerting their own independent partial pressure. P gauge (head pressure) = P refrigerant (saturation) + P air (non-condensable) P_{\text{gauge (head pressure)}} = P_{\text{refrigerant (saturation)}} + P_{\text{air (non-condensable)}} P gauge (head pressure) ​ = P refrigerant (saturation) ​ + P air (non-condensable) ​ +-----------------------------------------------------------------------------------+

  • | Symptoms of Non-Condensable Gas Contamination |
  • +-----------------------------------------------------------------------------------+
  • | 1. Abnormally High Head Pressure | High discharge gauge reading above PT chart |
  • | 2. Fluttering High-Side Gauge | Pressure needle vibrates rapidly on manifold |
  • | 3. High Discharge Temperatures | Compressor runs excessively hot; oil breakdown|
  • | 4. Increased Amp Draw | Compressor motor overworks against high head |
  • | 5. Loss of System Cooling | Reduced evaporator feed; high power bills |
  • +-----------------------------------------------------------------------------------+
  • Diagnostic Field Test for Non-Condensable Gases

Disconnect compressor electrical power to stop operation.

Force the outdoor condenser fan to run continuously (or let the system stand idle overnight in a shaded space) until the entire condenser coil temperature equalizes with the outdoor ambient dry-bulb temperature.

Measure outdoor ambient dry-bulb temperature accurately using a calibrated digital thermometer placed at the condenser inlet.

Connect a precision pressure gauge to the high-side service port and measure static system pressure.

Look up the expected saturation pressure on a Refrigerant Pressure-Temperature (PT) chart corresponding to the measured ambient temperature.

Evaluation : If the measured gauge pressure is higher than the PT chart saturation pressure (by more than 3 to 5 psi 3\text{ to } 5\text{ psi} 3 to 5 psi ), non-condensables are present in the system . The system must be recovered, evacuated below 500 microns, and recharged with virgin refrigerant.

Avogadro's Law and Fuel Gas Combustion Calculations

Avogadro's Law states that equal volumes of all ideal gases at identical temperature and pressure contain an equal number of molecules ( V ∝ n V \propto n V ∝ n ).

In HVAC fuel gas systems (governed by the International Fuel Gas Code - IFGC), Avogadro's Law establishes the volumetric air requirements for complete combustion:

Natural Gas (Methane - CH 4 \text{CH}_4 CH 4 ​ ) : CH 4 + 2 O 2 → CO 2 + 2 H 2 O + Heat \text{CH}_4 + 2\text{O}_2 \rightarrow \text{CO}_2 + 2\text{H}_2\text{O} + \text{Heat} CH 4 ​ + 2 O 2 ​ → CO 2 ​ + 2 H 2 ​ O + Heat One cubic foot of methane requires 2 cubic feet of pure oxygen . Because atmospheric air contains only 20.95% oxygen, supplying 2 cu ft of oxygen requires 2 / 0.2095 = 9.55 cu ft of air 2 / 0.2095 = \mathbf{9.55\text{ cu ft of air}} 2/0.2095 = 9.55 cu ft of air (nominally 10 cu ft of air per cu ft of natural gas 10\text{ cu ft of air per cu ft of natural gas} 10 cu ft of air per cu ft of natural gas ).

Liquefied Petroleum Gas (Propane - C 3 H 8 \text{C}_3\text{H}_8 C 3 ​ H 8 ​ ) : C 3 H 8 + 5 O 2 → 3 CO 2 + 4 H 2 O + Heat \text{C}_3\text{H}_8 + 5\text{O}_2 \rightarrow 3\text{CO}_2 + 4\text{H}_2\text{O} + \text{Heat} C 3 ​ H 8 ​ + 5 O 2 ​ → 3 CO 2 ​ + 4 H 2 ​ O + Heat One cubic foot of propane requires 5 cubic feet of pure oxygen , requiring 5 / 0.2095 = 23.87 cu ft of air 5 / 0.2095 = \mathbf{23.87\text{ cu ft of air}} 5/0.2095 = 23.87 cu ft of air (nominally 24 to 25 cu ft of air per cu ft of propane 24\text{ to } 25\text{ cu ft of air per cu ft of propane} 24 to 25 cu ft of air per cu ft of propane ).

If air supply is restricted below these stoichiometric volume ratios, incomplete combustion occurs, producing deadly carbon monoxide (CO) , aldehydes, and soot.

  • Step-by-Step Worked Engineering Calculations
  • Calculation 1: Compression Ratio of an R-410A Heat Pump

Problem : An R-410A split-system heat pump operates with a suction pressure of 125 psig 125\text{ psig} 125 psig and a liquid discharge head pressure of 395 psig 395\text{ psig} 395 psig . Assuming standard atmospheric pressure of 14.7 psia 14.7\text{ psia} 14.7 psia , calculate the absolute compression ratio of the compressor.

Step 1: Convert suction pressure from gauge to absolute (psia) P suction (psia) = 125 psig + 14.7 = 139.7 psia P_{\text{suction (psia)}} = 125\text{ psig} + 14.7 = 139.7\text{ psia} P suction (psia) ​ = 125 psig + 14.7 = 139.7 psia

Step 2: Convert discharge pressure from gauge to absolute (psia) P discharge (psia) = 395 psig + 14.7 = 409.7 psia P_{\text{discharge (psia)}} = 395\text{ psig} + 14.7 = 409.7\text{ psia} P discharge (psia) ​ = 395 psig + 14.7 = 409.7 psia

Step 3: Calculate compression ratio (CR) CR = P discharge (psia) P suction (psia) = 409.7 psia 139.7 psia = 2.93 : 1 \text{CR} = \frac{P_{\text{discharge (psia)}}}{P_{\text{suction (psia)}}} = \frac{409.7\text{ psia}}{139.7\text{ psia}} = \mathbf{2.93:1} CR = P suction (psia) ​ P discharge (psia) ​ ​ = 139.7 psia 409.7 psia ​ = 2.93 : 1

Result : The operating compression ratio is 2.93:1 .

Calculation 2: Nitrogen Holding Pressure Temperature Compensation

Problem : A newly installed VRF copper piping network is pressurized with dry nitrogen to 400 psig 400\text{ psig} 400 psig at an afternoon temperature of 90°F. The following morning, the line temperature has dropped to 60°F. The pressure gauge now reads 373 psig 373\text{ psig} 373 psig . Determine if the system is leaking or if the pressure change is entirely thermal.

Step 1: Convert initial and final temperatures to absolute Rankine T 1 = 90 ∘ F + 460 = 550 R and T 2 = 60 ∘ F + 460 = 520 R T_1 = 90^\circ\text{F} + 460 = 550\text{ R} \quad \text{and} \quad T_2 = 60^\circ\text{F} + 460 = 520\text{ R} T 1 ​ = 9 0 ∘ F + 460 = 550 R and T 2 ​ = 6 0 ∘ F + 460 = 520 R

Step 2: Convert initial pressure to absolute psia P 1 = 400 psig + 14.7 = 414.7 psia P_1 = 400\text{ psig} + 14.7 = 414.7\text{ psia} P 1 ​ = 400 psig + 14.7 = 414.7 psia

Step 3: Apply Gay-Lussac's Law to calculate expected pressure ( P 2 P_2 P 2 ​ ) P 2 = P 1 × ( T 2 T 1 ) = 414.7 psia × ( 520 R 550 R ) = 414.7 × 0.94545 = 392.09 psia P_2 = P_1 \times \left(\frac{T_2}{T_1}\right) = 414.7\text{ psia} \times \left(\frac{520\text{ R}}{550\text{ R}}\right) = 414.7 \times 0.94545 = 392.09\text{ psia} P 2 ​ = P 1 ​ × ( T 1 ​ T 2 ​ ​ ) = 414.7 psia × ( 550 R 520 R ​ ) = 414.7 × 0.94545 = 392.09 psia

Step 4: Convert expected absolute pressure back to gauge pressure (psig) P 2 (psig) = 392.09 psia − 14.7 = 377.39 psig P_{2\text{ (psig)}} = 392.09\text{ psia} - 14.7 = \mathbf{377.39\text{ psig}} P 2 (psig) ​ = 392.09 psia − 14.7 = 377.39 psig

Diagnostic Conclusion : The expected gauge pressure due purely to thermal contraction is 377.4 psig 377.4\text{ psig} 377.4 psig . Because the actual measured pressure is 373 psig 373\text{ psig} 373 psig ( 4.4 psi 4.4\text{ psi} 4.4 psi lower than expected), a minor physical piping leak is present .

Calculation 3: Trapped Non-Condensable Partial Pressure

Problem : An idle R-134a refrigeration system stands in a 70°F mechanical room overnight. The technician connects a gauge manifold and measures a static pressure of 85.0 psig 85.0\text{ psig} 85.0 psig . According to an R-134a PT chart, pure saturated R-134a at 70°F exhibits a vapor pressure of 71.1 psig 71.1\text{ psig} 71.1 psig . What is the partial pressure exerted by non-condensable gases in this system? P non-condensables = P measured − P saturation (PT chart) = 85.0 psig − 71.1 psig = 13.9 psi \begin{aligned}

  • P_{\text{non-condensables}} &= P_{\text{measured}} - P_{\text{saturation (PT chart)}} \\
  • &= 85.0\text{ psig} - 71.1\text{ psig} = \mathbf{13.9\text{ psi}}

\end{aligned} P non-condensables ​ ​ = P measured ​ − P saturation (PT chart) ​ = 85.0 psig − 71.1 psig = 13.9 psi ​

Result : Trapped non-condensable air is exerting 13.9 psi of excess partial pressure inside the refrigeration circuit.

Master Summary Table of Governing Gas Laws

Gas Law Name Mathematical Equation Held Constant Primary HVAC Application

Boyle's Law P 1 V 1 = P 2 V 2 P_1 V_1 = P_2 V_2 P 1 ​ V 1 ​ = P 2 ​ V 2 ​ Temperature ( T T T ) Compressor cylinder compression; compression ratio

Charles's Law V 1 T 1 = V 2 T 2 \frac{V_1}{T_1} = \frac{V_2}{T_2} T 1 ​ V 1 ​ ​ = T 2 ​ V 2 ​ ​ Pressure ( P P P ) Combustion flue gas buoyancy; chimney natural draft

Gay-Lussac's Law P 1 T 1 = P 2 T 2 \frac{P_1}{T_1} = \frac{P_2}{T_2} T 1 ​ P 1 ​ ​ = T 2 ​ P 2 ​ ​ Volume ( V V V ) Nitrogen pressure testing; recovery cylinder heating

Combined Gas Law P 1 V 1 T 1 = P 2 V 2 T 2 \frac{P_1 V_1}{T_1} = \frac{P_2 V_2}{T_2} T 1 ​ P 1 ​ V 1 ​ ​ = T 2 ​ P 2 ​ V 2 ​ ​ Gas mass ( m m m ) Combined multi-variable gas expansion and compression

Ideal Gas Law P V = n R T P V = n R T P V = n RT Universal ( R R R ) Exact thermodynamic modeling of superheated gases

Dalton's Law P t = P 1 + P 2 + ⋯ + P n P_t = P_1 + P_2 + \dots + P_n P t ​ = P 1 ​ + P 2 ​ + ⋯ + P n ​ Temperature, Volume Non-condensable air contamination in condenser coils

Avogadro's Law V ∝ n V \propto n V ∝ n Pressure, Temperature Combustion air stoichiometry for natural gas and LP

Loading diagram... Thermodynamic Gas Laws Applied Across HVAC/R Equipment